Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved. SmartPro
® is a registered trademark of Tripp Lite.
Important Safety Instructions 2
Mounting 4
Quick Installation 6
Optional Installation 7
Basic Operation 9
Storage and Service 17
Battery Replacement 18
Warranty Registration 20
Español 21
Français 41
SmartPro® 2U Rackmount
Intelligent, Line-Interactive UPS Systems
120V Sine Wave Output • 1,000VA—1,500VA
SMART1500RMXL2UA
(AG-0006, AG-02F7)
SMART1500RM2U
(AG-0007, AG-02F8)
SMART1000RMXL2U
(AG-0011, AG-02F9)
Not suitable for mobile applications.
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
18-05-213-933148.indb 1 7/13/2018 1:04:15 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation,
operation and storage of this product. Failure to heed these warnings may affect the warranty.
UPS Location Warnings
• Use caution when lifting the UPS. Because of the considerable weight of all rackmount UPS
systems, at least two people should assist in lifting and installing them.
• Install the UPS indoors, away from excess moisture or heat, dust or direct sunlight.
• For best performance, the ambient temperature near the UPS should be between 0° C and 40° C
(between 32° F and 104° F).
• Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents
or fan openings.
• When mounting the UPS system in a tower orientation, make sure the LCD Screen panel is at the
top of the UPS, not at the bottom.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner
will seriously inhibit the unit’s internal cooling, eventually causing product damage not covered
under warranty.
UPS Connection Warnings
• The UPS contains its own energy source (battery). The output terminals may be live even when
the UPS is not connected to an AC supply.
• Connect the UPS to a properly grounded AC power outlet. Do not modify the UPS’s plug in a way
that would eliminate the UPS’s connection to ground. Do not use adapters that eliminate the
UPS’s connection to ground.
• Do not plug the UPS into itself; this will damage the UPS and void your warranty.
• If you are connecting the UPS to a motor-powered AC generator, the generator must provide
filtered, frequency-regulated computer-grade output. Connecting the UPS to a generator will void
its Ultimate Lifetime Insurance.
• Install in accordance with National Electrical Code standards ANSI/NFPA 70 and Canadian
Electrical Code, Part I, C22.1.
• Short circuit backup protection and overcurrent protection are provided by the building installation
for permanently connected models.
• To reduce the risk of fire, connect only to a circuit provided branch circuit overcurrent protection
in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code,
Part I, C22.1. Be sure to use maximum 20A overcurrent protection, in accordance with the plug/
equipment rating, for the installation.
• The plug on the power supply cord is intended to serve as the disconnect device. Be sure that the
socket-outlet is installed near the equipment and is made easily accessible.
Caution! This UPS may receive power from more than one source. Disconnection
of the AC and DC sources is required to de-energize the unit before servicing.
18-05-213-933148.indb 2 7/13/2018 1:04:15 PM
3
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its safety
or effectiveness is not recommended.
• Do not connect surge suppressors or extension cords to the output of the UPS. This might
damage the UPS and may affect the surge suppressor and UPS warranties.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe
proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or batteries.
Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS before
performing battery replacement. Use tools with insulated handles. There are no user-serviceable
parts inside the UPS. Battery replacement should be performed only by authorized service
personnel using the same number and type of batteries (Sealed Lead-Acid). Tripp Lite offers a
complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the Web
at www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your
UPS. The RBC Type can also be found on the label affixed to the Battery Retention Plate.
• During hot-swap battery replacement, the UPS will not provide backup power in the event of a
blackout or other power interruptions.
• Do not operate the UPS without batteries.
External Battery Connection Warnings
• When adding external battery packs to select models with external battery pack connectors,
connect only Tripp Lite-recommended battery packs of the correct voltage and type. Do not
connect or disconnect battery packs when the UPS is operating on battery power. Visit
www.tripplite.com/support/battery/index.cfm to locate the supported battery type(s) for your UPS.
UPS and Battery Recycling
Please recycle Tripp Lite products. The batteries used in Tripp Lite products are sealed lead
acid batteries. These batteries are highly recyclable. Please refer to your local codes for
disposal requirements.
Call Tripp Lite for recycling info at 773.869.1234. Or go to the Tripp Lite website for
up-to-date information on recycling the batteries or any Tripp Lite product:
http://www.tripplite.com/support/recycling-program/
Important Safety Instructions
18-05-213-933148.indb 3 7/13/2018 1:04:15 PM
Product specificaties
Merk: | Tripp Lite |
Categorie: | UPS |
Model: | SmartPro SMART1000RMXL2U |
Heb je hulp nodig?
Als je hulp nodig hebt met Tripp Lite SmartPro SMART1000RMXL2U stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS Tripp Lite
15 November 2024
18 September 2024
20 Juni 2023
16 Juni 2023
13 Juni 2023
12 Juni 2023
3 Juni 2023
27 Mei 2023
12 Mei 2023
10 Mei 2023
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS CyberPower
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
14 December 2024
14 December 2024
10 December 2024
10 December 2024
8 December 2024
8 December 2024
2 December 2024
2 December 2024
2 December 2024
2 December 2024