System Sensor P2RL-SP Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor System Sensor P2RL-SP (4 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 263 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/4
1 I56-5845-001
01-12
BEFORE INSTALLING
Please read the System Sensor Audible Visible Application Reference Guide,
which provides detailed information on notification devices, wiring and spe-
cial applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed.
Important: The notification appliance used must be tested and maintained
following NFPA 72 requirements.
GENERAL DESCRIPTION
System Sensor series of notification appliances offer a wide range of audible
and visible devices for life safety notification. Our 2-wire horn strobes, chime
strobes and strobes come with 8 field selectable tone and volume combina-
tions and 7 field selectable candela settings. Intended for indoor applications
and approved for wall mount installations only. Available in two attractive
mounting designs, standard and compact (horn strobe and strobe only).
2-wire horn strobes and strobes are public mode notification appliances in-
tended to alert occupants of a life safety event. The 2-wire chime strobe is
a private mode notification appliance. The horn is listed to ANSI/UL 464
requirements (public mode) and the strobe is listed to ANSI/UL 1638 (pub-
lic mode). 2-wire chime strobe is a private mode notification appliances in-
tended to alert trained personnel to investigate a life safety event and take
appropriate actions. The chime portion of the chime strobe is listed to ANSI/
UL 464 (private mode) and the strobe portion is listed to ANSI/UL 1638 (pri-
vate mode).
System Sensor notification appliances are designed to be used in either 12
VDC, 24VDC, or 24V FWR (full wave rectified) systems. System Sensor AV de-
vices can be activated by a compatible fire alarm control panel or power sup-
ply. Refer to the appropriate fire alarm control panel manufacturer or power
supply for more information.
System Sensor wall 2-wire horn strobes, 2-wire chime strobes, and strobes are
electrically backward compatible with the previous generation, since 1996,
of notification appliances. They come enabled with System Sensor synchro-
nization protocol which requires connections to a power supply capable of
generating the System Sensor synchronization pulses, a FACP NAC output
configured to System Sensor synchronization protocol, or the use of MDL3
module to generate the synchronization protocol.
FIRE ALARM SYSTEM CONSIDERATIONS
The National Fire Alarm and Signaling Code, NFPA 72, requires that all noti-
fication appliances, used for building evacuation installed after July 1, 1996,
produce temporal coded signals. Signals other than those used for evacuation
purposes do not have to produce the temporal coded signal. System Sensor
recommends spacing notification appliances in compliance with NFPA 72.
SYSTEM DESIGN
The system designer must make sure that the total current draw by the devices
on the loop does not exceed the current capability of the panel supply, and
that the last device on the circuit is operated within its rated voltage. The
current draw information for making these calculations can be found in the
tables within the manual. For convenience and accuracy, use the voltage drop
calculator on the System Sensor website (www.systemsensor.com).
When calculating the voltage available to the last device, it is necessary to
consider the voltage due to the resistance of the wire. The thicker the wire, the
smaller the voltage drop. Wire resistance tables can be obtained from electri-
cal handbooks. Note that if Class A wiring is installed, the wire length may
be up to twice as long as it would be for circuits that are not fault tolerant.
The total number of strobes on a single NAC must not exceed 69 for 24 volt
applications.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Selectable Output
Horn Strobes, Chime Strobes
and Strobes – Wall Mount
For use with the following models:
Standard Wall Mount Horn Strobes: P2RL, P2WL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP
Compact Wall Mount Horn Strobes: P2GRL, P2GWL
Standard Wall Mount Chime Strobes: CHSRL, CHSWL
Standard Wall Mount Strobes: SRL, SWL, SRL-P, SWL-P, SRL-SP, SWL-CLR-ALERT
Compact Wall Mount Strobes: SGRL, SGWL
PRODUCT SPECIFICATIONS
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% Non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage: Regulated 12VDC or regulated 24DC/FWR
Operating Voltage Range: 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL3 Sync Module: 8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)
Input terminal wire gauge: 12 to 18 AWG
DIMENSIONS FOR PRODUCTS AND ACCESSORIES
WALL PRODUCTS Length Width Depth
Standard Strobe, Chime Strobe and Horn Strobe
5.6" (143mm) 4.7" (119mm) 1.25" (32mm)
Compact Strobe and Horn Strobe
5.26" (133 mm) 3.46" (88 mm) 1.93 (49 mm)
Standard device with SBBRL/WL Surface Mount Back Box 5.9" (149 mm) 4.9" (125 mm) 1.85" (47 mm)
C
ompact device with
SBBGRL/WL Surface Mount Back Box
5.5" (140 mm) 3.7" (94 mm) 1.6" (39 mm)
NOTE: SBBRL/WL Surface Mount Back Box intended only for standard horn strobes, chime strobes and strobes.
SBBGRL/WL Surface Mount Back Box intended for compact horn strobes and strobes.
MOUNTING BOX OPTIONS
Standard 2-Wire Indoor Products: 4" x 4" x 1½", Single Gang, Double Gang, 4" Octagon, SBBRL/WL (wall), SBBGRL/WL (wall)
Compact 2-Wire Indoor Products: Single Gang, SBBGRL/WL (wall)
NOTICE: This manual shall be left with the owner/user of this equipment.
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
I56-5845-001
2 I56-5845-001
01-12
FIGURE 3. LIGHT OUTPUT – FIGURE 4. VERTICAL
HORIZONTAL DISPERSION DISPERSION– WALL TO FLOOR
Degrees* Percent of
Rating Degrees* Percent of
Rating
0 0100 100
5-25 90 5-30 90
30-45 75 35 65
50 55 40 46
55 45 45 34
60 40 2750
65 35 55 22
70 35 60 18
75 65 1630
80 1530 70
85 25 75 13
90 25 80 12
Compound 45
to the left 24 85 12
Compound 45
to the right 24 90 12
A0467-00
A0469-00
*Tolerance of ±1 degree is permitted.
WIRING AND MOUNTING
All wiring must be installed in compliance with the National Electric Code
and the local codes as well as the authority having jurisdiction. Wiring must
not be of such length or wire size which would cause the notification appli-
ance to operate outside of its published specifications. Improper connections
can prevent the system from alerting occupants in the event of an emergency.
Wire sizes up to 12 AWG (2.5 mm°) may be used with the mounting plate.
The mounting plate ships with the terminals set for 12 AWG wiring.
Make wire connections by stripping about
3
/
8
" of insulation from the end of
the wire. Then slide the bare end of the wire under the appropriate clamping
plate and tighten the clamping plate screw.
We provide a wire strip guide. See Figure 5 for wiring terminals and strip
guide reference.
CAUTION
Factory finish should not be altered: Do not paint!
CAUTION
Do not over tighten mounting plate screws; this may cause mounting plate
to flex.
FIGURE 5. WIRING TERMINALS, SHORTING SPRING, AND STRIP GUIDE
Shorting Spring
Strip Guide
WIRING TERMINALS
1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out
A0475-01
SYSTEM WIRING
The 2-wire horn strobe, chime strobe and strobe only require two wires for
power and supervision. (See Figure 6.) Please consult your FACP manufac-
turer or power supply manufacturer for specific wiring configurations and
special cases.
AVAILABLE TONES
System Sensor offers a wide variety of tones for your life safety needs, includ-
ing temporal 3 pattern (½ second on, ½ second off, ½ second on, ½ second
off, ½ second on, 1½ off and repeat) which is specified by ANSI and NFPA 72
for standard emergency evacuation signaling.
To select the tone, turn the rotary switch on the back of the product to the
desired setting. (See Figure 1.)
Available horn settings can be found in Table 1. Available chime settings can
be found in Table 2.
TABLE 1. HORN TONES
Pos Tone Volume Setting
1 Temporal High
2 Temporal Low
3 Non-Temporal High
4 Non-Temporal Low
5 3.1 KHz Temporal High
6 3.1 KHz Temporal Low
7 3.1 KHz Non-Temporal High
8 3.1 KHz Non-Temporal Low
TABLE 2. CHIME TONES
Pos Tone Volume Setting
1 1 Second Chime High
2 1 Second Chime Low
3 1/4 Second Chime High
4 1/4 Second Chime Low
5 Temporal Chime High
6 Temporal Chime Low
7 5 Second Whoop High
8 5 Second Whoop Low
AVAILABLE CANDELA SETTINGS
System Sensor offers a wide range of candela settings for your life safety
needs. In order to select your candela output, adjust the slide switch on the
rear of the product to the desired candela setting on the selector switch. (See
Figure 2.)
The candela setting can also be verified by looking into the small window on
the front of the unit. See Table 3 for candela settings for wall products. All
products meet the light output profiles specified in the appropriate UL Stan-
dards. (See Figures 3 and 4.)
CURRENT DRAW AND AUDIBILITY RATINGS
For the strobe, the current draw for each setting is listed in Table 3. For the
horn strobe, the current draw and audibility settings are listed in Table 4. For
the chime strobe, the current draw and audibility settings are listed in Table 5.
TABLE 3. WALL-MOUNT STROBE CURRENT DRAW (mA)
Candela
8-17.5
Volts 16-33 Volts
DC DC FWR
15 88 43 60
NOTE: Products set at 15 and 30
candela automatically work on ei-
ther 12V or 24V power supplies.
The products are not listed for
12V DC operation when set to any
other candela settings.
30 143 63 83
75 - 107 136
95 - 121 155
110 - 148 179
135 - 172 209
185 - 222 257
FIGURE 1. AUDIO SELECTOR
A0517-00
FIGURE 2. CANDELA SELECTOR
A0486-00
3 I56-5845-001
01-12
TABLE 4. WALL-MOUNT HORN STROBE CURRENT DRAW (mA) AND SOUND OUTPUT (dBA)
NOTE: Products set at 15 and 30 candela automatically work on either 12V or 24V power supplies. The products are not listed for 12VDC operation when set to
any other candela settings.
TABLE 5. WALL MOUNT CHIME STROBE CURRENT DRAW (mA) AND SOUND OUTPUT (dBA)
NOTE: Products set at 15 and 30 candela automatically work on either 12V or 24V power supplies. The products are not listed for 12VDC operation when set to
any other candela settings.
Current draw (mA)
Sound Output (dBA)
Pos Tone Volume
Setting
8-17.5 VDC 16-33 VDC 16-33 FWR
8-17.5 V 16-33 V
15 30 30 75 95 135 185 30 75 95 135 18515 110 15 110
DC DC FWR
1 Temporal High 98 158 54 74 142 162 196 245 83 156 177 198 234 287 84 89 89121 107
2 Temporal 93 154 44 65 133 157 184 235 68 145 165 185 223 75 83 83Low 111 91 271
3 Non-Temporal High 166 73 94 139 160 182 262 135 185 264 85 90 90106 211 111 207 230 316
4 Non-Temporal 93 156 139 162 190 239 79 157 175 197 235 283 76 84 84Low 51 71 119 104
53.1 KHz
Temporal High 93 156 53 73 140 164 190 242 155 177 196 234 284 83 88 88119 81 105
63.1 KHz
Temporal Low 91 154 45 66 133 160 185 235 68 90 145 166 186 222 276 76 82 82112
73.1 KHz
Non-Temporal High 99 162 69 90 135 157 175 177 264 326 84 89 89208 261 104 131 204 230
83.1 KHz Non-
Temporal Low 93 156 52 72 138 162 192 242 77 156 177 199 234 77 83 83119 102 291
Current draw (mA)
Sound Output (dBA)
Pos Chime Tone Volume
Setting
8-17.5 VDC 16-33 VDC 16-33 FWR
8-17.5 V 16-33 V
15 30 30 75 95 135 185 30 75 95 135 18515 110 15 110
DC DC FWR
1 1 Second High 90 154 136 242 90 160 176 197 233 275 62 6251 71 116 161 202 70 61
2 1 Second 89 154 136 154 199 238 67 88 158 175 232 56 55 55Low 50 70 115 191 271
3 1/4 Second High 90 154 52 72 137 168 242 69 93 159 175 198 233 272 67117 201 70 70
4 1/4 Second 89 153 49 136 165 199 68 93 154 169 196 232Low 70 115 241 270 61 61 61
5 Temporal High 88 153 49 69 137 168 246 65 90 145 189 228 283 64 66 66112 201 170
6 Temporal 88 152 47 68 136 167 196 64 89 142 188 282 59 60 60Low 111 241 170 219
75 Second
Whoop High 154 52 132 176 243 93 145 168 187 223 278 76 78 7891 70 113 206 70
85 Second
Whoop Low 130 20287 149 46 66 108 170 240 62 84 137 159 180 272 62 64 64216
FIGURE 6. 2-WIRE CIRCUIT
+
–
+
–
INPUT
FROM
FACP
OR
PRIOR
DEVICE
OUTPUT
TO
NEXT
DEVICE
OR EOL
A0367-02
SHORTING SPRING FEATURE
System Sensor notification appliances come with a shorting spring that is pro-
vided between terminals 2 and 3 of the mounting plate to enable system con-
tinuity checks after the system has been wired, but prior to installation of the
final product. (See Figure 5.) This spring will automatically disengage when
the product is installed, to enable supervision of the final system.
MOUNTING
1. Attach mounting plate to junction box. The standard mounting plate is
compatible with 4" square, single gang, double gang, and 4" octagon junction
boxes. The compact mounting plate is compatible with single gang junction
boxes. (See Figures 7 and 8, respectively.)
2. Connect field wiring according to terminal designations. (See Figures 5 and
6.)
3. If the product is not to be installed at this point, use the protective dust
cover to prevent contamination of the wiring terminals on the mounting plate.
4. To attach product to mounting plate, hook tabs on the top of the product
housing into the grooves on mounting plate. Then, hinge the product into
FIGURES 7 AND 8. MOUNTING
Standard Device
A087-00
Compact Device
A0488-00
FIGURES 9 AND 10. SURFACE MOUNT BACK BOX MOUNTING:
Standard SBBRL/SBBWL
A0490-00
Compact SBBGRL/SBBGWL
A0491-00


Product specificaties

Merk: System Sensor
Categorie: Niet gecategoriseerd
Model: P2RL-SP
Kleur van het product: Rood
Soort: Bedrade sirene
Licht alarm: Ja
Afmetingen (B x D x H): 119 x 64 x 142 mm
Bedrijfstemperatuur (T-T): 0 - 49 °C
Relatieve vochtigheid in bedrijf (V-V): 10 - 93 procent
Plaatsing beschikbaar: Binnen

Heb je hulp nodig?

Als je hulp nodig hebt met System Sensor P2RL-SP stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd System Sensor

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd