CyberPower BR450ELCD Handleiding
CyberPower
UPS
BR450ELCD
Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower BR450ELCD (2 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 32 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/2
BR450ELCD/BR650ELCD/BR850ELCD
User’s Manual
K01-0000056-00
SAFETY WARNINGS
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to unpack,
install, or operate your UPS.
This equipment can be operated by any individuals with no previous training.
The socket-outlet shall be installed near the equipment and easily accessible.
During the installation of this equipment it should be assured that the sum of the leakage currents of the
UPS and the connected loads does not exceed 3.5mA.
Attention, hazardous through electric shock. Also with disconnection of this unit from the mains,
hazardous voltage still may be accessible through supply from battery. The battery supply should be
therefore disconnected in the plus and minus pole at the quick connectors of the battery when
maintenance or service work inside the UPS is necessary.
Do not dispose of batteries in a fire, the battery may explode.
Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes.
INSTALLING YOUR UPS SYSTEM
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
(1)UPS Unit¯ ¯1; (1)Phone Line 1;(3)USB Cable¯1;(4)User Manual¯1;(5)Management software
Disk¯1;(6)Green Power Technology description¯ ¯1;(7)Battery Charger 1;(8)Cable Collector¯1
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Insure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS
unit’s rated capacity (450VA/270W for BR450ELCD, 650VA/390W for BR650ELCD, 850VA/510W for
BR850ELCD). If rated unit capacities are exceeded, an overload condition may occur and cause the
UPS unit to shut down or the fuse blow.
2. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert
Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only
calculates the maximum amount of VA that the equipment can use, not what is typically used by the
equipment at any one time. Users should expect usage requirements to be approximately 60% of
below value.
TO ESTIMATE POWER REQUIREMENTS
1. Watts (W) x 1.67 = VA or Amps (A) x 230 = VA
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual
requirements. There are many factors that can affect the amount of power that your computer system
will require. Suggest the total load to be placed on the battery-powered outlets should not exceed
80% of the unit’s capacity.
HARDWARE INSTALLATION GUIDE
Before installation, please read and understand the following instructions:
1. Placement
The UPS must be installed in a protected environment away from heat- emitting appliances such
as a radiator or heat register. Do not install this product where excessive moisture is present.
2. Ventilation
The location should provide adequate air flow around the UPS with one inch minimum clearance
on all sides for proper ventilation.
3. Charge the Battery
Your new UPS may be used immediately upon receipt. However charge loss may occur during
shipping and storage. So charging the battery for at least 8 hours is recommended to insure that
the battery is fully charged. (To recharge the battery, simply leave the unit plugged into an AC
outlet.)
This UPS can be charged even when UPS is not turn on.
4. Connect to AC
Use power cord to connect
the UPS to a wall outlet. Please avoid
using extension cords and adapter
plugs. (To maintain optimal battery
charge, leave the UPS plugged in at
all times.)
5. Connect the Load
Connect the equipment to your UPS
outlets. The IEC power cord coming
with the unit are used to connect your
computer and monitor to the UPS.
Items such as copiers, laser
printers, vacuums, space heaters,
or other large electrical devices
SHOULD NOT be connected to the
UPS. Please make sure that the total
loads of your equipments are less than the maximum total power load of your UPS.
6. Connect to Computer
Install your software and accessories. To use the software, simply use the USB cable to connect
the UPS unit and your computer.
BASIC OPERATION
1. Power On/Off Switch
Press the power switch to turn the UPS ON or OFF.
2. LCD Function Selected Switch
Press the LCD function selected switch to know the UPS status.
3. LCD Display
The LCD will display the UPS status including input voltage, output voltage, runtime, percentage of
load and battery…etc.
4. Communication Protection Ports RJ11/RJ45
Communication protection ports will protect any standard modem, fax, telephone line, or network
cable from surge and spikes.
5. Battery Charger port
Charge external AA/AAA battery via battery charger port with battery charger.
6. AC outlet
The UPS provides 3 outlets for connected equipment to insure temporary uninterrupted operation
during a power failure and against surges and spikes and another 3 outlets against surges and spikes
only.
7. USB Port to PC
This port allows connection and communication
from the USB port on the computer to the UPS
unit. The UPS communicates its status to the
PowerPanel® Personal Edition software. This
interface is also compatible with the UPS service
provided by Windows NT, Windows 2000,
Windows XP, Windows Vista. Mac OSX, Linux.
8. Input Circuit Breaker
The Circuit Breaker provides optimal overload protection.
9 Power on LED
The power on LED lights up when the UPS is ON.
10 Cable Collector
Collect the cables connected from the AC outlets in the cable collector.
11 Battery Charger
Put external AA/AAA batteries into the battery charger for charge.
Functional Test
AC Mode
The UPS delivers power to the loads derived from the utility and maintains proper battery charge. It also
regulates the output voltage to within a narrow range.
On-Battery Mode
The UPS operates on battery when the line voltage or frequency has fallen outside the limits. Local
users are alerted to this mode of operation by visual and audible indicators. The UPS provides power to
the load from the battery and through its inverter and the output voltage and frequency of the UPS are
regulated within a narrow range
1. Switch On
Press the power switch on the top panel then the “power on” LED will light up.
2. Switch Off
Press again the power switch, the “power on” LED on the top panel will go off.
3. Cold Start / Start on Battery:
This UPS can be turned on even when AC is not present.
Press the power switch on the top panel then the “power on” LED will light up.
ROUTINE MAINTENANCE AND STORAGE
ROUTINE MAINTENANCE
1. Use dry soft clothes to clean the top panel and plastic parts. Do not use any detergent that contains
alcoholic ingredient.
2. The expected lifetime of the battery is around 3 years. Improper operation and harsh environment
will reduce the actual lifetime.
3. Unplug the UPS from power inlet if the UPS will not operate for long period of time.
STORAGE
1. First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables
connected the UPS to avoid battery drain.
2. The UPS should be stored in a cool dry location.
3. Make sure the battery is fully charged before the UPS is stored.
4. For extended storage in moderate climates, the battery should be charged for 12 hours every 3
months by plugging the power cord into the wall receptacle. Repeat it every 2 months in high
temperature locations.
TROUBLE SHOOTING
Problem Possible Cause Solution
The battery is not fully
charged. Recharge the battery by leaving the UPS
plugged in.
The UPS does
not perform
expected
runtime. The battery is slightly worn
out. Contact CyberPower Systems at
service@cyberpower-eu.com
The on/off switch is
designed to prevent
damage by rapidly turning it
off and on.
Turn the UPS off. Wait 10 seconds and
then turn the UPS on.
The unit is not connected to
an AC outlet. The unit must be connected to a
220-240V 50/60Hz outlet.
The battery is worn out. Contact CyberPower Systems at
service@cyberpower-eu.com
The UPS will not
turn on.
Mechanical problem. Contact CyberPower Systems at
service@cyberpower-eu.com
The circuit breaker is
tripped due to overload.
Turn the UPS off and unplug at least one
piece connected equipment. Unplug the
power cord of the UPS then remove the
fuse compartment beneath the power inlet
of the UPS and replace the blown fuse
with a spare one. Lock the compartment
back to the UPS. Connect power cord
then turn the UPS on. Make sure that your
spare fuse meets the specification.
The battery is discharged Allow the unit to recharge for at least 4
hours.
Outlets do not
provide power to
equipment
The unit has been damaged
by a surge or spike. Contact CyberPower Systems at
service@cyberpower-eu.com
The USB cable is not
connected.
Connect the USB cable to the UPS unit
and an open serial port on the back of
the computer. You must use the cable
that came with the unit.
The USB cable is
connected to the wrong
port. Try another USB port of your computer.
The unit is not providing
battery power.
Shutdown your computer and turn the
UPS off. Wait 10 seconds and turn the
UPS back on. This should reset the unit.
PowerPanel®
Personal Edition
is inactive (all
icons are gray).
The serial cable is not the
cable that was provided with
the unit.
You must use the cable included with the
unit for the software.
TECHNICAL SPECIFICATIONS
Model BR 450ELCD BR 650ELCD BR 850ELCD
Capacity (VA) 450VA 650VA 850VA
Capacity (Watts) 270W 390W 510W
Input
Input Voltage Range 165-270Vac
Frequency Range 50/60 Hz+/-3Hz (Auto Sensing)
Output
On Battery Output
Voltage Simulated Sine Wave at 230Vac +/-10%
On Battery Output
Frequency 50/60 Hz +/-1%
Overload Protection Yes
Physical
Total # of UPS
Receptacles Schuko*6 (3 for battery backup and surge ;3 for surge )
Dimensions(mm) 271(L) x160.7(W) x113.6(H)
Weight (kg) 4.4 5.5 6.4
Battery
Sealed Maintenance
Free Lead Acid Battery 12V / 4.5Ah p2-x1 12V / 7Ah p2-x1 12V / 9Ah p2-x1
Typical Recharge Time 8 Hours
Warning Diagnostics
Indicators Power On
Audible Alarms On Battery, Low Battery, Overload
Environmental
Operating Temperature +32°F to 104°F ( 0°C to 40°C )
Operating Relative
Humidity 0 to 85% NON-CONDENSING
Communication
PowerPanel® Personal
Edition Software Windows2000/NT/XP/Server 2003/Vista/Mac OSX,Linux
Management
Auto-Charger Yes
Auto-Restart Yes
USB Interface Yes
Other Features
Green Power Yes (Energy saving technology)
Batter Charger External AAA/AA battery charger, connection via USB charger
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
LCD Indication
Line mode
UPS Status Display Capacity Display Digital Value Display
Select SW
Press Load
Cap.
Battery
Cap.
Input
Voltage
Output
Voltage
Run
Time
%
of Load
%
of Batt.
Initial V X -- X V X V
1st V X -- X V X V
2nd V X -- X V X V
3rd V X -- X X V V
4th V X -- X V X V
5th(Return) V X -- X V X V
Press >3sec
(Sound Disable) V X V X -- -- -- -- -- -- --
Press >3sec
again
(Sound Enable)
V X X X -- -- -- -- -- -- --
(Overload) V X -- V -- -- -- -- -- -- --
“V” : Illuminated, “X” : Not Illuminated, “--“ : Either
Battery mode
UPS Status Display Capacity Display Digital Value Display
Select SW
Press Load
Cap. Battery
Cap. Input
Voltage Output
Voltage Run
Time %
of Load %
of Batt.
Initial X V -- X X V V
1st X V -- X X V V
2nd X V -- X V X V
3rd X V -- X X V V
4th X V -- X X V V
5th(Return) X V -- X X V V
Press >3sec
(Sound Disable) X V V X -- -- -- -- -- -- --
Press >3sec
again
(Sound Enable)
X V X X -- -- -- -- -- -- --
(Overload) X V -- V -- -- -- -- -- -- --
“V” : Illuminated, “X” : Not Illuminated, “--“ : Either
For more information, visit eu.cyberpowersystems.com or contact
CyberPower Systems B.V.
Flight Forum 3545 5657DW Eindhoven The Netherlands
Tel: +31 40 2348170, E-MAIL: sales@cyberpower-eu.com
CyberPower Systems Inc. (USA) 4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A.
Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: sales@cyberpowersystems.com
Entire contents copyright ©2008 CyberPower Systems B.V., All rights reserved. Reproduction in whole
or in part without permission is prohibited. PowerPanel
® Personal Edition is the trademark of
CyberPower Systems Inc.
CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in
design, assembly, materials and workmanship for two years ( battery is only one year) from the date of
original purchase. Any warranty services, please contact your local dealers or distributors.
Product specificaties
Merk: | CyberPower |
Categorie: | UPS |
Model: | BR450ELCD |
Kleur van het product: | Zwart |
Gewicht: | 5500 g |
LED-indicatoren: | Ja |
Aantal USB 2.0-poorten: | 1 |
Aantal Ethernet LAN (RJ-45)-poorten: | 1 |
Geluidsalarm(en): | Ja |
Responstijd: | 6 ms |
Uitgangsvermogen: | 390 W |
Accu/Batterij oplaadtijd: | 8 uur |
Temperatuur bij opslag: | -15 - 45 °C |
Frequentie: | 47/63 Hz |
Compatibele besturingssystemen: | Windows 98/Me/2000/NT/XP/Vista, Linux |
Mac-compatibiliteit: | Ja |
Afmetingen (B x D x H): | 160.7 x 271 x 113.6 mm |
Modem (RJ-11) poort: | 1 |
Bedrijfstemperatuur (T-T): | 0 - 40 °C |
Relatieve vochtigheid in bedrijf (V-V): | 0 - 95 procent |
Batterijtechnologie: | Sealed Lead Acid (VRLA) |
Output power capacity: | 0.65 kVA |
Netspanning, in bedrijf: | 230 V |
EMI/RFI geluidsfiltering: | Ja |
Heb je hulp nodig?
Als je hulp nodig hebt met CyberPower BR450ELCD stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS CyberPower
15 November 2024
7 November 2024
7 November 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Tripp Lite
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
18 November 2024
17 November 2024
17 November 2024
17 November 2024
16 November 2024
15 November 2024
14 November 2024
14 November 2024
12 November 2024
22 Oktober 2024