Interlogix ESL 500N Handleiding
Interlogix
Rookmelder
ESL 500N
Lees hieronder de đ handleiding in het Nederlandse voor Interlogix ESL 500N (8 pagina's) in de categorie Rookmelder. Deze handleiding was nuttig voor 35 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/8
Š 2017 United Technologies Corporation 1 / 8 P/N 1036525-EN ⢠REV F
ESL 500N Series Smoke Detector
Installation Sheet
Description
Note: This document is intended for licensed electricians or
alarm installers. We cannot provide technical support to
unqualified persons. If you have any questions, contact us
using the âContact informationâ on page 8.
The ESL 500N Series conventional two-wire and four-wire
photoelectric smoke detectors have intelligent software and
digitally processed sensing capabilities. This intelligence,
coupled with the ESL patented optical sensing chamber,
means the ESL 500N Series quickly and accurately detects
smoke. CleanMe compatible software, self-diagnostics, and
dust (drift) compensation are standard in every unit. The ESL
500N Series offers application flexibility with optional auxiliary
relays, rate-of-rise/fixed temperature heat sensors, isolated
heat sensors and/or 85 dBA temporal-three sounders.
Standard features
All models ship standard with the features described below.
Detector-base lock: Discourages unauthorized removal of the
smoke detector by requiring a screwdriver to remove the
detector from the base.
Self-diagnostics: Includes automatic sensitivity testing. Once
a day and immediately upon first power up, each 500N Series
detector performs a full diagnostic test that includes a dynamic
test of the sensing chamber and internal electronics. This
meets NFPA 72 field sensitivity testing requirements without
the need for external meters.
Drift compensation (dust compensation): The detectors
automatically adjust sensitivity, up to a maximum of 1.0%/ft.,
as the detectors become dirty.
Additional features
Depending on the model, the smoke detector may also provide
the following features.
CleanMe: Enables a CleanMe compatible control panel to
receive a warning signal, indicating that the optical chamber
needs to be replaced. This feature is available on the 500N
Series two-wire detectors only.
The 500N Series two-wire detectors enable the CleanMe
function by recognizing voltage polarity at installation. If the +
and â terminal connections are reversed, the CleanMe function
is enabled. New 500N Series detectors are compatible on the
same loop with previous 500 Series detectors if proper wiring
is observed. See âWiringâ on page 4.
Integral temporal-three sounder: In the 500N models with
sounder, a piezoelectric horn produces an interrupted 85 dBA
tone when the detector alarms or when the polarity is reversed.
Sounder follows input voltage in reverse polarity.
In order for all sounders to activate when the panel alarms, the
panel must reverse the supply voltage polarity to the loop on
alarm. If the panel does not implement polarity reversal, an
ESL 405 Polarity Reversal Relay Module must be used. (Refer
to the installation sheet for the ESL 405 Polarity Reversal
Relay Module.)
Auxiliary and end-of-line relays: Auxiliary relays are Form C
and operate at 1 A at 30 VDC to allow for the addition of
auxiliary notification devices to the smoke loops. Products with
an âRâ in the suffix signify the auxiliary relay feature.
An end-of-line relay operates as a power supervision relay and
is normally energized and will release with the loss of power.
Products with an âEâ in the suffix signify the end-of-line feature.
Heat sensors: Some models come with rate-of-rise or fixed
temperature heat sensors which allow the unit to detect
changes in temperature that may signal a fire event. Models
with an âXTâ in the suffix have a heat sensor included.
Some models are available with an isolated heat sensor. If the
unit senses a temperature change it will alert the panel and
signal an alarm independent of smoke in the photoelectric
chamber. The heat alarm output is on the alarm relay and the
smoke detector output is on the auxiliary relay. Models with an
âHâ in the suffix have an isolated heat sensor which is both rate
of-rise and fixed temperature.
2 / 8 P/N 1036525-EN ⢠REV F
Compatibility
Please refer to the ESL Compatibility Index for a complete
listing of control panels and proper identifiers. For a copy of the
compatibility index, see âContact informationâ on page 8.
Remember, four-wire smoke detectors do not require a
compatibility listing.
Selecting a location
Selecting a suitable location is critical to the operation of
smoke detectors. This equipment should be installed in
accordance with NFPA 72. Figure 1 shows required and
additional locations.
Figure 1: Detector location
(1) Dining Room
(2) Kitchen
(3) Living Room
(4) Bedroom
(5) TV Room
(6) Basement
Required smoke detectors
Additional alarms required for new construction
Where to locate the required smoke detectors in existing
construction. The major threat from fire in a family living unit
occurs at night when everyone is asleep. The principal threat
to persons in sleeping areas comes from fires in the remainder
of the unit. Therefore, a smoke detector is best located
between the bedroom areas and the rest of the unit. In units
with only one bedroom area on one floor, the smoke detector
should be located as shown in Figure 1-A.
In family living units with more than one bedroom area or with
more than one floor, more than one smoke detector is
required, as shown in Figure 1-B.
In addition to smoke detectors outside of the sleeping areas,
the installation of a smoke detector on each additional story of
the family living unit, including the basement, is required.
These installations are shown in Figure 1-C. The living area
smoke detector should be installed in the living room or near
the stairway to the upper level, or in both locations. The
basement smoke detector should be installed in close
proximity to the stairway leading to the floor above. Where
installed on an open-joisted ceiling, the alarm should be placed
on the bottom of the joists. The alarm should be positioned
relative to the stairway to intercept smoke coming from a fire in
the basement before the smoke enters the stairway.
Where to locate the required smoke detectors in new
construction. All of the smoke detectors specified for existing
construction are required and, in addition, a smoke detector is
required in each bedroom.
Are more smoke detectors desirable? The required number
of smoke detectors might not provide reliable early warning
protection for those areas separated by a door from the areas
protected by the required smoke detectors. For this reason, it
is recommended that the householder consider the use of
additional smoke detectors for those areas for increased
protection. The additional areas include the basement,
bedrooms, dining room, furnace room, utility room, and
hallways not protected by the required smoke detectors. The
installation of smoke detectors in kitchens, attics (finished or
unfinished), or garages is not normally recommended, as these
locations occasionally experience conditions that can result in
improper operation.
Note: Regulations pertaining to smoke detector installation
vary from state to state. For more information, contact your
local fire department or local authority having jurisdiction.
Additional considerations. In addition to NFPA 72, use the
following location guidelines to optimize performance and
reduce the chance of false alarms from the detector:
⢠Locate ceiling-mounted smoke detectors in the center of a
room or hallway at least 4 in. (10 cm) from any walls or
partitions.
⢠Locate wall-mounted smoke detectors so the top of the
alarm is 4 to 12 in. (10 to 31 cm) below the ceiling.
⢠Do not locate detectors in or near bathrooms or kitchens.
⢠Locate smoke alarms in a suitable environment with
temperature and humidity as defined in âSpecificationsâ on
page 8.
⢠Locate smoke detectors away from air conditioners,
heating registers, and any other ventilation source that
may interfere with smoke entering the alarm.
⢠Mount smoke detectors on a firm, permanent surface.
Installing the detector
All wiring must conform to the National Electric Code (NEC)
and/or local codes having jurisdiction. Use 12 to 24 AWG (16
to 22 AWG recommended) wire to install the detector.
1. If you are using the detector-base lock, remove the
detector knockout and break off the tab on the mounting
base. See Figure 2.
2. Remove the red plastic cover from the detector. The
detector is shipped with a cover for protection against
construction site dust.
(1) (2)
(3)
(4) (4)
(4)
(1) (2)
(3)
(4)(5)
(4)
(4)
(4) (4)
(3) (1)
(6)
A B
C
P/N 1036525-EN ⢠REV F 3 / 8
3. Run system wiring to the detector location and mount
electrical boxes if necessary. The detector fits standard
single-gang boxes and 3-1/2 in. and 4 in. round ceiling
boxes.
4. Line up and attach the mounting base to the electrical box,
wall, or ceiling using the screws provided. Use wall
anchors if necessary. See Figure 3.
5. Strip the system wires and connect them to the
appropriate terminals on the detector. See âWiringâ on
page 4.
6. Attach the detector to the mounting base as follows:
a. Line up the raised tab on the side of the detector with
the arrow on the mounting base. See Figure 4.
b. Insert the smoke detector into the base and turn
clockwise approximately 15 degrees. It should snap firmly
into place.
7. Apply power and test the detector. See âSmoke testingâ on
page 5.
Figure 2: Detector-base lock
Figure 3: Detector installation
Figure 4: Mounting
Removing the detector
To remove the detector from the mounting base: Grasp the
detector and turn it counterclockwise approximately 15
degrees. The detector should snap off of the mounting base.
To remove the detector from the mounting base when the
detector-base lock is used: Insert a small screwdriver into
the locking tab slot on the side of the base and press in while
simultaneously turning the detector counterclockwise 15
degrees. See Figure 5.
Figure 5: Unlocking the detector
Product specificaties
Merk: | Interlogix |
Categorie: | Rookmelder |
Model: | ESL 500N |
Kleur van het product: | Wit |
Hoogte: | 50 mm |
Gebruikershandleiding: | Ja |
Stroombron: | DC |
Type verpakking: | Doos |
Montage gereedschap: | Ja |
Ondersteuning voor plaatsing: | Horizontaal |
Connectiviteitstechnologie: | Bedraad |
Montagewijze: | Opbouwmontage |
Diameter: | 140 mm |
Ingangsspanning: | 12/24 V |
Aantal: | 1 |
Inclusief schroeven: | Ja |
Beste gebruik: | Home, Office |
Detector type: | Foto-electrische reflectie detector |
Koppelbaar: | Nee |
Vals-alarmbescherming: | Ja |
Bedrijfstemperatuur (T-T): | 0 - 37 °C |
Relatieve vochtigheid in bedrijf (V-V): | 0 - 95 procent |
Alarm decibels: | 85 dB |
Montagediameter: | 133 mm |
Insectenrooster: | Ja |
Heb je hulp nodig?
Als je hulp nodig hebt met Interlogix ESL 500N stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Rookmelder Interlogix
7 April 2023
22 Januari 2023
Handleiding Rookmelder
- Rookmelder Bosch
- Rookmelder IKEA
- Rookmelder Grundig
- Rookmelder Gigaset
- Rookmelder Honeywell
- Rookmelder Siemens
- Rookmelder Abus
- Rookmelder Ajax
- Rookmelder Alecto
- Rookmelder AngelEye
- Rookmelder Bavaria
- Rookmelder Blaupunkt
- Rookmelder Brennenstuhl
- Rookmelder BRK
- Rookmelder BRK DICON
- Rookmelder Denver
- Rookmelder Elgato
- Rookmelder Elro
- Rookmelder Eminent
- Rookmelder EQ-3
- Rookmelder ESYLUX
- Rookmelder Ferguson
- Rookmelder FireAngel
- Rookmelder First Alert
- Rookmelder FirstAlert
- Rookmelder Flamingo
- Rookmelder Gira
- Rookmelder Gloria
- Rookmelder Hager
- Rookmelder Hama
- Rookmelder HQ
- Rookmelder KlikaanKlikuit
- Rookmelder Kogan
- Rookmelder Konig
- Rookmelder Marmitek
- Rookmelder Marquant
- Rookmelder Mercury
- Rookmelder Nedis
- Rookmelder Nest
- Rookmelder Netatmo
- Rookmelder Pyle
- Rookmelder Satel
- Rookmelder Smartwares
- Rookmelder Somfy
- Rookmelder Stabo
- Rookmelder Sygonix
- Rookmelder TFA
- Rookmelder Trust
- Rookmelder Vivanco
- Rookmelder Yale
- Rookmelder Jung
- Rookmelder Olympia
- Rookmelder Clas Ohlson
- Rookmelder Schwaiger
- Rookmelder Steren
- Rookmelder EMOS
- Rookmelder Malmbergs
- Rookmelder DSC
- Rookmelder M-e
- Rookmelder REV
- Rookmelder Chacon
- Rookmelder Nexa
- Rookmelder Swann
- Rookmelder Deltronic
- Rookmelder Ei Electronics
- Rookmelder Fibaro
- Rookmelder FireHawk
- Rookmelder FireX
- Rookmelder Fito
- Rookmelder GEV
- Rookmelder Insafe
- Rookmelder Kidde
- Rookmelder No-Flame
- Rookmelder Pyrexx
- Rookmelder System Sensor
- Rookmelder Dahua Technology
- Rookmelder Busch-Jaeger
- Rookmelder EVE
- Rookmelder Popp
- Rookmelder EQ3
- Rookmelder Homematic IP
- Rookmelder Calex
- Rookmelder Lanberg
- Rookmelder Mobeye
- Rookmelder X-Sense
- Rookmelder Chuango
- Rookmelder ORNO
- Rookmelder ETiger
- Rookmelder TEF
- Rookmelder Jalo Helsinki
- Rookmelder Heatit
- Rookmelder Fito Profi-line
- Rookmelder H-Tronic
- Rookmelder Inovonics
- Rookmelder Pristine
- Rookmelder Cavius
- Rookmelder Jemay
- Rookmelder Pentatech
- Rookmelder Mircom
- Rookmelder WisuAlarm
- Rookmelder Cordes
- Rookmelder SAVS
- Rookmelder STI
- Rookmelder Gewiss
- Rookmelder Egardia
- Rookmelder Frient
- Rookmelder Qolsys
Nieuwste handleidingen voor Rookmelder
2 December 2024
30 November 2024
30 November 2024
30 November 2024
24 November 2024
18 November 2024
18 November 2024
18 November 2024
18 November 2024
16 November 2024