Tripp Lite SmartPro SMART2000RMXL2U Handleiding
Tripp Lite
UPS
SmartPro SMART2000RMXL2U
Lees hieronder de 📖 handleiding in het Nederlandse voor Tripp Lite SmartPro SMART2000RMXL2U (64 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 16 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/64
1
Owner’s Manual
Español 22
Français 43
SmartPro® 2U Rack-Mount
Intelligent, Line-Interactive UPS Systems
120V Sine Wave Output • 2200VA—3000VA Capacities
SMART2200RM2U,
SMART2200RM2UN
(Series Number: AGSM8207)
SMART2000RMXL2U,
SMART2200RMXL2U,
SMART2200RMXLN
(Series Number: AGSM8208)
SM2200RMXL2UP
(Series Number: AGSM7012)
SMART3000RM2U,
SMART3000RM2UN
(Series Number: AGSM8209)
SMART3000RMXL2U,
SMART3000RMXLN
(Series Number: AGSM7010)
SMART2600RM2U
(Series Number: AGSM7012)
Not suitable for mobile applications.
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2019 Tripp Lite. All rights reserved.
WARRANTY REGISTRATION
Register your product today and be
automatically entered to win an ISOBAR
surge protector in our monthly drawing!
www.tripplite.com/warranty
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation,
operation and storage of this product. Failure to heed these warnings may affect the warranty.
UPS Location Warnings
• Use caution when lifting the UPS. Because of the considerable weight of all rack-mount UPS
systems, at least two people should assist in lifting and installing them.
• Install the UPS indoors, away from excess moisture or heat, dust or direct sunlight.
• For best performance, the ambient temperature near the UPS should be between 0° C and 40° C
(between 32° F and 104° F).
• Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents
or fan openings.
• When mounting the UPS system in a tower orientation, make sure the LCD panel is at the top of
the UPS, not at the bottom.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner
will seriously inhibit the unit’s internal cooling, eventually causing product damage not covered
under warranty.
UPS Connection Warnings
• The UPS contains its own energy source (battery). The output terminals may be live even when
the UPS is not connected to an AC supply.
• Connect the UPS to a properly grounded AC power outlet. Do not modify the UPS’s plug in a way
that would eliminate the UPS’s connection to ground. Do not use adapters that eliminate the
UPS’s connection to ground.
• Do not plug the UPS into itself; this will damage the UPS and void your warranty.
• If you are connecting the UPS to a motor-powered AC generator, the generator must provide
filtered, frequency-regulated computer-grade output. Connecting the UPS to a generator will void
its Ultimate Lifetime Insurance.
• Install in accordance with National Electrical Code standards ANSI/NFPA 70 and Canadian
Electrical Code, Part I, C22.1.
• Short Circuit backup protection and overcurrent protection is provided by the building installation
for permanently connected models.
• To reduce the risk of fire, connect only to a circuit provided branch circuit overcurrent protection
in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code,
Part I, C22.1. Be sure to use maximum 20A overcurrent protection for model AGSM7012,
and maximum 30A overcurrent protection for model AGSM7010, in accordance with the plug/
equipment rating, for the installation.
• The plug on the power supply cord is intended to serve as the disconnect device. Be sure that the
socket-outlet is installed near the equipment and is made easily accessible.
Caution! This UPS receives power from more than one source. Disconnection of the
AC and DC sources is required to de-energize the unit before servicing.
3
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its safety
or effectiveness is not recommended.
• Do not connect surge protectors or extension cords to the output of the UPS. This might damage
the UPS and may affect the surge suppressor and UPS warranties.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe
proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or batteries.
Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS before
performing battery replacement. Use tools with insulated handles. There are no user-serviceable
parts inside the UPS. Battery replacement should be performed only by authorized service
personnel using the same number and type of batteries (Sealed Lead-Acid). The batteries are
recyclable. Refer to your local codes for disposal requirements or visit http://www.tripplite.com/
support/recycling-program for recycling information. Tripp Lite offers a complete line of UPS
System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web at http://www.tripplite.
com/products/battery-finder/ to locate the specific replacement battery for your UPS.
• During hot-swap battery replacement, the UPS will not provide backup power in the event of a
blackout or other power interruptions.
• Do not operate the UPS without batteries.
External Battery Connection Warnings
• When adding external battery packs to select models with external battery pack connectors,
connect only Tripp Lite-recommended battery packs of the correct voltage and type. Do not
connect or disconnect battery packs when the UPS is operating on battery power.
Visit www.tripplite.com/support/battery/index.cfm to locate the supported battery type(s) for
your UPS.
UPS and Battery Recycling
Please recycle Tripp Lite Products. The batteries used in Tripp Lite products are
sealed Lead-Acid batteries. These batteries are highly recyclable. Please refer to
your local codes for disposal requirements.
You can call Tripp Lite for recycling info at 773.869.1234.
You can go the Tripp Lite Website for up-to-date information on recycling the batteries or any
Tripp Lite product. Please follow this link: http://www.tripplite.com/support/recycling-program/
Important Safety Instructions
Product specificaties
Merk: | Tripp Lite |
Categorie: | UPS |
Model: | SmartPro SMART2000RMXL2U |
Kleur van het product: | Zwart |
Gewicht: | 26130 g |
Breedte: | 439.9 mm |
Diepte: | 490 mm |
Hoogte: | 87.9 mm |
Snoerlengte: | 3.1 m |
Geluidsniveau: | 45 dB |
Gewicht verpakking: | 32340 g |
Breedte verpakking: | 617.2 mm |
Diepte verpakking: | 548.6 mm |
Hoogte verpakking: | 215.9 mm |
Gebruikershandleiding: | Ja |
Materiaal behuizing: | Staal |
Vormfactor: | Rackmontage |
USB-poort: | Ja |
Meegeleverde kabels: | Serial, USB cable |
Ingebouwde ventilator: | Ja |
Land van herkomst: | China |
Aantal USB 2.0-poorten: | 1 |
Certificering: | FCC Part 15 Category A, CSA, NOM, UL1778 |
Geluidsalarm(en): | Ja |
Duurzaamheidscertificaten: | RoHS |
Uitgangsvermogen: | 1920 W |
Temperatuur bij opslag: | -15 - 50 °C |
Stroomspanning bescherming: | Over voltage, Under voltage |
Frequentie: | 60 Hz |
Luchtvochtigheid bij opslag: | 0 - 95 procent |
Power factor: | 0.96 |
Type koeling: | Actief |
Seriële poort(en): | 1 |
Stekker: | NEMA 5-20P |
Efficientie: | 96 procent |
(Buitenste) hoofdverpakking hoogte: | 215.9 mm |
(Buitenste) hoofdverpakking breedte: | 617.2 mm |
(Buitenste) hoofdverpakking brutogewicht: | 32340 g |
(Buitenste) hoofdverpakking lengte: | 548.6 mm |
Hoeveelheid per (buitenste) hoofdverpakking: | 1 stuk(s) |
Rackcapaciteit: | 2U |
Bedrijfstemperatuur (T-T): | 0 - 40 °C |
Relatieve vochtigheid in bedrijf (V-V): | 0 - 95 procent |
Type beeldscherm: | LCD |
Surge energy rating: | 570 J |
Aantal AC uitgangen: | 8 AC-uitgang(en) |
Stopcontacttypes: | NEMA 5–15R, NEMA 5–20R |
Stroom (max.): | 16 A |
Rekbevestigingspakket: | Ja |
Output power capacity: | 2 kVA |
Ingang operation voltage (min): | 83 V |
Ingang operation voltage (max): | 145 V |
Uitgang operation voltage (min): | 110 V |
Uitgang operation voltage (max): | 120 V |
UPS-topologie: | Line-interactive |
Aantal input fases: | 1 |
Typische backup tijd op halve lading: | 12 min |
Typische backup tijd op volledige lading: | 4.5 min |
Hot-swap batterij: | Ja |
Seriële interface: | Ja |
Output frequentie: | 60 Hz |
Hoorbare alarmstanden: | Alarm when on battery, Fault, Low battery alarm, Overload alarm |
Emergency Power Off (EPO): | Ja |
Uitgangsspanningsregeling: | -14 - 6 procent |
EMI/RFI geluidsfiltering: | Ja |
Golfvorm: | Zuivere sinus |
Noodstop-aansluiting (EPO): | Ja |
Koude start: | Ja |
Automatic Voltage Regulation (AVR): | Ja |
USB-poorttype: | USB Type-B |
Heb je hulp nodig?
Als je hulp nodig hebt met Tripp Lite SmartPro SMART2000RMXL2U stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS Tripp Lite
15 November 2024
18 September 2024
20 Juni 2023
16 Juni 2023
13 Juni 2023
12 Juni 2023
3 Juni 2023
27 Mei 2023
12 Mei 2023
10 Mei 2023
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS CyberPower
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
14 December 2024
14 December 2024
10 December 2024
10 December 2024
8 December 2024
8 December 2024
2 December 2024
2 December 2024
2 December 2024
2 December 2024