Gossen Metrawatt SINEAX VQ604s Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Gossen Metrawatt SINEAX VQ604s (22 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 66 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/22
VQ604s Be Version 01 12.12
Operating instructions
SINEAX VQ604s
Programmable multifunctional transmitter
with very fast setting times
Camille Bauer AG
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax +41 56 618 21 21
info@camillebauer.com
www.camillebauer.com
2 Operating instructions VQ604s Be Camille Bauer
Operating instructions
Programmable multifunctional transmitter SINEAX VQ604s
First read, then …
The unobjectionable and safe operation pre-
supposes that these operating instructions
have been read and understood!
Devices may only be disposed of in a pro-
fessional manner!
Contents
1. Functional description .................................................2
2. Connection to a PC and communication via
CB-Manager ................................................................2
3. Block diagram .............................................................. 3
4. Technical data .............................................................. 4
5. Signal fl ow ...................................................................8
6. Modbus interface ......................................................... 9
6.1 EIA-RS-485 Standard ............................................ 9
6.2 Coding and addressing ......................................... 9
6.3 Mapping .............................................................. 10
6.4 Device identifi cation ............................................ 10
6.5 Measured values ................................................. 11
6.6 Confi guration parameters ....................................12
7. Electric connections .................................................. 18
8. Dimensional drawing ................................................. 20
9. Accessories ............................................................... 20
10. Conformity declaration .............................................. 20
1. Functional description
VQ604s is a multifunctional transmitter for top-hat rail as-
sembly with the following main characteristics:
Fast measurement of DC voltage, DC current, tempera-
ture (RTD, TC) and resistance
Setting time up to 10 ms
Sensor connection without any external jumpers
2 inputs (e.g. for sensor redundancy or difference
formation)
2 outputs (I)
2 inputs can be linked with each other and allocated
to the 2 outputs which enables calculations and
sensor monitoring (e.g. prognostic maintenance of
sensors)
System capability: Communication via Modbus
interface
Freely programmable relay, e.g. for limit or alarm sig-
nalling
AC/DC wide-range power supply unit
Pluggable high-quality screw or spring cage terminals
All settings of the instrument can be adapted to the measur-
ing task by PC software. The software also serves visualising,
commissioning and service.
2. Connection of SINEAX VQ604s to a PC and communication via CB-Manager.
VQ604s communicates with a PC (CB-Manager) via an RS
232/RS485 interface and a MODBUS protocol.
Select the following settings in this respect:
Select the RS 232/ RS485 interface under Options / Inter-
face.
This is also applicable if an RS485/USB converter is used
and the converter is connected to the computer via the
USB connection.
Subsequently, enter the following settings under Options /
Interface / Settings:
Camille Bauer Operating instructions VQ604s Be 3
D
A
D
3,7 kV
A
3,7 kV3,7 kV
Measuring
inputs
Power supply
Relay
contact
A1+
A–
A2+
Bus
0,5 kV
2,3 kV
+
Tx
Rx
GND
Analog
outputs
μP
3. Block diagram
To determine which COM port has been allocated to
the RS485 converter (if required), please proceed as
follows:
The COM port of an external RS232 or RS485 converter
may be determined (and, if required, changed) via the
Windows system control.
Example for Windows XP: System control => System
This example shows the COM ports of a PCMCIA card
and a USB-RS232 converter:
- Silicom Serial Card: COM1
- USB-RS232 adapter: COM4
The existing COM ports are determined as the communi-
cation interface when starting the program and selecting
RS232/RS485. Only COM ports found are available for
selection.
Limiting the range of possible device addresses speeds
up the search of connected devices considerably.
Example: If only 2 devices are connected, it makes sense
to select the address range from 1 to 2.
All settings are stored as the program is terminated. If the
COM port is not available upon the next start of the pro-
gram (e.g. because the converter has not been plugged in)
another valid interface is set.
If you use the Camille Bauer USB-RS485 converter
(Article Number 163189), the same is to be connected as
follows:


Product specificaties

Merk: Gossen Metrawatt
Categorie: Niet gecategoriseerd
Model: SINEAX VQ604s

Heb je hulp nodig?

Als je hulp nodig hebt met Gossen Metrawatt SINEAX VQ604s stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Gossen Metrawatt

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd