System Sensor SPSCWL Handleiding
System Sensor
Rookmelder
SPSCWL
Lees hieronder de 📖 handleiding in het Nederlandse voor System Sensor SPSCWL (4 pagina's) in de categorie Rookmelder. Deze handleiding was nuttig voor 62 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/4
1 I56-0002-002
12/10/2018
For use with the following models:
Wall Speakers: SPSRL, SPSWL, SPSRL-P, SPSWL-P, SPSRL-SP, SPSWL-CLR-ALERT
Ceiling Speakers: SPSCRL, SPSCWL, SPSCWL-P, SPSCWL-SP, SPSCWL-CLR-ALERT
PRODUCT SPECIFICATIONS
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% Non-condensing
Nominal Voltage (speakers): 25 Volts or 70.7 Volts
Maximum Supervisory Voltage: 50 VDC
Speaker Frequency Range: 400 – 4000 Hz
Power Settings: ¼, ½, 1, 2 Watts
Input terminal wire gauge: 12 to 18 AWG
Strobe Flash Rate: 1 flash per second
Nominal Voltage (strobes): Regulated 12VDC, regulated 24VDC or FWR
Operating Voltage Range (includes fire alarm
panels with built in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL3 Sync Module: 8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)
DIMENSIONS FOR PRODUCTS AND ACCESSORIES MOUNTING BOX OPTIONS
WALL PRODUCTS Length Width Depth SPEAKER STROBES
Wall Speaker Strobe 6.5" (165 mm) 5.00" (127 mm) 2.30" (58.4 mm) SBBSPRL/WL (wall), SBBCRL/WL (ceil-
ing), 4" x 4" x 2
1
/
8
"or deeper (When
using 12AWG, 14 AWG, or adding extra
wires in the box, a deeper box or exten-
sion ring is recommended.)
CEILING PRODUCTS Length Width Depth
Ceiling Speaker Strobe 6.8" (173 mm) N/A 2.87" (73mm)
WALL SURFACE MOUNT BACK BOX Length Width Depth
Speaker Strobe with SBBSPRL/WL Surface
Mount Back Box 6.62" (168mm) 5.12" (130 mm) 2.30" (58.4 mm)
CEILING SURFACE MOUNT BACK BOX Diameter Depth
Speaker Strobe with SBBCRL/WL Surface
Mount Back Box 6.92" (176 mm) 5.37" (116mm)
NOTICE: This manual shall be left with the owner/user of this equipment.
BEFORE INSTALLING
Please read the System Sensor Voice Evacuation Application Guide, which
provides detailed information on speaker notification devices, wiring and
special applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed. System Sensor also rec-
ommends installing fire alarm speakers in compliance with NFPA 72, ANSI/
UL 1480 and NEC 760
Important: The notification appliance used must be tested and maintained
following NFPA 72 requirements.
GENERAL DESCRIPTION
System Sensor series of notification appliances offer a wide range of audible
and visible devices for life safety notification. Our indoor speaker strobes
come with 7 field selectable candela setting. The strobe portion is designed
to be used in 12 VDC, 24VDC, or 24V FWR (full wave rectified) systems. The
speaker is designed to be used at either 25 or 70.7 volts, and operate at any
one of four input power levels. Our speaker strobes are suitable for dry and
damp environments. These products are electrically backwards compatible
with previous generation of System Sensor speaker strobes. With its low total
harmonic distortion, the System Sensor SPL series offers high fidelity sound
output.
Speakers Strobes are public mode notification appliances intended to alert oc-
cupants of a life safety event. The speaker is listed to ANSI/UL 1480 (public
mode) and the strobe is listed to ANSI UL 1638 (public mode).
FIRE ALARM SYSTEM CONSIDERATIONS
System Sensor also recommends installing fire alarm speakers in compliance
with NFPA 72, ANSI/UL 1480 and NEC 760.
SYSTEM DESIGN
The system designer must make sure that the total current drawn by the de-
vices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage. The
current draw information for making these calculations can be found in the
tables within this manual. For convenience and accuracy, use the voltage drop
calculator on the System Sensor website (www.systemsensor.com).
When calculating the voltage for the last device, it is necessary to consider
the voltage drop due to the resistance of the wire. The thicker the wire, the
smaller the voltage drop. Note that if Class A wiring is installed, the wire
length may be up to twice as long as it would be circuits that are not fault
tolerant. The total number of strobes on a single NAC must not exceed 69 for
24 volt applications.
AVAILABLE CANDELA SETTINGS
System Sensor offers a wide range of candela settings for your life safety
needs. In order to select your candela output, adjust the slide switch on the
rear of the product to the desired candela setting on the selector switch. (See
Figure 1.)
The candela setting can also be verified by looking into the small window
on the front of the unit. See Tables 1 and 2 for candela settings for wall and
ceiling products. All products meet the light output profiles specified in the
appropriate UL Standards. (See Figures 2–4.)
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Selectable Output Speaker Strobes
– Wall and Ceiling Mount
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
I56-0002-002
2 I56-0002-002
12/10/2018
FIGURE 4. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TO FLOOR
Degrees* Percent of
Rating
0 100
5-25 90
30-45 75
50 55
60 45
65 35
70 35
75 30
80 30
85 25
90 25
A0468-00
WIRING AND MOUNTING
All wiring must be installed in compliance with the National Electric Code
and the local codes as well as the authority having jurisdiction. Wiring must
not be of such length or wire size which would cause the notification appli-
ance to operate outside of its published specifications. Improper connections
can prevent the system from alerting occupants in the event of an emergency.
Wire sizes up to 12 AWG (2.5 mm²) may be used with the mounting plate. The
mounting plate ships with the terminals set for 12 AWG wiring.
Make wire connections by stripping about
3
/
8
" of insulation from the end of
the wire. Then slide the bare end of the wire under the appropriate clamping
plate and tighten the clamping plate screw.
See Figure 5 for wiring terminals and strip guide reference.
1. Connect the speaker. (See Figure 5.)
2. There are two rotary switches on the back of the product. The first switch
is used to select either 25 or 70.7 volts input and the second switch is used to
select the input power of ¼, ½, 1 or 2 watts. (See Figure 6.)
FIGURE 5. WIRING DIAGRAM AND WIRING TERMINALS
(-)
(+)
(-)
(+)
(-)
(+)
(-)
(+)
From FACP
OUTPUT
To Next Device or EOL
From Amplifier
INPUT
To Next Device or EOL
A0519-01
Wiring Terminals
1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out
NOTE: Do not loop electrical wiring un-
der terminal screws. Wires connecting
the device to the control panel must be
broken at the device terminal connec-
tion in order to maintain electrical su-
pervision.
FIGURE 6. SPEAKER WATTAGE AND VOLTAGE SETTINGS
A0419-01
FIGURE 1. CANDELA SELECTOR
A0486-00
CURRENT DRAW AND AUDIBILITY RATINGS
For the strobe, the current draw for each setting is listed in Tables 1 and 2.
TABLE 1. WALL-MOUNT STROBE CURRENT DRAW (mA)
Candela
8-17.5
Volts 16-33 Volts
DC DC FWR
15 88 43 60
NOTE: Products set at 15 and 30
candela automatically work on ei-
ther 12V or 24V power supplies.
The products are not listed for
12V DC operation when set to any
other candela settings.
30 143 63 83
75 - 136107
95 - 155121
110 - 148 179
135 - 172 209
185 - 222 257
TABLE 2. CEILING-MOUNT STROBE CURRENT DRAW (mA)
Candela
8-17.5
Volts 16-33 Volts
DC DC FWR
15 87 6041
NOTE: Products set at 15 and 30
candela automatically work on
either 12V or 24V power supplies.
The products are not listed for 12V
DC operation when set to any other
candela settings.
30 153 63 86
75 - 142111
95 - 134 164
115 - 158 191
150 - 189 228
177 - 226 264
FIGURE 2. WALL LIGHT OUTPUT – FIGURE 3. VERTICAL
HORIZONTAL DISPERSION DISPERSION, WALL TO FLOOR
Degrees* Percent of
Rating Degrees* Percent of
Rating
0 0100 100
5-25 90 5-30 90
30-45 75 35 65
50 55 40 46
55 45 45 34
60 40 2750
65 35 55 22
70 35 60 18
75 65 1630
80 1530 70
85 25 75 13
90 25 80 12
Compound 45
to the left 24 85 12
Compound 45
to the right 24 90 12
A0467-00
A0469-00
*Tolerance of ±1 degree is permitted.
3 I56-0002-002
12/10/2018
SHORTING SPRING FEATURE
System Sensor notification appliances come with a shorting spring that is pro-
vided between terminals 2 and 3 of the mounting plate to enable system con-
tinuity checks after the system has been wired, but prior to installation of the
final product. (See Figure 7.) This spring will automatically disengage when
the product is installed, to enable supervision of the final system.
FIGURE 7. SHORTING SPRING
Shorting
Spring
WIRING TERMINALS
1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out
Strip Guide
A0499-02
AVAILABLE POWER SETTINGS
System Sensor offers a wide range of power settings for your life safety needs,
including ¼, ½, 1, and 2W.
Sound levels data per UL 1480 can be found in Table 3.
TABLE 3. SOUND LEVELS FOR EACH TRANSFORMER POWER SETTING
Setting UL Reverberant
(dBA @10 ft)
UL Anechoic
(dBA @10 ft)
¼ W 77 77
½ W 80 80
1 W 83 83
2 W 86 86
CAUTION
Signal levels exceeding 130% rated signal voltage can damage the speaker.
Consequently, an incorrect tap connection may cause speaker damage. This
means that if a 25V tap is selected when a 70.7V amplifier is being used,
speaker damage may result. Therefore, be sure to select the proper taps for the
amplifier voltage/input power level combination being used.
MOUNTING AND REMOVNG APPLIANCE
1. Attach mounting plate to junction box using two of the provided Philips
head screws. (See Figures 8 and 9.)
2. Connect field wiring according to terminal designations. (See Figure 5.)
3. If the product is not to be installed at this point, use the protective dust
cover to prevent contamination of the wiring terminals on the mounting
plate.
4. To attach product to mounting plate:
a. Remove the protective dust cover.
b. Hook the tabs on the top of the product housing into the grooves on mount-
ing plate.
c. Pivot the product into position to engage the terminals on the mounting
plate. Make sure that the tabs on the back of the product housing fully en-
gage with the mounting plate.
d. Hold product in place with one hand, and secure product by tightening the
single mounting screw in the front of the product housing.
Ceiling Models only: To remove product from the mounting plate, press the
locking button after loosening the captive mounting screw.
CAUTION
The “hold in place” snaps are not intended to secure the product to the back
box. The product must be secured to the back box using the screws provided.
CAUTION
Factory finish should not be altered: Do not paint!
CAUTION
Do not over tighten mounting plate screws; this may cause mounting plate
to flex.
FIGURE 8. WALL SPEAKER/STROBE
A0522-01
FIGURE 9. CEILING SPEAKER/STROBE
A0521-02
Locking
Button
A0575-00
TAMPER SCREW
For tamper resistance, the standard captive screw may be replaced with a Torx
screw (sold separately).
1. To remove the captive screw, back out the screw and apply pressure to the
back of the screw until it disengages from the housing. Replace with Torx
screw. (See Figure 10.)
FIGURE 10. TAMPER SCREW
T15 Torx
#6-32, 5/8"
SCREW-TMPR-50
A0502-01
INSTALLING A SURFACE MOUNT BACK BOX
1. The surface mount back box may be secured directly to the wall or
ceiling. Use of grounding bracket with ground screw is optional. (See
Figures 11 and 12.)
2. The wall mount box must be mounted with the up arrow pointing up. (See
Figure 13.)
NOTE: Ceiling Surface Mount Back Box SBBCR/CWL is a common back box
for ceiling horn strobes, strobes and ceiling speakers and speaker strobes. Use
Product specificaties
Merk: | System Sensor |
Categorie: | Rookmelder |
Model: | SPSCWL |
Type stroombron: | DC |
Koolmonoxidemelder: | Nee |
Bedrijfstemperatuur centrale besturingseenheid (T-T): | 0 - 49 °C |
Brandmeldcentrale: | Ja |
Centrale besturingseenheid werkzaam bij relatieve vochtigheid (V-V): | 10 - 93 procent |
Geluidsalarmeenheid voor noodgevallen: | Ja |
Heb je hulp nodig?
Als je hulp nodig hebt met System Sensor SPSCWL stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Rookmelder System Sensor
9 Juni 2023
4 Juni 2023
30 Mei 2023
30 Mei 2023
28 Mei 2023
22 Mei 2023
18 Mei 2023
16 Mei 2023
13 Mei 2023
Handleiding Rookmelder
- Rookmelder Bosch
- Rookmelder IKEA
- Rookmelder Grundig
- Rookmelder Gigaset
- Rookmelder Honeywell
- Rookmelder Siemens
- Rookmelder Abus
- Rookmelder Ajax
- Rookmelder Alecto
- Rookmelder AngelEye
- Rookmelder Bavaria
- Rookmelder Blaupunkt
- Rookmelder Brennenstuhl
- Rookmelder BRK
- Rookmelder BRK DICON
- Rookmelder Denver
- Rookmelder Elgato
- Rookmelder Elro
- Rookmelder Eminent
- Rookmelder EQ-3
- Rookmelder ESYLUX
- Rookmelder Ferguson
- Rookmelder FireAngel
- Rookmelder First Alert
- Rookmelder FirstAlert
- Rookmelder Flamingo
- Rookmelder Gira
- Rookmelder Gloria
- Rookmelder Hager
- Rookmelder Hama
- Rookmelder HQ
- Rookmelder Interlogix
- Rookmelder KlikaanKlikuit
- Rookmelder Kogan
- Rookmelder Konig
- Rookmelder Marmitek
- Rookmelder Marquant
- Rookmelder Mercury
- Rookmelder Nedis
- Rookmelder Nest
- Rookmelder Netatmo
- Rookmelder Pyle
- Rookmelder Satel
- Rookmelder Smartwares
- Rookmelder Somfy
- Rookmelder Stabo
- Rookmelder Sygonix
- Rookmelder TFA
- Rookmelder Trust
- Rookmelder Vivanco
- Rookmelder Yale
- Rookmelder Jung
- Rookmelder Olympia
- Rookmelder Clas Ohlson
- Rookmelder Schwaiger
- Rookmelder Steren
- Rookmelder EMOS
- Rookmelder Malmbergs
- Rookmelder DSC
- Rookmelder M-e
- Rookmelder REV
- Rookmelder Chacon
- Rookmelder Nexa
- Rookmelder Swann
- Rookmelder Deltronic
- Rookmelder Ei Electronics
- Rookmelder Fibaro
- Rookmelder FireHawk
- Rookmelder FireX
- Rookmelder Fito
- Rookmelder GEV
- Rookmelder Insafe
- Rookmelder Kidde
- Rookmelder No-Flame
- Rookmelder Pyrexx
- Rookmelder Dahua Technology
- Rookmelder Busch-Jaeger
- Rookmelder EVE
- Rookmelder Popp
- Rookmelder EQ3
- Rookmelder Homematic IP
- Rookmelder Calex
- Rookmelder Lanberg
- Rookmelder Mobeye
- Rookmelder X-Sense
- Rookmelder Chuango
- Rookmelder ORNO
- Rookmelder ETiger
- Rookmelder TEF
- Rookmelder Jalo Helsinki
- Rookmelder Heatit
- Rookmelder Fito Profi-line
- Rookmelder H-Tronic
- Rookmelder Inovonics
- Rookmelder Pristine
- Rookmelder Cavius
- Rookmelder Jemay
- Rookmelder Pentatech
- Rookmelder Mircom
- Rookmelder WisuAlarm
- Rookmelder Cordes
- Rookmelder SAVS
- Rookmelder STI
- Rookmelder Gewiss
- Rookmelder Egardia
- Rookmelder Frient
- Rookmelder Qolsys
Nieuwste handleidingen voor Rookmelder
2 December 2024
30 November 2024
30 November 2024
30 November 2024
24 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
16 November 2024