Aritech AD044 Handleiding
Aritech
Beveiliging
AD044
Lees hieronder de đź“– handleiding in het Nederlandse voor Aritech AD044 (10 pagina's) in de categorie Beveiliging. Deze handleiding was nuttig voor 78 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/10
EN
FR
NL
IT
© 2005 GE Security B.V. All Rights Reserved 1051425 REV B
www.gesecurity.net 02/2005
Lid
Circuit board
Bracket
Base
Wire access
opening
Address Setting
0 00000000
1 10000000
2 01000000
3 11000000
4 00100000
5 10100000
6 01100000
7 11100000
8 00010000
9 10010000
10 01010000
Address Setting
11 11010000
12 00110000
13 10110000
14 01110000
15 11110000
16 00001000
17 10001000
18 01001000
19 11001000
20 00101000
21 10101000
Address Setting
22 01101000
23 11101000
24 00011000
25 10011000
26 01011000
27 11011000
28 00111000
29 10111000
30 01111000
31 11111000
Address 0
Address 2
Address 31
AD044
Installation Manual
o
n
p
2
EN
Installation Manual
DESCRIPTION
The AD044 is a universal external interface between
conventional detector devices and the Advisor MASTER
ATS1290 Addressable Devices DGP. It supports up to four
inputs and four supervised outputs.
You can connect four generic detectors with a dual zone
configuration (2-resistor EOL connection, 2 x 47kohm).
The outputs can be used, for example, to enable / disable
the alarm LED on the detector (depending on the detector’s
other functionalities, which can be programmed or activating
devices).
Output supervision is useful for monitoring outputs, such as
fire sounders, etc. (UL requirement).
DEVICE CATEGORY
The AD044 belongs to device category I/O, type 1, and will
be automatically recognised after learning the device into
the ATS1290 DGP.
MOUNTING THE UNIT
1. Pull the wiring through the wire access opening in the
unit base. See Figure n. Exploded view: 1. Lid; 2.
Circuit board; 3. Bracket; 4. Base; 5. Wire access
opening.
CAUTION! You must be free of static
electricity before handling sensor circuit
boards. Touch a grounded, bare metal
surface before touching circuit boards
or wear a grounding strap.
2. Mount the base using the appropriate mounting holes.
3. Mount the metal bracket to the base.
4. Mount the circuit board to the metal bracket.
CONNECTING THE UNIT
Connect the AD044 to the detector and Bus system. See
Figure q.
1. Connect the wires to the appropriate screw terminals
on the circuit board and tighten the screws. See
Figure o: 1. Bus In; 2. Bus Out; 3. Monitor*; 4. Inputs;
5. Outputs**, 6. Power supply
*Note 1: An open contact on the AC monitor input
causes an AC fault to be transmitted to the control
panel. An open contact on the battery monitor input
causes a battery fault to be transmitted to the control
panel. When both contacts are closed or hard wired
to close, these inputs will force the AC and battery
monitor to normal state.
**Note 2: Outputs connect the supply voltage (12 or
24 VDC) across the load when ON.
2. Set the address DIP-switches. See Figure p.
Note 3: Devices are shipped with the DIP switches set
to 255. This is an invalid address. The device will not
communicate with the control panel until a valid
address has been set. Refer to the ATS1290 manual
to determine the correct address setting for each unit.
3. Attach the unit lid to the base. See Figure n.
4. Test the unit when the Bus system is completely
installed and the control panel is powered.
ADDRESS SETTING, ZONE NUMBERS AND OUTPUT NUMBERS
Set the AD044 to its unique address on the Point ID bus.
For details, see figure p.
The AD044 normally occupies four consecutive addresses,
where the DIP switch represents the main address. Where
output-supervision is used, the AD044 occupies up to eight
consecutive addresses.
THE ATS INPUTS
Input 1 is linked to main address.
Input 2 is linked to main address + 1.
Input 3 is linked to main address + 2.
Input 4 is linked to main address + 3.
THE ATS OUTPUTS
Output 1 is linked to main address.
Output 2 is linked to main address + 1.
Output 3 is linked to main address + 2.
Output 4 is linked to main address + 3.
OUTPUT SUPERVISION
The AD044 can support output supervision on all four
outputs. Supervision of Output 1 is linked to Input 5 and
onwards.
In the default setting, all output are supervised. If an output
(e.g. Output 1) is open, it misses the EOL resistor (47K), the
linked input (input 5) is in Alarm. The relay output will not
follow the linked output of the control panel.
Note 4: The EOL resistor must be available before the
outputs of the AD044 work properly.
The supervision for Outputs 1 to 4 are linked to the
consecutive input addresses:
Supervision Output 1 is linked to Input 5 with main
address+4.
Supervision Output 2 is linked to Input 6 with main
address+5.
Supervision Output 3 is linked to Input 7 with main
address+6.
Supervision Output 4 is linked to Input 8 with main
address+7.
1. It is possible to map another PID device within the
AD044 range. For example, when the AD044 is set
to Address 0 and the AD011 is set to Address 2, the
AD044 occupies Address 0 (I/O 1), 1 (I/O 2) and 3 (I/O
4), and AD011 occupies Address 2. I/O 3 of the AD044
is not available.
3
2. If Inputs 2,3 or 4 or even 5, 6, 7 and 8 are used, they
must be within the ATS1290 I/O range. If they are out
of range, they are not available.
3. If some AD044 inputs are not used, the linked zone
input in the ATS control panel must be programmed
as disabled (default).
4. If some AD044 outputs are not used, the linked output
in the ATS control panel must not be programmed
(default).
Refer also to the ATS1290 manual for the direct link to the
zone number (control panel).
MEMORY LOCATION MAP
Every PID device has its own characteristics concerning
related I/O lines or certain functionality of the device.
A total of 16 memory locations are reserved to configure
the PID devices. Only the first nine are normally user
configurable. This depends on the functionality of the
particular device.
For the AD044 external PID interface only memory locations
3 and 5 matter.
On Memory Location 3, the zone type can be configured for
each input to Single EOL, Double EOL (default) or the zone
can be switched off (the status will always be “Normal”).
On Memory Location 5, the output supervision can be
enabled (default) or disabled for each output.
MEMORY LOCATION MAP FOR AD044
Location Function Decimal values Binary values
3 Zone types
For example:
0 = All zones are Off
85 = All zones are Single EOL
170 = All zones are Double EOL (default)
Zone 4 Zone 3 Zone 2 Zone 1
Bit 7-6 Bit 5-4 Bit 3-2 Bit 1-0
00 = Zone is Off
01 = Single EOL
10 = Double EOL (default)
11 = Undefined
5 Supervision
outputs
For Example:
0 = All Output Supervisions disabled
15 = All Output Supervisions enabled (default)
Output 4 Output 3 Output 2 Output 1
Bit 3 Bit 2 Bit 1 Bit 0
0 = Disabled
1 = Enabled (default)
ZONE TYPE
Input loop
resistance Status ATS control panel
Double EOL
Status ATS control panel
Single EOL
<20 ohm Short Short
47K Normal Normal
94K Alarm Open
> 1Meg ohm Open Open
TECHNICAL SPECIFICATIONS
Bus protocol.........................................GE Interlogix Point ID
Bus voltage........................................................ 12 V or 24 V
External power supply ...................12/24 V (see Note below)
Current consumption from bus ...................................290 µA
Unit load for DGP ................................................................ 1
Address range .......................................................... 0 to 255
Max Current Outputs ......................................500 mA (each)
Single EOL resistor Inputs ................................ 47 kΩ +/- 5%
Double EOL resistors Inputs........................2 x 47 kΩ +/- 5%
EOL resistors Outputs ................................................. 47 KΩ
Category........................................................................... I/O
Device type........................................................................ T1
Note: The auxiliary power output of closest panel or DGP can
also be used.
Product specificaties
Merk: | Aritech |
Categorie: | Beveiliging |
Model: | AD044 |
Heb je hulp nodig?
Als je hulp nodig hebt met Aritech AD044 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Beveiliging Aritech
23 December 2022
23 December 2022
23 December 2022
23 December 2022
23 December 2022
23 December 2022
18 September 2022
18 September 2022
19 September 2022
18 September 2022
Handleiding Beveiliging
- Beveiliging Bosch
- Beveiliging Panasonic
- Beveiliging Bticino
- Beveiliging Fysic
- Beveiliging Grundig
- Beveiliging Honeywell
- Beveiliging Medion
- Beveiliging Siemens
- Beveiliging Abus
- Beveiliging AceSee
- Beveiliging Airbolt
- Beveiliging Ajax
- Beveiliging Alecto
- Beveiliging Alhua - Dahua
- Beveiliging Alphatronics
- Beveiliging AngelEye
- Beveiliging Audiovox
- Beveiliging AVTech - Velleman
- Beveiliging Axa
- Beveiliging Axis
- Beveiliging Basetech
- Beveiliging Batavia
- Beveiliging Bavaria
- Beveiliging Bellman
- Beveiliging Bitron Video
- Beveiliging Blaupunkt
- Beveiliging BML
- Beveiliging Bolyguard
- Beveiliging Brennenstuhl
- Beveiliging BRK
- Beveiliging BRK DICON
- Beveiliging Dahua
- Beveiliging Dedicated Micros
- Beveiliging Dericam
- Beveiliging Devolo
- Beveiliging Directed Electronics
- Beveiliging Dnt
- Beveiliging Doro
- Beveiliging Dymond
- Beveiliging Easy Home
- Beveiliging Easymaxx
- Beveiliging Eden
- Beveiliging Edimax
- Beveiliging Ednet
- Beveiliging Electronics Line
- Beveiliging Elkron
- Beveiliging Elro
- Beveiliging Elro-Flamingo
- Beveiliging Eminent
- Beveiliging Entrya
- Beveiliging Epine
- Beveiliging Eufy
- Beveiliging Ezviz
- Beveiliging FBII
- Beveiliging Fenton
- Beveiliging First Alert
- Beveiliging Flamingo FA15RF
- Beveiliging FlinQ
- Beveiliging Foscam
- Beveiliging Fracarro
- Beveiliging Friedland
- Beveiliging Galaxy
- Beveiliging GE Security
- Beveiliging Geemarc
- Beveiliging Gira
- Beveiliging Goliath
- Beveiliging Golmar
- Beveiliging Goobay
- Beveiliging Grandstream
- Beveiliging Grothe
- Beveiliging Guardall
- Beveiliging Hagenuk
- Beveiliging Heidemann
- Beveiliging Hikvision
- Beveiliging Home Protector
- Beveiliging Home8
- Beveiliging HomeWizard
- Beveiliging HUMANTECHNIK
- Beveiliging I-onik
- Beveiliging I-Tel
- Beveiliging Iget
- Beveiliging Iiquu
- Beveiliging Indexa
- Beveiliging Inner Range
- Beveiliging Interlogix
- Beveiliging Kocom
- Beveiliging Kompernass
- Beveiliging Kopp
- Beveiliging Ksenia
- Beveiliging Lamax
- Beveiliging LevelOne
- Beveiliging Logicom
- Beveiliging Maginon
- Beveiliging Marmitek
- Beveiliging Marquant
- Beveiliging ME
- Beveiliging Microtech
- Beveiliging Mikros
- Beveiliging Monacor
- Beveiliging Mr Safe
- Beveiliging Muller
- Beveiliging Myfox
- Beveiliging Nedis
- Beveiliging Nemef
- Beveiliging Nest
- Beveiliging Netatmo
- Beveiliging NetBotz
- Beveiliging Netgear
- Beveiliging NetworX
- Beveiliging Niko
- Beveiliging Nor-tec
- Beveiliging Notifier
- Beveiliging Paradox
- Beveiliging Perel
- Beveiliging PIR Alarm
- Beveiliging Plustek
- Beveiliging Powerfix
- Beveiliging Powermax
- Beveiliging Prestigio
- Beveiliging Profile
- Beveiliging PROmax
- Beveiliging Protector
- Beveiliging Provision ISR
- Beveiliging QuattSecure
- Beveiliging Ranex
- Beveiliging RISCO Group
- Beveiliging Satel
- Beveiliging SecuFirst
- Beveiliging Secure Pro
- Beveiliging Securitas
- Beveiliging Selvag
- Beveiliging Skytronic
- Beveiliging Smanos
- Beveiliging Smartalarm
- Beveiliging SmartHome
- Beveiliging Smartwares
- Beveiliging Somfy
- Beveiliging Sonic Alert
- Beveiliging Steinel
- Beveiliging Stobo
- Beveiliging Storage Options
- Beveiliging Storex
- Beveiliging Switel
- Beveiliging Sygonix
- Beveiliging Technaxx
- Beveiliging Tegui
- Beveiliging Tevion
- Beveiliging Theben
- Beveiliging Topcraft
- Beveiliging Trebs
- Beveiliging Trendnet
- Beveiliging Trust
- Beveiliging Unitec
- Beveiliging Unitron
- Beveiliging Urmet
- Beveiliging V-Tac
- Beveiliging Velbus
- Beveiliging Velleman
- Beveiliging Visonic
- Beveiliging Voxx
- Beveiliging Waeco
- Beveiliging Wanscam
- Beveiliging Woonveilig
- Beveiliging Xavax
- Beveiliging Xena
- Beveiliging Y-cam
- Beveiliging Yale
- Beveiliging Zmodo
- Beveiliging Jablotron
- Beveiliging Jacob Jensen
- Beveiliging Jung
- Beveiliging Jupiter Pro
- Beveiliging Juwel
- Beveiliging One2track
- Beveiliging Oplink
- Beveiliging Optex
- Beveiliging Orbis
- Beveiliging Overmax
- Beveiliging Fito
- Beveiliging One Concept
Nieuwste handleidingen voor Beveiliging
6 Maart 2024
4 Februari 2024
16 Oktober 2023
16 Oktober 2023
16 Oktober 2023
16 Oktober 2023
16 Oktober 2023
16 Oktober 2023
16 Oktober 2023
16 Oktober 2023