Schneider WDE002963 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Schneider WDE002963 (75 pagina's) in de categorie Thermostaat. Deze handleiding was nuttig voor 54 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/75
KNX room temperature controller
Application 705C/0.1
© 2011 Schneider Electric
Application: Continuous-action controller with pushbutton interface, 4-fold 705C
Executable from mask version: 7.1
Number of addresses (max): 120 dynamic table handling Yes No
Number of assignments (max): 120 maximum length of table 120
Communication objects: 59
Pushbutton interface functions:
Function: Binary input / switching (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name DPT-ID Type Flag
0-3 Switching object X.1 PBI input X 1.001 1 bit C, T
4-7 Switching object X.2 PBI input X 1.001 1 bit C, T
8-11 Disable switching object X.1 PBI input X 1.001 1 bit C, W
12-15 Disable switching object X.2 PBI input X 1.001 1 bit C, W
Function: Binary input / dimming (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Switching PBI input X 1.001 1 bit C, T
4-7 dimming PBI input X 3.007 4 bit C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / blind/shutter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Short-time operation PBI input X 1.007 1 bit C, T
4-7 Long-time operation PBI input X 1.008 1 bit C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / dimming value transmitter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Value PBI input X 5.001 1 byte C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / light-scene extension (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Light-scene extension PBI input X 18.001 1 byte C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / brightness value transmitter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Brightness value PBI input X 9.004 2 bytes C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
Function: Binary input / temperature value transmitter (for all 4 binary inputs (X = 1 to 4))
disabling function enabled
Object Function Name: DPT-ID Type Flag
0-3 Temperature value PBI input X 9.001 2 bytes C, T
8-11 Disabling PBI input X 1.001 1 bit C, W
KNX room temperature controller
Application 705C/0.1
© 2011 Schneider Electric
Function: output / basic stage ... or additional stage ... (for channels 1 and 2 (Y = 1 to 2))
Object Function Name: DPT-ID Type Flag
0-1 Switching PBI output Y 1.001 1 bit C, T
Function: output / output external switching object ... (for channels 1 and 2 (Y = 1 to 2))
Object Function Name: DPT-ID Type Flag
0-1 Switching PBI output Y 1.001 1 bit C, T
4-5 external switching object PBI output Y 1.001 1 bit C, W
Function: external temperature sensor (for channel 4)
Object Function Name: DPT-ID Type Flag
If channel 4 is used as an external temperature sensor for the room temperature controller, its measuring
value is internally written into communication object 24 "External temperature sensor" of the controller.
To avoid malfunctions, it is not permitted to write other values from outside into this object.
Function: temperature limiter (for channel 4)
Object Function Name DPT-ID Type Flag
3 floor temperature PBI input 4 9.001 2 bytes C, T
KNX room temperature controller
Application 705C/0.1
© 2011 Schneider Electric
Room temperature controller functions:
Function: Actual temperature
Object Function Name DPT-ID Type Flag
23 Actual temperature RTC output 9.001 2 bytes C, R, T
Function: additional temperature sensor
Object Function Name DPT-ID Type Flag
24 External temperature sensor RTC input 9.001 2 bytes C, W, T
Function: basic setpoint preset
Object Function Name DPT-ID Type Flag
26 Basic setpoint RTC input 9.001 2 bytes C, W
Function: Operating mode switch-over
With operating mode switch-over "via value (1 byte)":
Object Function Name DPT-ID Type Flag
28 Operating mode switch-over RTC input 20.102 1 byte C, W(, T) 6
32 Operating mode forcing object RTC input 20.102 1 byte C, W
With operating mode switch-over "via switching (4 x 1 bit)":
Object Function Name DPT-ID Type Flag
28 Comfort mode RTC input 1.001 1 bit C, W(, T)6
29 Standby mode RTC input 1.001 1 bit C, W(, T)6
30 Night mode RTC input 1.001 1 bit C, W(, T)6
31 Frost/ heat protection RTC input 1.001 1 bit C, W(, T)6
Presence object and window status:
Object Function Name DPT-ID Type Flag
33 Presence object RTC input / output 1.001 1 bit C, W, T
34 Window status RTC input 1.019 1 bit C, W
Function: Control option switch-over
Object Function Name DPT-ID Type Flag
35 Heating / cooling switch-over 7 RTC input 1.001 1 bit C, W, (T)
6: Optionally, the "T" ags can be set for the operating mode switch-over. Once the flags are set, the object
values which have changed according to the newly set operating mode will be actively transmitted to the bus.
7: This object is only visible in mixed operation "heating and cooling" or "basic / additional heating / cooling". The
"T" ag is set for automatic heating / cooling switch-over.


Product specificaties

Merk: Schneider
Categorie: Thermostaat
Model: WDE002963

Heb je hulp nodig?

Als je hulp nodig hebt met Schneider WDE002963 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Thermostaat Schneider

Handleiding Thermostaat

Nieuwste handleidingen voor Thermostaat