Vemer Aros Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Vemer Aros (3 pagina's) in de categorie Thermostaat. Deze handleiding was nuttig voor 39 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/3
67
1 8OPERATIONUser Manual
ELECTRONIC TOUCH SCREEN THERMOSTATS
Read all instructions carefully
PACKAGE CONTENTS
ADJUSTABLE COVER PLATES
INSTALLATION
2
5REMOVAL OF BATTERY POWERED AROS
3WIRING DIAGRAMS
4LEGEND
Advanced programming
Reset
Setpoint modification
Depleted batteries signal
Error messages
Night reduction (only for battery models)
frames and plastic elements are available in white and anthracite grey colours
thermostat
covers A mount B mount
VI side BM side
AIR mount
COM
NA NC
N L
230V~
Aros 230 Aros
COM
NA NC
1 2 3 4 5 1 2 3 4 5
EXTERNAL
CONTACT
Switch off
or
3 sec.
3 sec.
19.8
19.9
...
Default values
Heating setpoint 21°C
Cooling setpoint 25°C
Minimum settable setpoint - L0 2°C
Maximum settable setpoint - Xi 35°C
Operating mode (heating)
Antifreeze temperature 6°C
Regulation type On /Off
Differential 0.3°C
Password - - - (desabled)
3 sec.
3 sec.
Vemer S.p.A.
I - 32032 Feltre (BL) • Via Camp Lonc, 16
Tel +39 0439 80638 • Fax +39 0439 80619
e-mail: info@vemer.it - web site: www.vemer.it
V3IS00686-014-062017
Mod. AROS
Flush-mounting electronic touch screen thermostats for temperature control
both in heating and cooling. They perform actions of type 1B and are intended
for operating in environments with Pollution Degree 2 and Overvoltage
Category III (EN60730-1).
with battery power supply and monocolour backlit display, has got an Aros
input to connect an external contact suitable to reduce the setpoint of 3°C.
Aros 230 with AC power supply and multicolor backlit display: red, green
and blue. The colour changes according to the gap between the measured
temperature and the programmed setpoint.
Code Model Description
VE458600 Aros Touch screen thermostat batteries with digital input
VE459400 Aros 230 Touch screen thermostat 230V with multicolor display
SAFETY WARNINGS
During product installation and operation it is necessary to observe the
following instructions:
1) The device must be installed by a qualified person, in strict compliance with the
connection diagrams.
2) Do not power or connect the device if any part of it is damaged.
3) After installation, inaccessibility to the connection terminals without appropriate
tools must be guaranteed.
4) The device must be installed and activated in compliance with current electric
systems standards.
5) Before accessing the connection terminals, verif y that the leads are not live.
6) In the electrical system of the building where the device must be installed, a
switch and a protection device from the overcurrents must be present (for Aros
230 model only).
TECHNICAL SPECIFICATIONS
Power supply Aros: – 2 alkaline batteries 1.5V (AAA type)
– battery life: 12 months
– depleted batteries indication
Power supply Aros 230: – 230Vac (-15% ÷ +10%) 50/60Hz
– max absorption: 6 VA / 230Vac
3 modules box installation (503 type)
Terminals Aros:
– 3 terminals for 1.5 mm2 cable section for bistable output relay 5A / 250Vac
– 2 terminals for 1.5 mm2 cable section for digital input (3°C setpoint reduction)
Terminals Aros 230:
– 3 terminals for 1.5 mm2 cable section for bistable output relay 5A / 250Vac
– 2 terminals for 1.5 mm2 cable section for power supply
Operating mode: summer/winter/off (with antifreeze operating mode)
Password protected lock keypad
Regulation type:
– on/off with settable differential (0.1 ÷ 1°C)
– P8 proportional with 0.8°C band (-0.3 ÷ +0.5°C) and period 8 minutes
– P15 proportional with 1.5°C band (-0.7 ÷ +0.8°C) and period 15 minutes
Measurement precision: ± 0.5 °C
Measurement temperature resolution: 0.1 °C
Setpoint range: 2°C ÷ +35°C
Operating temperature: 0 °C ÷ +50 °C
Storage temperature: -10 °C ÷ +65 °C
Relative humidity: 20÷90% non-condensing
Degree of protection: IP40
Insulation: reinforced among accessible parts (frontal) and all other terminals
During the standard operation the thermostat displays the detected temperature value and the relay status is identified by the symbol (heating mode) or the symbol
(cooling mode).
REFERENCE STANDARDS
Compliance with Community Directives
2014/35/EU (LVD)
2014/30/EU (EMCD)
is declared with reference to the following harmonized standards:
• EN 60730-2-9
Minimum settable setpoint - L0
It’s the minimum value settable as setpoint.
Settable values: 2 ÷ 35°C
Maximum settable setpoint - KI
It’s the maximum value settable as setpoint.
Settable values: ÷ 35°CL0
Operating mode - E-I
if connected to the boiler (heating)
if connected to a cooling system
Antifreeze temperature - Toff
Minimum temperature maintained with Aros off
(see box «Switch off»).
Settable values: 1 ÷ 10 °C or --- (excluded function)
Regulation type - REG - (only in heating)
0 = on/off with settable differential
P8 = proportional with band 0.8°C and period 8 minutes
P15 = proportional with band 1.5°C and period 15 minutes
Differential - d0.3 - (only for on/off regulation)
Differential (or hysteresis) for temperature regulation.
Settable values: 0.1 ÷ 1°C
Password for keypad lock - PAS
Set a value between 001 and 999 to activate the keypad lock.
Set to disable the lock.“ ”---
If the keypad lock is active, pressing one key appears LoC
and the password is required. If its properly inserted the
keyboard is unlocked for the next 30 seconds.
Aros has got an input to whom to connect an external contact for the setpoint reduction
of 3° than the programmed one.
The adapters inside the box allow the monitoring of the following cover
plates:
For information about the possibility to adapt the thermostat with different
cover plates from those listed, contact the Technical Service.
* through mount that you can buy on request (code VE767500)
All the above trademarks are the property of their respective owners.
Install the thermostat at a height of about 1.5 m above the floor, away from
direct sunlight, away from doors, windows, heat sources, locations with excess
or total lack of ventilation.
Install the white or anthracite grey cover according to your preferences by
hooking it to the cogs of the device.
Make the connection by respecting the diagrams described in this manual.
Fix the device inside the 3 modules box in compliance with the assembly
diagrams described on the back of this instruction sheet. The accessories
for the installation included in the package allow the mounting of the plates
described in the diagram “adjustable cover plates” and they are:
- mount A
- mount B (according to the needs it could be necessary to remove the side cogs)
- mount AIR
- couple of side BM plastic elements (both of white colour and grey colour)
- couple of side VI plastic elements (both of white colour and grey colour)
- covers of white colour and anthracite grey colour.
ABB Chiara series
ABB Mylos series
Ave S44 series
Bticino Axolute series
Bticino Axolute Air
Bticino Light series
Bticino Light tech series
Bticino Living series
Bticino Livinglight series
Bticino Livinglight Air series
Bticino Matix series
Gewiss Chorus series
Vimar Eikon series
Vimar Eikon Evo series
Vimar Idea series
Vimar Plana series
Vimar Arké series
To enter menu Advanced programming keep simultaneously pressed for 5 seconds the
keys and until will appear. PR
The items of the menu are displayed in succession. For each item is displayed an
identity breviation and its relative blinking value. Use the keys and
to modify the value. After 3 seconds without touching the keys
there is the passage to the following parameter. The writing END
will appear when all parameters are set and the thermostat returns
successively in standard mode saving the effected modifications.
6-2017
Backlighting management
Battery models
Aros has got a backlighting which is is normally OFF and it is enabled (blue
colour) entering menu: setpoint modification, advanced programming,
pin enter.
Models 230V~
Aros 230 has got a backlighting which is normally ON and it will be:
blue if the measured temperature is lower than the setpoint at least of
0.5 °C or if you are in the menu setpoint modification, advanced
programming or pin enter.
green if the gap between the measured temperature and the setpoint is
lower than 0.5 °C or if the thermostat is in off mode
red if the measured temperature is higher than the setpoint at least of 0.5 °C.
Backlighting switching OFF
If not desired the backlighting function can be disabled by pressing the key
for at least 3 seconds (for example in bedrooms). Then the thermostat continues
its standard operation and the backlighting is enabled entering menu setpoint
modification, advanced programming, pin enter.
“Environment temperature” field
“Off” field
“Heating activation field
“Cooling activation” field
Key decreases the selected field
Key increases the selected field
Attention: the keys are active only if the device is
correctly inserted in the flush-mounting
box.
Unhook and re-hook the thermostat from the base ( battery models) or remove and restore power (230 V versions).
Press the keys and for at least 3 seconds during the flashing of the keyboard.
The removal of the battery powered device takes place by pulling on the frame convexity (section 5).
Note: in heating mode (winter), if the thermostat is off, it regulates the antifreeze
Toff temperature in order to prevent freezing of the system.
Toff can have values from 1 to 10° C or be excluded; in this case no minimum
temperature is guaranteed.
Occurs in case of probe failure.
In this case thermostat activates the heating for 10 minutes
every 4 hours (if the antifreeze temperature Toff is active)
Occurs for the following values of measured temperature:
t < 0°C
t >50°C
Normal operation Replace the batteries as
soon as possible! Dispose of
batteries in the appropriate
recycling containers.
Modification of the desired temperature (setpoint),
to increase to decrease
Normal operation
heating on ( )
3 sec.
3 sec.
3 sec.
9 10
AROS BATTERY MOUNTING AROS 230 MOUNTING
Bticino Living, Light, Light Tech, Livinglight, Axolute series
Vimar Eikon, Eikon Evo, Plana series
Ave S44 series ABB Mylos series
Gewiss Chorus series
ABB Chiara series
Vimar Ar, Idea series
Bticino Matix series
Remove the cogs Remove the cogs
A
B
BM
B
Bticino Livinglight AIR series
* Note: If the box extension is not present (adapter
which increases the depth of the in-built box)
we recommend using the frame for installation
Livinglight AIR.
AIR
*
Bticino Matix series
ABB Chiara series
Vimar Ar, Idea series
Gewiss Chorus series
Bticino Living, Light, Light Tech, Livinglight, Axolute series
Vimar Eikon, Eikon Evo, Plana series
Ave S44 series – ABB Mylos series
Remove the cogs Remove the cogs
B
BM
B
A
Bticino Livinglight AIR series
* Note: If the box extension is not present (adapter
which increases the depth of the in-built box)
we recommend using the frame for installation
Livinglight AIR.
AIR
*
*Note: only for installing the Vimar Idea series
cover plate, use the side plastic elements VI.
B
VI
Bticino Axolute AIR series
AXO mount not included in the package.
AXO AIR
*Note: only for installing the Vimar Idea series
cover plate, use the side plastic elements VI.
Bticino Axolute AIR series
AXO AIR mount not included in the package.
AXO AIR
B
VI


Product specificaties

Merk: Vemer
Categorie: Thermostaat
Model: Aros

Heb je hulp nodig?

Als je hulp nodig hebt met Vemer Aros stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Thermostaat Vemer

Handleiding Thermostaat

Nieuwste handleidingen voor Thermostaat