System Sensor F-A3384-000 Handleiding


Lees hieronder de đź“– handleiding in het Nederlandse voor System Sensor F-A3384-000 (1 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 46 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/1
F-A3384-000 Air Filter Assembly
INSTALLATION AND MAINTENANCE INSTRUCTIONS
GENERAL DESCRIPTION
The F-A3384-000 replacement air filter for the FAAST™ 8100 series aspiration
detectors comes fully assembled and ready to use. It is a 30 micron filter de-
signed specifically for use with the FAAST system.
FILTER ASSEMBLY REPLACEMENT
The filter is located behind the Display Door under the User Interface Card, as
shown in Figure 1.
FIGURE 1. FRONT VIEW OF DETECTOR WITH DISPLAY DOOR OPEN AND
USER INTERFACE CARD IN PLACE:
USER INTERFACE CARD
ASP-82
To replace the filter perform the procedure in Table 1.
TABLE 1. FILTER REPLACEMENT PROCEDURE
STEP ACTION
1 Before performing maintenance, notify the proper authorities that the
system is undergoing maintenance, and will temporarily be out of ser-
vice. Disable the system to prevent unwanted alarms.
2 Turn off the system by removing the 24 Volt power connector from the unit
or by unplugging the converter from its power outlet.
NOTE: If power is not removed, the unit automatically enters Service
Mode when the screws are removed from the filter. This removes
power from the fan and the sensing chamber. In addition, the filter
fault indicator is illuminated and the urgent relay is set.
3 Open the Display Door, as shown in Figure 1, and remove the User
Interface card in front of the filter.
4 Remove the two Philips head screws securing the filter to the unit,
as shown in Figure 2.
5 Replace the entire filter assembly, as shown in Figure 3, with a new
unit by pulling the old filter out and sliding a new filter assembly
back into position.
6 Torque the two Philips head screws to 6in-lb (0.7N-m) or ÂĽ turn
past “lightly snug”. DO NOT OVER TIGHTEN.
7 Carefully reinstall the User Interface card.
1 I56-3743-003
©2016 System Sensor. 06-10
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
I56-3743-003
FILTER MOUNTING SCREWS
(DO NOT OVERTIGHTEN)
ASP90-01
FIGURE 3. REMOVABLE AIR FILTER ASSEMBLY:
FILTER MOUNTING SCREWS
(DO NOT OVERTIGHTEN)
ASP91-01
FIGURE 2. FILTER MOUNTING SCREWS WITH USER INTERFACE
CARD REMOVED:


Product specificaties

Merk: System Sensor
Categorie: Niet gecategoriseerd
Model: F-A3384-000

Heb je hulp nodig?

Als je hulp nodig hebt met System Sensor F-A3384-000 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd System Sensor

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd