Tripp Lite SmartOnline SU10000RT3TFTAA Handleiding
Tripp Lite
UPS
SmartOnline SU10000RT3TFTAA
Lees hieronder de 📖 handleiding in het Nederlandse voor Tripp Lite SmartOnline SU10000RT3TFTAA (104 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 24 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/104
1
Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA
www.tripplite.com/support
Copyright © 2011 Tripp Lite. All rights reserved. SmartOnline is a trademark of Tripp Lite.
SmartOnline™
Single-Phase 8kVA—10kVA
Intelligent True On-Line UPS Systems (Rackmount/Tower)
• Includes power module, external battery module and PDU
• Detachable PDU features outlets and maintenance bypass switch* • Rackmount and tower adaptable
*An optional detachable hardwire PDU is available; contact Tripp Lite for details.
Not suitable for mobile applications.
Important Safety Warnings 2
Mounting 3
Connection 6
Features 4
Operation 12
Storage and Service 26
Warranty and Warranty Registration 26
Optional Connection 8
Manual Bypass Operation 9
Specifications 11
WARRANTY
REGISTRATION:
register online today for a
chance to win a FREE Tripp Lite
product—www.tripplite.com/warranty
Español 27
Français 53
Ðóññêèé 79
201102160 93-2897.indb 1 3/30/2011 9:30:37 AM
2
Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and
maintenance of all Tripp Lite SmartOnline Rackmount/Tower UPS Systems and their batteries. Failure to heed these warnings may affect your
warranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
• Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
• Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor
temperatures between 62° F and 84° F (between 17° C and 29° C).
• Leave adequate space around all sides of the UPS for proper ventilation.
• Do not install the UPS near magnetic storage media, as this may result in data corruption.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit's
internal cooling, eventually causing product damage not covered under warranty.
UPS Connection Warnings
• Isolate the UPS before working on this circuit.
• Required Protective Devices and Cable Cross-Sections.
Recommended upstream protection.
UPS wer Rating Upstream Circuit BreakerPo
8kV
A D
cur -63Ave
10kVA D cur -83Ave
G L1
L1
2 poles circuit breaker
To UPS Normal sourceAC
L2(N)
L2(N)
• The power supply for this unit must be single-phase rated in accordance with
the equipment nameplate. It also must be suitably grounded.
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
• Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
Maintenance Warnings
• Your UPS power module and battery module(s) do not require routine maintenance. Do not open them for any reason. There are no user-
serviceable parts inside.
Battery Warnings
• Do not operate your UPS without connecting it to an external battery module.
• Connect only Tripp Lite battery modules to your UPS power module’s external battery connector.
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the
batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS
before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement
should be performed only by authorized service personnel using the same number and type of batteries (Sealed Lead-Acid). The batteries
are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-
822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges
(R.B.C.).Visit Tripp Lite on the Web at www.tripplite.com/support/battery/index.cfm to locate the specific replacement battery for your UPS.
• Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
• Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
• Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed
via the transformer. Note that potentially lethal voltages exist within this unit as long as the battery supply
is connected.
• Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the detachable PDU is not in bypass
mode.
• During “hot-swap” battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.
• Only connect compatible battery module(s).
Legend.
B Contactor solenoid.
Q Mains input thermal-magnetic itchsw
T Two-pole contactor 100 A 1; coil ltage: according to the mains input.AC vo
Remark: Q needs to use the approved component of Safety Certification.
External po rwe
distribution unit UPS
L
Q
B
T
N
L
N
201102160 93-2897.indb 2 3/30/2011 9:30:37 AM
3
Mounting (Rack)
4-Post Mounting
1 The included plastic pegs A will temporarily support the empty rackmount shelves B while
you install the permanent mounting hardware. Insert a peg near the center of the front and rear
bracket of each shelf as shown. (Each front bracket has 6 holes and each rear bracket has 3 holes.)
The pegs will snap into place.
After installing the pegs, expand each shelf to match the depth of your rack rails. The pegs will
fit through the square holes in the rack rails to support the shelves. Refer to the rack unit labels to
confirm that the shelves are level in all directions. Note: The support ledge of each shelf must
face inward.
2 Secure the shelves B to the mounting rails permanently using the included screws and cup
washers C as shown.
• For 2U equipment mounting, place 4 screws total at the front and 4 screws total at the back.
• For 3U equipment mounting, place 6 screws total at the front and 4 screws total at the back.
Tighten all screws before proceeding.
Warning: Do not attempt to install your equipment until you have inserted and tightened
the required screws. The plastic pegs will not support the weight of your equipment.
3 Attach mounting ears D to the front mounting holes of your equipment E using the screws
provided F. The ears should face forward.
4 Using an assistant, lift your equipment and slide it onto the mounting shelves. Attach your
equipment to the rack by passing the screws, nuts and washers (user-provided) G through its
mounting ears and into the rack rails.
5 (Optional) Attach 2 PDU hanger brackets to the right-side, rear mounting rail using included
screws and cage nuts. Important: determining where to attach your PDU hanger brackets will
depend on your rack configuration. Generally it is recommended to mount the top bracket in
the bottom two square holes of the U space that the UPS and PDU are mounted in. The second
bracket should be installed 3U measures down and placed in the top two square holes of the U.
(For example: If the PDU and UPS are mounted in 7U, the first bracket will be installed in the
bottom two square holes of 7U. The second bracket would be installed in the top two square holes
of 4U.
Mount your equipment in either a 4-post or 2-post rack or rack enclosure. The user must determine the fitness of hardware and procedures before
mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rack enclosure. The procedures
described in this manual are for common rack and rack enclosure types and may not be appropriate for all applications.
Note: The power module and battery module must be installed in separate shelves.
2-Post Mounting (Optional)
To mount your equipment in a 2-post rack, you must purchase a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTRMKITWM, sold
separately) for each module installed. See the Installation Kit’s owner’s manual for complete mounting instructions.
3
E
D
G
F
4
1
BB
A
A
A
2
2
B
B
B
B
C
C
C
C
7
6
5
4
Mount Here
5
201102160 93-2897.indb 3 3/30/2011 9:30:39 AM
Product specificaties
Merk: | Tripp Lite |
Categorie: | UPS |
Model: | SmartOnline SU10000RT3TFTAA |
Kleur van het product: | Zwart |
Diepte: | 838.2 mm |
Geluidsniveau: | 60 dB |
Gewicht verpakking: | 231330 g |
Breedte verpakking: | 660.4 mm |
Diepte verpakking: | 1041.4 mm |
Hoogte verpakking: | 1016 mm |
Gebruikershandleiding: | Ja |
Materiaal behuizing: | Staal |
LED-indicatoren: | Ja |
Vormfactor: | Rackmontage |
USB-poort: | Ja |
Meegeleverde kabels: | RS-232, USB cable |
Ingebouwde ventilator: | Ja |
Land van herkomst: | Taiwan |
Aantal USB 2.0-poorten: | 1 |
RS-232 port: | 1 |
Geluidsalarm(en): | Ja |
Responstijd: | 0 ms |
Duurzaamheidscertificaten: | RoHS |
Uitgangsvermogen: | 9000 W |
Temperatuur bij opslag: | -15 - 50 °C |
ECO mode: | Ja |
Stroomspanning bescherming: | Over voltage, Under voltage |
Frequentie: | 50/60 Hz |
Luchtvochtigheid bij opslag: | 0 - 95 procent |
Naleving van duurzaamheid: | Ja |
Gewicht batterij: | 72120 g |
Hoogte, in bedrijf: | 0 - 3000 m |
Power factor: | 0.9 |
Type koeling: | Actief |
Seriële poort(en): | 2 |
Stekker: | Hardwire |
Efficientie: | 91 procent |
(Buitenste) hoofdverpakking hoogte: | 1016 mm |
(Buitenste) hoofdverpakking breedte: | 660.4 mm |
(Buitenste) hoofdverpakking brutogewicht: | 231330 g |
(Buitenste) hoofdverpakking lengte: | 1041.4 mm |
Hoeveelheid per (buitenste) hoofdverpakking: | 1 stuk(s) |
Rackcapaciteit: | 10U |
Bedrijfstemperatuur (T-T): | 0 - 40 °C |
Relatieve vochtigheid in bedrijf (V-V): | 0 - 95 procent |
Batterijtechnologie: | Sealed Lead Acid (VRLA) |
Type beeldscherm: | LCD |
Surge energy rating: | 2565 J |
Aantal AC uitgangen: | 30 AC-uitgang(en) |
Stopcontacttypes: | NEMA 5–15R, NEMA 5–20R, NEMA L6-20R, NEMA L6-30R |
Stroom (max.): | 60 A |
Rekbevestigingspakket: | Ja |
Output power capacity: | 10 kVA |
Ingang operation voltage (min): | 120 V |
Ingang operation voltage (max): | 208 V |
Uitgang operation voltage (min): | 120 V |
Uitgang operation voltage (max): | 208 V |
Crest factor: | 3:1 |
UPS-topologie: | Dubbele conversie (online) |
Aantal input fases: | 1 |
Typische backup tijd op halve lading: | 12.5 min |
Typische backup tijd op volledige lading: | 4.3 min |
Hot-swap batterij: | Ja |
Seriële interface: | Ja |
Output frequentie: | 60 Hz |
Emergency Power Off (EPO): | Ja |
Uitgangsspanningsregeling: | +/- 2 procent |
EMI/RFI geluidsfiltering: | Ja |
Golfvorm: | Zuivere sinus |
Noodstop-aansluiting (EPO): | Ja |
Koude start: | Ja |
Uitgangsfrequentieregeling: | +/- 0.05 Hz |
Efficiëntie (ECO-modus): | 96 procent |
USB-poorttype: | USB Type-B |
Heb je hulp nodig?
Als je hulp nodig hebt met Tripp Lite SmartOnline SU10000RT3TFTAA stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS Tripp Lite
15 November 2024
18 September 2024
20 Juni 2023
16 Juni 2023
13 Juni 2023
12 Juni 2023
3 Juni 2023
27 Mei 2023
12 Mei 2023
10 Mei 2023
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS CyberPower
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
14 December 2024
14 December 2024
10 December 2024
10 December 2024
8 December 2024
8 December 2024
2 December 2024
2 December 2024
2 December 2024
2 December 2024