Read and understand the instruction manual before using the product.
For your safety, read and follow the below safety considerations before using. For your safety,
read and follow the considerations written in the instruction manual.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc are subject to change without notice for product improvement.
Safety Considerations
• Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
• symbol indicates caution due to special circumstances in which hazards may occur.
Warning Failure to follow instructions may result in serious injury or death
01. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire.
02. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity,
direct sunlight, radiant heat, vibration, impact or salinity may be present.
Failure to follow this instruction may result in explosion or fire.
03. Install on a device panel to use.
Failure to follow this instruction may result in electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in fire or electric shock.
05. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
06. Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.
Caution Failure to follow instructions may result in injury or product damage
01. When connecting the power input and relay output, use AWG 20 (0.50 mm 2) cable or over, and
tighten the terminal screw with a tightening torque of 0.74 to 0.90 N m.
When connecting the sensor input and communication cable without dedicated cable, use
AWG 28 to 16 cable and tighten the terminal screw with a tightening torque of 0.74 to 0.90 N
m.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
02. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage
03. Use a dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in fire or electric shock.
04. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
Failure to follow this instruction may result in fire or product damage.
Cautions during Use
• Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
• Check the polarity of the terminals before wiring the temperature sensor. For RTD temperature sensor,
wire it as 3-wire type, using cables in same thickness and length.
For thermocouple (TC) temperature sensor, use the designated compensation wire for extending wire.
• Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power
line and input signal line closely, use line filter or varistor at power line and shielded wire at input
signal line. Do not use near the equipment which generates strong magnetic force or high frequency
noise.
• Do not apply excessive power when connecting or disconnecting the connectors of the product.
• Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting
the power.
• Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
• When changing the input sensor, turn off the power first before changing. After changing the input
sensor, modify the value of the corresponding parameter.
• Do not overlapping communication line and power line. Use twisted pair wire for communication line
and connect ferrite bead at each end of line to reduce the effect of external noise.
• Make a required space around the unit for radiation of heat. For accurate temperature measurement,
warm up the unit over 20 min after turning on the power.
• Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
• Do not wire to terminals which are not used.
• This unit may be used in the following environments.
-Indoors (in the environment condition rated in ‘Specifications’)
-Altitude Max. 2,000 m
-Pollution degree 2
-Installation category II
Product Components
• Product (+ bracket) • Instruction manual
Operating Instructions for download
Use the link www.conrad.com/downloads (alternatively scan the QR code) to download the complete
operating instructions (or new/current versions if available). Follow the instructions on the web page.
Specifications
Series TK4S
Power supply AC type 100 - 240 VAC~ 50/60 Hz
Permissible voltage range 90 to 110 % of rated voltage
Power
consumption AC type ≤ 8 VA
Unit weight (packaged) ≈ 105 g
(≈ 150 g)
Sampling period 50 ms
Input specification Refer to 'Input Type and Using Range'
Control
output
Relay 250 VAC ~ 3 A, 30 VDC 3 A 1a
SSR 11 VDC ±2 V, ≤ 20 mA
Current DC 4-20 mA or DC 0-20 mA (parameter), Load resistance: ≤ 500 Ω
Alarm
output Relay AL1: 250 VAC~ 3 A 1a
Display type 7 segment (red, green, yellow), LED type
Control
type
Heating, Cooling
ON/OFF, P, PI, PD, PID Control
Heating & Cooling
Hysteresis • Thermocouple, RTD: 1 to 100 (0.1 to 100.0) °C/°F
• Analog: 1 to 100 digit
Proportional band (P) 0.1 to 999.9 °C/°F (0.1 to 999.9%)
Integral time (I) 0 to 9,999 sec
Derivative time (D) 0 to 9,999 sec
Control cycle (T) • Relay output, SSR drive output: 0.1 to 120.0 sec
• Selectable current or SSR drive output: 1.0 to 120.0 sec
Manual reset 0.0 to 100.0%
Relay life
cycle
Mechanical OUT1/2: ≥ 5,000,000 operations
AL1/2: ≥ 20,000,000 operations
Electrical ≥ 100,000 operations
Dielectric strength Dependent on the power supply
AC voltage type Between the charging part and the case: 3,000 VAC ~ 50/60 Hz for 1 minute
Vibration 0.75 mm amplitude at frequency of 5 to 55 Hz in each X, Y, Z direction for
2 hours
Insulation resistance ≥ 100 MΩ (500 VDC megger)
Noise immunity ±2 kV square shaped noise by noise simulator (pulse width: 1 µs) R-phase,
S-phase
Memory retention ≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature -10 to 50 °C, storage: -20 to 60 °C (no freezing or condensation)
Ambient humidity 35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Protection structure IP65 (Front panel, IEC standards)
Insulation type Double insulation or reinforced insulation (mark: , dielectric strength
between the measuring input part and the power part: 2 kV)
Certification
Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Input type Decimal
point Display Using range (°C) Using range (°F)
Thermo
-couple
K (CA) 1 -200 to 1,350 to 2,462-328
0.1 -199.9 to 999.9 -199.9 to 999.9
J (IC) 1 -200 to to 1,472800 -328
0.1 -199.9 to -199.9 to 999.9800.0
E (CR) 1 -200 to to 1,472800 -328
0.1 -199.9 to -199.9 to 999.9800.0
T (CC) 1 -200 to 400 to 752-328
0.1 -199.9 to 400.0 -199.9 to 752.0
B (PR) 1 0 to 32 to 3,2721,800
R (PR) 1 0 to 1,750 32 to 3,182
S (PR) 1 0 to 1,750 32 to 3,182
N (NN) 1 -200 to 1,300 to 2,372-328
C (TT) 01) 1 0 to 2,300 32 to 4,172
G (TT) 02) 1 0 to 2,300 32 to 4,172
L (IC) 1 -200 to 900 to 1,652-328
0.1 -199.9 to 900.0 -199.9 to 999.9
U (CC) 1 -200 to 400 to 752-328
0.1 -199.9 to 400.0 -199.9 to 752.0
Platinel II 1 0 to 1,390 32 to 2,534
RTD
Cu50 Ω 0.1 -199.9 to 200.0 -199.9 to 392.0
Cu100 Ω 0.1 -199.9 to 200.0 -199.9 to 392.0
JPt100 Ω 1 -200 to 650 to 1,202-328
0.1 -199.9 to 650.0 -199.9 to 999.9
DPt50 Ω 0.1 -199.9 to 600.0 -199.9 to 999.9
DPt100 Ω 1 -200 to 650 to 1,202-328
0.1 -199.9 to 650.0 -199.9 to 999.9
Nickel120 Ω -801 to 200 -112 to 392
Analog
0 to 10 V - 0 to 10 V
0 to 5 V - 0 to 5 V
1 to 5 V - 1 to 5 V
0 to 100 mV - 0 to 100 mV
0 to 20 mA - 0 to 20 mA
4 to 20 mA - 4 to 20 mA
01) C (TT): Same as existing W5 (TT) type sensor
02) G (TT): Same as existing W (TT) type sensor
• Permissible line resistance per line: ≤ 5 Ω
â– Display accuracy
Input type Using temperature Display accuracy
Thermo
-couple RTD
At room temperature
(23 °C ±5 °C)
(PV ±0.3% or ±1 °C higher one) ±1-digit
• Thermocouple K, J, T, N, E below -100 °C and L, U, PLII,
RTD Cu50 Ω, DPt50 Ω:
(PV ±0.3% or ±2 °C higher one) ±1-digit
• Thermocouple C, G and R, S below 200 °C:
(PV ±0.3% or ±3 °C higher one) ±1-digit
• Thermocouple B below 400 °C:
There is no accuracy standards
Out of room temperature
range
(PV ±0.5% or ±2 °C higher one) ±1-digit
• RTD Cu50 Ω, DPt50 Ω:
(PV ±0.5% or ±3 °C higher one) ±1-digit
• Thermocouple R, S, B, C, G:
(PV ±0.5% or ±5 °C higher one) ±1-digit
• Other sensors: ≤ ±5 °C (≤-100 °C)
Analog
At room temperature
(23 °C ±5 °C) ±0.3% F.S. ±1-digit
Out of room temperature
range ±0.5% F.S. ±1-digit
Unit Descriptions
1. PV display part (Red)
• Run mode: Displays PV (Present value).
• Setting mode: Displays parameter name.
2. SV display part (Green)
• Run mode: Displays SV (Setting value).
• Setting mode: Displays parameter setting value.
3. Input key
Display Name
[A/M] Control switching key
[MODE] Mode key
[â—„], [â–¼], [â–²] Setting value control key
4. Indicator
Display Name Description
°C, %, °F Unit Displays selected unit (parameter)
AT Auto tuning Flashes during auto tuning every 1 sec
OUT1/2 Control
output
Turns ON when the control output is ON
• SSR output (cycle/phase control)
MV over 5% ON
• Current output
Manual control: 0% OFF, over ON
Auto control: below 2% OFF, over 3% ON
AL1 Alarm
output Turns ON when the alarm output is ON
MAN Manual
control Turns ON during manual control
SV1/2/3 Multi SV The SV indicator is ON which is currently
displayed. (When using multi SV function)
TK4S
5. PC loader port:
For connecting
communication
converter (SCM series).
Dimensions
• Unit: mm
■ Panel cut-out
Body Panel cut-out
A B C D E F G H I J
TK4S 48 48 ≥65 ≥656 64.5 1.7 45 45 +0.6
045 +0.6
0
â– Bracket
TK4S
Simultaneous Heating & Cooling
Output PID Temperature Controller
TK4S-14RC
Item no.: 3016144
INSTRUCTION MANUAL
TCD210240AD
Installation Method
â– TK4S
Flathead screwdriver
After mounting the product to panel with bracket, insert the unit into a panel, fasten the bracket by
pushing with a flathead screwdriver.
Errors
Display Input Description Output Troubleshooting
Temperature
sensor
Flashes at 0.5 sec interval
when input sensor is
disconnected or sensor is not
connected.
'Sensor error, MV'
parameter setting
value
Check input sensor
status.
Analog Flashes at 0.5 sec interval
when input is over F.S. ±10%.
'Sensor error, MV'
parameter setting
value
Check analog input
status.
Temperature
sensor
Flashes at 0.5 sec intervals if
the input value is above the
input range.
01)
Heating: 0%,
Cooling: 100%
When input is within
the rated input
range, this display
disappears.
Analog Flashes at 0.5 sec intervals if
the input value is over 5 to 10%
of high limit or low limit value.
Normal output
Temperature
sensor
Flashes at 0.5 sec. intervals
if the input value is below the
input range.
01)
Heating: 100%,
Cooling: 0%
Analog
Flashes at 0.5 sec intervals if
the input value is over 5 to 10%
of low limit or high limit value. Normal output
Temperature
sensor
Flashes at 0.5 sec intervals if
there is error for setting and
it returns to the error-before
screen.
- Check setting method.
Analog
01) Be careful that when / error occurs, the control output may occur by recognizing the maximum or minimum input
depending on the control type.
Connections
• Shaded terminals are standard model.
• Digital input is not electrically insulated from internal circuits, so it should be insulated when
connecting other circuits.
â– TK4S
Crimp Terminal Specifications
• Unit: mm, use the crimp terminal of the following shape.
≥3.0
≤5.8
≥3.0
≤5.8
Fork crimp terminal Round crimp terminal
Initial Display When Power is ON
When power is supplied, after all display will flash for 1 sec, model name is displayed sequentially. After
input sensor type will flash twice, enter into RUN mode.
1. All display 2. Model 3. Input
specification 4. Run mode
PV display part
SV display part
Mode Setting
RUN
RUN
Auto before entering
to mode (when using
password)
Move digits: [â—„]
Change value: [â–²], [â–¼]
Save: [MODE] or no
key input over 5 sec
Password Key input Entering mode
Pass Auto Selected mode
Fail [â—„], [â–²], [â–¼] Password input
[MODE] Run mode
[MODE] over 3 sec
Refer to ‘Parameter Reset’
[A/M]
Auto
[â—„], [â–²], [â–¼]
Password input
SV setting
Parameter group
Parameter reset
Auto/Manual control
switching
Digital input key
[MODE] over 2 sec
[â—„] + [â–²] + [â–¼] over 5 sec
[â–²] + [â–¼] over 3 sec
[A/M] 01)
01) In case of TK4S model, short press of [MODE] key replaces [A/M] key function.
Parameter Reset
01. Pressthe[◄]+[▲]+[▼]keysforover5sec.inrunmode,INITturnsON.
02. ChangethesettingvalueasYESbypressingthe[▲],[▼]keys.
03. Pressthe[MODE]keytoresetallparametervaluesasdefaultandtoreturntorunmode.
Parameter Setting
• Some parameters are activated/deactivated depending on the model or setting of other parameters.
• The 'Parameter mask' feature hides unnecessary or inactive parameters, and the 'User parameter
group' feature quickly and easily sets up certain parameters that are frequently used.
• Refer to the user manual for the details.
Disposal
This symbol must appear on any electrical and electronic equipment placed on the EU
market. This symbol indicates that this device should not be disposed of as unsorted
municipal waste at the end of its service life.
Owners of WEEE (Waste from Electrical and Electronic Equipment) shall dispose of it
separately from unsorted municipal waste. Spent batteries and accumulators, which are not
enclosed by the WEEE, as well as lamps that can be removed from the WEEE in a non-
destructive manner, must be removed by end users from the WEEE in a non-destructive
manner before it is handed over to a collection point.
Distributors of electrical and electronic equipment are legally obliged to provide free take-back of waste.
Conrad provides the following return options free of charge (more details on our website):
• in our Conrad offices
• at the Conrad collection points
• at the collection points of public waste management authorities or the collection points set up by
manufacturers or distributors within the meaning of the ElektroG
End users are responsible for deleting personal data from the WEEE to be disposed of.
It should be noted that different obligations about the return or recycling of WEEE may apply in countries
outside of Germany.
■ Parameter 1 group
Parameter Display Default
Control output RUN/STOP
Multi SV selection
Heater current monitoring
Alarm output1 low limit
Alarm output1 high limit
Multi SV 0
Multi SV 1
Multi SV 2
Multi SV 3
■ Parameter 2 group
Parameter Display Default
Auto tuning RUN/STOP
Heating proportional band
Cooling proportional band
Heating integral time
Cooling integral time
Heating derivative time
Cooling derivative time
Dead overlap band
Manual reset
Heating hysteresis
Heating OFF offset
Cooling hysteresis
Cooling OFF offset
MV low limit
MV high limit
RAMP up change rate
RAMP down change rate
RAMP time unit
■ Parameter 3 group
Parameter Display Default
Input specification
Temperature unit
Analog low limit
Analog high limit
Scaling decimal point
Low limit scale
High limit scale
Display unit
Input correction
Input digital filter
SV low limit
SV high limit
Control output mode (Normal type)
(Heating& Cooling type)
Control type (Normal type)
(Heating& Cooling-type)
Auto tuning mode
OUT1 control output selection
OUT2 control output selection
OUT2 current output range
Heating control cycle
(Relay)
(SSR)
Cooling control cycle
■ Parameter 4 group
Parameter Display Default
Alarm output1 Operation mode
Alarm output1 Option
Alarm output1 Hysteresis
Alarm output1 contact type
Alarm output1 ON delay time
Alarm output1 OFF delay time
LBA time
LBA band
Analog Transmission output1 Mode
Transmission output1 low limit
Transmission output1 high limit
Analog Transmission output2 Mode
Transmission output2 low limit
Transmission output2 high limit
Communication address
Communication speed
Comm. parity bit
Comm. stop bit
Response time
Comm. write
■ Parameter 5 group
Parameter Display Default
Multi SV number
Digital input key
Digital input1 Terminal Function
Digital input2 Terminal Function
Manual control, initial MV
Manual control, preset MV
Sensor error MV
Control stop MV
Control stop alarm output
User level
SV setting lock
Parameter 1 group lock
Parameter 2 group lock
Parameter 3 group lock
Parameter 4 group lock
Parameter 5 group lock
Password setting
This is a publication by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau (www.conrad.com).
All rights including translation reserved. Reproduction by any method, e.g. photocopy, microîš¿lming, or the
capture in electronic data processing systems require the prior written approval by the editor. Reprinting, also
in part, is prohibited. This publication represents the technical status at the time of printing.
Copyright 2024 by Conrad Electronic SE.
*BN3016144_TK4S-14RC_INST_W_V1_EN_20240417
Product specificaties
Merk: | Tru Components |
Categorie: | Thermostaat |
Model: | TK4S-14RC |
Heb je hulp nodig?
Als je hulp nodig hebt met Tru Components TK4S-14RC stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Thermostaat Tru Components
18 December 2024
18 December 2024
17 December 2024
12 December 2023
12 December 2023
12 December 2023
12 December 2023
12 December 2023
Handleiding Thermostaat
- Thermostaat Bosch
- Thermostaat Panasonic
- Thermostaat Bticino
- Thermostaat AEG
- Thermostaat ATAG
- Thermostaat Honeywell
- Thermostaat Junkers
- Thermostaat Nefit
- Thermostaat Remeha
- Thermostaat Siemens
- Thermostaat Vaillant
- Thermostaat ACV
- Thermostaat Agpo Ferroli
- Thermostaat Airwell
- Thermostaat Alecto
- Thermostaat Ambiano
- Thermostaat Amfra
- Thermostaat Arnold Rak
- Thermostaat ATTACK
- Thermostaat AVM
- Thermostaat AWB
- Thermostaat Basetech
- Thermostaat Berker
- Thermostaat Boneco
- Thermostaat Brennenstuhl
- Thermostaat Brink
- Thermostaat Bryant
- Thermostaat Buderus
- Thermostaat Bulex
- Thermostaat Daikin
- Thermostaat Danfoss
- Thermostaat De Dietrich
- Thermostaat Devi
- Thermostaat Devolo
- Thermostaat Dimplex
- Thermostaat Drayton
- Thermostaat Drayton Erie
- Thermostaat Easy Timer
- Thermostaat EasyTemp
- Thermostaat EBERLE
- Thermostaat Econo-Heat
- Thermostaat Elco
- Thermostaat Elektrobock
- Thermostaat Elgato
- Thermostaat Eliwell
- Thermostaat Elro
- Thermostaat ELV
- Thermostaat Emerson
- Thermostaat Emmeti
- Thermostaat Enda
- Thermostaat Eneco
- Thermostaat EQ-3
- Thermostaat Eqiva
- Thermostaat Essent
- Thermostaat Etherma
- Thermostaat Eurotronic
- Thermostaat Extraflame
- Thermostaat Feller
- Thermostaat Ferguson
- Thermostaat Ferroli
- Thermostaat Finder
- Thermostaat GE
- Thermostaat Gira
- Thermostaat Go Green
- Thermostaat Google
- Thermostaat Grasslin
- Thermostaat Grohe
- Thermostaat Hager
- Thermostaat Hama
- Thermostaat Helios (Amfra)
- Thermostaat HomeMatic
- Thermostaat Hornbach
- Thermostaat HQ
- Thermostaat Hugo Muller
- Thermostaat Hunter
- Thermostaat ICY
- Thermostaat Intergas
- Thermostaat IR-V
- Thermostaat Itho
- Thermostaat Itho-Daalderop
- Thermostaat Landis Gyr
- Thermostaat Levica
- Thermostaat Lowes
- Thermostaat Magnum
- Thermostaat Max
- Thermostaat Muller
- Thermostaat Nest
- Thermostaat Netatmo
- Thermostaat Niko
- Thermostaat Nobo
- Thermostaat Noma
- Thermostaat Perel
- Thermostaat Plieger
- Thermostaat Plugwise
- Thermostaat Profile
- Thermostaat Rademacher
- Thermostaat Radson
- Thermostaat REMKO
- Thermostaat Renkforce
- Thermostaat RWE
- Thermostaat Salus
- Thermostaat Saunier Duval
- Thermostaat Schneider
- Thermostaat Silvercrest
- Thermostaat Somfy
- Thermostaat Stiebel Eltron
- Thermostaat Sygonix
- Thermostaat Tado
- Thermostaat Taurus
- Thermostaat Techno Line
- Thermostaat Technoline
- Thermostaat Tesla
- Thermostaat TFA
- Thermostaat Theben
- Thermostaat THERMAFLEX
- Thermostaat Thermy
- Thermostaat TP Link
- Thermostaat Trotec
- Thermostaat Truma
- Thermostaat UPM
- Thermostaat Vasco
- Thermostaat VDH
- Thermostaat Velleman
- Thermostaat Viessmann
- Thermostaat Wachendorff
- Thermostaat Watts
- Thermostaat Webasto
- Thermostaat Weishaupt
- Thermostaat Westfalia
- Thermostaat Wolf
- Thermostaat Worcester-Bosch
- Thermostaat Xavax
- Thermostaat Z-Wave
- Thermostaat Zehnder
- Thermostaat Johnson Control
- Thermostaat Jung
- Thermostaat Oertli
- Thermostaat OJ ELECTRONICS
- Thermostaat Orbis
- Thermostaat Oregon Scientific
- Thermostaat Otio
- Thermostaat Schwaiger
- Thermostaat Fenix
- Thermostaat Conrad
- Thermostaat Corberó
- Thermostaat EMOS
- Thermostaat King
- Thermostaat Cotech
- Thermostaat Avidsen
- Thermostaat Hive
- Thermostaat Kemot
- Thermostaat Coati
- Thermostaat Nexa
- Thermostaat SPC
- Thermostaat Baxi
- Thermostaat Aube
- Thermostaat Carrier
- Thermostaat Cepra
- Thermostaat Delta Dore
- Thermostaat ELKO
- Thermostaat Fantini Cosmi
- Thermostaat Heatmiser
- Thermostaat Heimeier
- Thermostaat Horstmann
- Thermostaat IMIT
- Thermostaat Oventrop
- Thermostaat Seitron
- Thermostaat TrickleStar
- Thermostaat Tylö
- Thermostaat Vemer
- Thermostaat Warmup
- Thermostaat Fibaro
- Thermostaat Energenie
- Thermostaat Mikoterm
- Thermostaat Ariston Thermo
- Thermostaat Carel
- Thermostaat Busch-Jaeger
- Thermostaat EVE
- Thermostaat Optima
- Thermostaat Frico
- Thermostaat EQ3
- Thermostaat Homematic IP
- Thermostaat Computherm
- Thermostaat Wattio
- Thermostaat Crestron
- Thermostaat ORNO
- Thermostaat POER
- Thermostaat Heatit
- Thermostaat 2Heat
- Thermostaat Veria
- Thermostaat ThermoSmart
- Thermostaat Yokis
- Thermostaat Vimar
- Thermostaat PECO
- Thermostaat H-Tronic
- Thermostaat Intertechno
- Thermostaat Emko
- Thermostaat Innogy
- Thermostaat Wallair
- Thermostaat Maico
- Thermostaat HomePilot
- Thermostaat Ouellet
- Thermostaat ChiliTec
- Thermostaat Tellur
- Thermostaat Jumo
- Thermostaat Qubino
- Thermostaat STI
- Thermostaat Gewiss
- Thermostaat Sinustec
- Thermostaat Rose LM
- Thermostaat MundoControl
- Thermostaat Bearware
- Thermostaat GENERAL Life
- Thermostaat Oreg
- Thermostaat Braeburn
Nieuwste handleidingen voor Thermostaat
29 Januari 2025
28 Januari 2025
16 December 2024
16 December 2024
15 December 2024
11 December 2024
10 December 2024
9 December 2024
9 December 2024
9 December 2024