Tripp Lite SMART3000RMOD2U Handleiding

Tripp Lite UPS SMART3000RMOD2U

Lees hieronder de 📖 handleiding in het Nederlandse voor Tripp Lite SMART3000RMOD2U (16 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 75 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/16
Introduction 2
Features 3
Mounting 5
Quick Installation 7
Optional Installation 8
Basic Operation 9
Power Module Replacement 12
Battery Replacement 13
Storage 14
Service 14
Warranty 15
Warranty Registration 15
Owners Manual
SmartPro® Rackmount
Intelligent, Line-Interactive UPS System
Model: SMART3000RMOD2U
110/120/127V Sine Wave Input/Output • 3000VA
1111 W. 35th Street, Chicago, IL 60609 USA • (773) 869-1234 •www.tripplite.com
Copyright © 2008 Tripp Lite. All rights reserved. SmartPro
® is a registered trademark of Tripp Lite.
Not suitable for mobile applications.
Warranty
Registration:
register online today for a
chance to win a FREE Tripp Lite
product—www.tripplite.com/warranty
Español 17
Français 33
2
UPS Location Warnings
The UPS is extremely heavy. Use caution when lifting and installing.•
Install the UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.•
Install the UPS in a structurally sound area. •
Only operate the UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures •
between 62° F and 84° F (between 1 C and 29° C).
Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its ventilation fans or openings.
•
Do not install the UPS near magnetic storage media, as this may result in data corruption.•
If you are installing the UPS in a stack configuration, always stack the power module above the battery module(s) if present.•
Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit's internal •
cooling, eventually causing product damage not covered under warranty.
UPS Connection Warnings
The power supply for this unit must be rated in accordance with the equipment nameplate. It also must be suitably grounded.
Connect the UPS system only to a NEMA L5-30R receptacle (outlet).
Connect the UPS to a properly grounded AC power source. Do not modify the input connection in a way that would eliminate the connection to
ground.
Do not use adapters that eliminate the connection to ground.
Do not connect the UPS input to its output; this will damage the UPS and void the warranty.
If you are connecting the UPS to a motor-powered AC generator, the generator must provide filtered, frequency-regulated computer-grade output.
Connecting the UPS to a generator will void its Ultimate Lifetime Insurance.
Equipment Connection Warnings
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support
equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable
anesthetic mixture with air, oxygen or nitrous oxide
The UPS is connected to a DC energy source (battery). The output terminals may be live even when the UPS is not connected to an AC power
source.
Do not connect surge suppressors or extension cords to the output of the UPS. This might overload the UPS and will void the surge suppressor and
UPS warranties.
Maintenance Warnings
The UPS does not require routine maintenance. Do not open the UPS for any reason. There are no user-serviceable parts inside.
Battery Warnings
Connect only Tripp Lite battery packs to the battery connectors. Connect battery packs of the correct voltage and type.
Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the batteries
in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS before
performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement should be
performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). The batteries are recyclable. Refer
to your local codes for disposal requirements or in the USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit
www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite
on the Web at www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.
Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
Fuses should be replaced only by factory-authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
Service and repair should be performed only by trained personnel. During any service work to the UPS, it should be turned off.
Do not connect or disconnect external battery pack(s) while the UPS is operating from the battery supply.
During hot-swap battery pack replacement, the UPS will not provide backup power in the event of a blackout or other power interruption.
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed
during the installation and maintenance of this UPS system.
Introduction
3
1
5
9
10
11
12
23
4
6
7
8
The SMART3000RMOD2U UPS System features a hot-swappable power module. When the bracket holding the power module in place is removed (there
is no manual bypass switch on the unit), the UPS automatically switches to “BYPASS” mode. This allows the power module to be removed for mainte-
nance, repair or replacement without disrupting power to connected loads. Review the location and function of the UPS system’s features before installing
and operating it.
1 “Load/Battery” Bar Graph: This display indicates the power load and battery levels.
2
“On” Button: Press this button and hold it for one second until you hear a beep to turn the UPS System ON. If the battery alarm is sounding,
press this button to silence it.
3 Off/StandbyButton: Press this button and hold it for one second to turn the UPS system OFF.
4
“Load Level” LED (Green): This LED illuminates when the Load/Battery Bar Graph is displaying the load level.
5
“Battery Capacity” LED (Green): This LED illuminates when the Load/Battery Bar Graph is displaying the battery capacity.
6
AC Mode” LED (Green): This LED illuminates when the UPS System is ON and supplying connected equipment with AC power from a utility
source.
7
Automatic Voltage Regulation (AVR) Mode” LED (Yellow): This LED illuminates whenever the UPS system is lowering voltage and blinks
continuously when the UPS is boosting voltage.
8
“Overload” LED (Red): When this LED is illuminated, the load is >105%. Clear the overload immediately by unplugging some of your
equipment from the outlets until the LED changes from red to yellow (or green). CAUTION! Any overload that is not immediately corrected
by the user may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout.
9
“UPS Fault” LED (Red): This LED illuminates if the UPS system has an internal fault.
10
Site Wiring Fault” LED (Red): This LED illuminates if the UPS system detects a site wiring problem.
11
“Battery Fault” LED (Yellow): This LED illuminates if the UPS system senses a weak, bad or disconnected battery.
12
“On Battery” LED (Green): This LED illuminates if the UPS system is operating from battery power.
Front Control Panel
Features


Product specificaties

Merk: Tripp Lite
Categorie: UPS
Model: SMART3000RMOD2U
Kleur van het product: Zwart
Gewicht: 39500 g
Breedte: 444 mm
Diepte: 610 mm
Hoogte: 89 mm
Snoerlengte: 3 m
Gewicht verpakking: 47200 g
Breedte verpakking: 605 mm
Diepte verpakking: 1011 mm
Hoogte verpakking: 234 mm
Materiaal behuizing: Staal
LED-indicatoren: Ja
Vormfactor: Rackmontage/toren
Aantal USB 2.0-poorten: 1
Certificering: UL1778, CSA, NOM, FCC
Geluidsalarm(en): Ja
Responstijd: 4 ms
Duurzaamheidscertificaten: RoHS, ENERGY STAR
Uitgangsvermogen: 2880 W
Accu/Batterij oplaadtijd: 4 uur
Temperatuur bij opslag: -15 - 50 °C
Stroomspanning bescherming: Over voltage, Under voltage
Frequentie: 50/60 Hz
Type koeling: Actief
Seriële poort(en): 1
Stekker: NEMA L5-30P
Efficientie: 95 procent
Rackcapaciteit: 2U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 95 procent
Surge energy rating: 800 J
Aantal AC uitgangen: 7 AC-uitgang(en)
Nominale input voltage: 120 V
Stopcontacttypes: NEMA 5–15R, NEMA L5-30R
Stroom (max.): 30 A
Output power capacity: 3 kVA
Ingang operation voltage (min): 90 V
Ingang operation voltage (max): 146 V
Uitgang operation voltage (min): 100 V
Uitgang operation voltage (max): 127 V
UPS-topologie: Line-interactive
Aantal input fases: 1
Typische backup tijd op halve lading: 11 min
Typische backup tijd op volledige lading: 4 min
Hot-swap batterij: Ja
Netspanning, in bedrijf: 120 V
Emergency Power Off (EPO): Ja
EMI/RFI geluidsfiltering: Ja
Golfvorm: Sinus
Koude start: Ja
Automatic Voltage Regulation (AVR): Ja

Heb je hulp nodig?

Als je hulp nodig hebt met Tripp Lite SMART3000RMOD2U stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding UPS Tripp Lite

Handleiding UPS

Nieuwste handleidingen voor UPS