1. Basic safety information
Danger of death through electric shock or fire!
Installation should only be carried out by a qualied
electrician!
WARNING
The device is designed for installation on DIN top hat rails (in
accordance with IEC 60715)
It complies with product standard EN 60669-2-1
Do not operate the device outside the specied technical data
!The device must be installed in an enclosed switchgear cabinet
made of metal or an appropriate re-resistant material!
!After proper installation, the housing component under the
cover must not be accessible!
2. Proper use
Control box TC 649 C is an annual time switch with astronomical
function, which can be controlled and updated via Theben Cloud and
managed centrally from a computer and a smartphone. The control
box is used for lighting and ventilation.
!Do not use on safety devices, e.g. escape route doors, re
safety equipment, etc.
Disposal
For an environmentally appropriate disposal, send the device back
to the owner
3. Installation and connection
Installing TC 649 C
click
Connecting TC 649 C
Connecting the power supply
Strip cable to 8 mm (max. 9 mm)
Insert the line into the terminal and fasten it
Plug terminal into power supply socket
Connect to power supply
During the start of the operating system, all LEDs are ashing.
After approx. 150 s the start process is completed and the
power LED (PWR/TLS) ashes.
Wiring diagram
L
L
N
L L LN
L L
L
N
TC 649 C
LSwitch the load with a contactor.
!If a load is switched directly, secure the device with a circuit
breaker of 6 A.
4. Device description
Connections
Service interface
Connection to LAN
network
Power supply
socket (230 V)
Voltage
LThe performance specications can be found on the side and on
the device shoulder (see picture). After installation they are not
visible any more!
2
LEDs
LStatus messages are indicated by four LEDs.
LEDs for
status messages
TC 649 C
Label Description
Web server Web server started
Time Connection to NTP server
Relay at least 1 relay connected
PWR/TLS Power and TLS
5. Start-up
For the professional electrician/network administrator
LBy default, the network interface is set to DHCP.
LFor conguration with a static IP address, see
https://www.theben.de/tc-649-en/
Connect TC 649 C with the local network at LAN interface
„Ethernet“.
Connect voltage.
During the start of the operating system, all LEDs are ashing.
After approx. 150 s the start process is completed and the
power LED (PWR/TLS) ashes.
For the operator
To use the TC 649 C device, proceed as follows:
Access via host name (DHCP):
Enter the host name in the address bar of the browser (only with
Google Chrome). The host name is the serial number of TC 649 C
(printed on the housing)
Example: http://dthe0200001234
If access via the host name does not work (depending on router), use
the manual at https://www.theben.de/tc-649-en/
Access via static IP address:
To set up access via a static IP address, use the manual
LDuring initial operation, enter the user name “admin” and the
password “admin” to log in.
LBy default, the network interface is set to DHCP. If the TC 649 C
device is to be used without DHCP server, please contact your
network administrator or use the manual.
Start-up with Theben Cloud, use the manual.
Operation using the App OBELISK top3
You can access the cloud directly via the OBELISK top3 app.
Download OBELISK software
The OBELISK software is required to carry out an ot.2 download in the
Control menu. It can be found at
https://www.theben.de/en/pc-set-obelisk-top2-3-9070409
6. Technical data
Operating voltage: extended operating range
230 V~, –20% +15%
Switching capacity: 6 A/250 V AC, cos = 1 ϕ
Switching of any external conductor
is permitted. Switching SELV is only
permissible if both switching channels,
top or bottom, switch SELV.
Minimum load: 5 V / 1 mA
Switch contact: µ contact
Frequency: 50 Hz
Power consumption: 3 W
Set operating range: –10 °C to +45 °C
Threshold for operation: –25 °C to +55 °C
Threshold for storage and
transport:
–25 °C to +70 °C
Humidity: 95%, non-condensing
Protection class: II subject to designated installation
Protection rating: IP 30
7. Contact
Service address
Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Phone +49 7474 692-0
Fax +49 7474 692-150
8. Use of open source software
LThis product uses open source software (OSS). A list of the OSS
components used and their licence type and version can be found
at https://www.theben.de/tc-649-en/
LIf you need to connect groups of devices, please contact the
Theben hotline.
Hotline
Phone +49 7474 692-369
hotline@theben.de
Addresses, telephone numbers etc.
www.theben.de


Product specificaties

Merk: Theben
Categorie: Niet gecategoriseerd
Model: TC 649 C

Heb je hulp nodig?

Als je hulp nodig hebt met Theben TC 649 C stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Theben

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd