Important Safety Instructions 2
Installation 3
Basic Operation 5
Battery Replacement 11
Storage and Service 11
SmartOnline™
True On-Line Tower UPS Systems
Warranty Registration 12
Español
Français 25
13
Copyright ©2009 Tripp Lite. All rights reserved. SmartOnline
™ is a trademark of Tripp Lite.
Troubleshooting 9
Warranty
Registration:
register online today for a chance
to win a FREE Tripp Lite product—
www.tripplite.com/warranty
Not suitable for mobile applications.
2
UPS Location Warnings
• InstallyourUPSindoors,awayfromexcessmoistureorheat,conductivecontaminants,
dustordirectsunlight.
• Forbestperformance,keeptheindoortemperaturebetween32ºFand104ºF(0ºCand
40ºC).
• LeaveadequatespacearoundallsidesoftheUPSforproperventilation.
• Donotmountunitwithitsfrontorrearpanelfacingdown(atanyangle).
 Mountinginthismannerwillseriouslyinhibittheunit’sinternalcooling,eventually
 causingproductdamagenotcoveredunderwarranty.
UPS Connection Warnings
• ConnectyourUPSdirectlytoaproperlygroundedACpoweroutlet.Donotplugthe
UPSintoitself;thiswilldamagetheUPS.
• DonotmodifytheUPS'splug,anddonotuseanadapterthatwouldeliminatetheUPS’s
groundconnection.
• DonotuseextensioncordstoconnecttheUPStoanACoutlet.Yourwarrantywillbe
voidedifanythingotherthanTrippLitesurgesuppressorsareusedtoconnectyourUPS
to an outlet.
• IftheUPSreceivespowerfromamotor-poweredACgenerator,thegeneratormust
provideclean,filtered,computer-gradeoutput.
Equipment Connection Warnings
• Useofthisequipmentinlifesupportapplicationswherefailureofthisequipmentcan
reasonablybeexpectedtocausethefailureofthelifesupportequipmentorto
significantlyaffectitssafetyoreffectivenessisnotrecommended.Donotusethis
equipmentinthepresenceofaflammableanestheticmixturewithair,oxygenornitrous
oxide.
• DonotconnectsurgesuppressorsorextensioncordstotheoutputofyourUPS.This
mightdamagetheUPSandwillvoidthesurgesuppressorandUPSwarranties.
Battery Warnings
Batteriescanpresentariskofelectricalshockandburnfromhighshort-circuitcurrent.
Observeproperprecautions.Donotdisposeofthebatteriesinafire.DonotopentheUPS
orbatteries.Donotshortorbridgethebatteryterminalswithanyobject.Unplugandturn
offtheUPSbeforeperformingbatteryreplacement.Usetoolswithinsulatedhandles.
Therearenouser-serviceablepartsinsidetheUPS.Batteryreplacementshouldbe
performedonlybyauthorizedservicepersonnelusingthesamenumberandtypeof
batteries(SealedLead-Acid).Thebatteriesarerecyclable.Refertoyourlocalcodesfor
disposalrequirementsorintheUSAonlycall1-800-SAV-LEADor1-800-8-BATTERY
(1-800-822-8837)orvisitwww.rbrc.comforrecyclinginformation.TrippLiteoffersa
completelineofUPSSystemReplacementBatteryCartridges(R.B.C.).VisitTrippLiteon
theWebatwww.tripplite.com/support/battery/index.cfmtolocatethespecificreplacement
batteryforyourUPS.
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the
installation,operationandstorageofallTrippLiteUPSSystems.Failuretoheedthese
warningswillvoidyourwarranty.
2
Important Safety Instructions
1
2
3
1
33
Important Safety Instructions
Connection and Start-Up
Plug your UPS’s line cord into an
electrical outlet.
Your UPS must be connected to a dedicated
circuit of sufficient amperage.Note,however,
that the select models may be fitted with
differentplugtypes.Refertothe“OPRating/
PlugRating”chartprinted onthetopof your
UPS.
OnceyourUPSisplugged in,thefanandall
IndicatorLightswillturnON.The“LINE”and
“LOADACTIVEMETER”LEDswillilluminate
andtheUPSwillemitabeeptoindicatenormal
operation. However, power is not supplied to
your UPS’sAC outletsuntil theUPS isturned
on.
Plug your equipment into your UPS.
Your UPS is designed to support computer
equipmentonly.YouwilloverloadyourUPSif
you connect household appliances or laser
printerstotheUPS'soutlets.
Turn your UPS ON:
• Pressthe“ON/TEST”Button
• Holditforseveralsecondsuntilyou
 hearabeep
• Releaseit
Your UPS will begin providing AC power to its outlets.
The “ON LINE” LED will illuminate.
Your UPS will function properly without these
connections.
Phone Line or Phone/Network
Line Surge Suppression
Your UPS has jacks which protect against
surges on a phone or network line.* Using
appropriate network cords connect your wall
jack to the UPS jack marked “IN.” Connect
your equipment to the UPS jack marked
“OUT.”Makesuretheequipmentyouconnect
to the UPS's jacks is also protected against
surgesontheACline.
*NotcompatiblewithPoE(PowerOverEthernet)applications.
Your model may differ.
1
2
3
Your model
may differ.
Installation
Optional Connections
1
Your model may differ.


Product specificaties

Merk: Tripp Lite
Categorie: UPS
Model: SU750XL
Kleur van het product: Zwart
Gewicht: 13020 g
Breedte: 171.4 mm
Diepte: 336.6 mm
Hoogte: 254 mm
Snoerlengte: 3 m
Geluidsniveau: 45 dB
Gewicht verpakking: 14420 g
Breedte verpakking: 254 mm
Diepte verpakking: 454.7 mm
Hoogte verpakking: 353.1 mm
Materiaal behuizing: Staal
LED-indicatoren: Ja
Vormfactor: Tower
Land van herkomst: China
Aantal USB 2.0-poorten: 1
Aantal Ethernet LAN (RJ-45)-poorten: 1
Certificering: UL1778, CSA, FCC
Geluidsalarm(en): Ja
Duurzaamheidscertificaten: RoHS
Aansluitingen: 6x 5-15R
Uitgangsvermogen: 600 W
Accu/Batterij oplaadtijd: 6 uur
Temperatuur bij opslag: -15 - 50 °C
Stroomspanning bescherming: Over voltage,Under voltage
Frequentie: 50/60 Hz
Power factor: 0.8
Type koeling: Actief
Seriële poort(en): 1
Modem (RJ-11) poort: 1
Stekker: NEMA 5-15P
Efficientie: 87 procent
(Buitenste) hoofdverpakking hoogte: 353.1 mm
(Buitenste) hoofdverpakking breedte: 254 mm
(Buitenste) hoofdverpakking brutogewicht: 14420 g
(Buitenste) hoofdverpakking lengte: 454.7 mm
Hoeveelheid per (buitenste) hoofdverpakking: 1 stuk(s)
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 95 procent
Surge energy rating: 570 J
Aantal AC uitgangen: 6 AC-uitgang(en)
Stopcontacttypes: NEMA 5–15R
Golf protectie functies: Fax,Modem,Network,Telephone
Stroom (max.): 15 A
Output power capacity: 0.75 kVA
Ingang operation voltage (min): 100 V
Ingang operation voltage (max): 120 V
Uitgang operation voltage (min): 100 V
Uitgang operation voltage (max): 120 V
Crest factor: 3:1
UPS-topologie: Dubbele conversie (online)
Aantal input fases: 1
Typische backup tijd op halve lading: 11 min
Typische backup tijd op volledige lading: 4 min
Hot-swap batterij: Ja
Emergency Power Off (EPO): Ja
Uitgangsspanningsregeling: +/- 2 procent
EMI/RFI geluidsfiltering: Ja
Spanningsbeveiliging: Ja
Golfvorm: Sinus
Koude start: Ja