SpaceLogic KNX
Switch actuator REG-K/2x230/16 with
manual mode
Operating instructions
Art. no. MTN647393
For your safety
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR
ARC FLASH
Safe electrical installation must be carried out only by
skilled professionals. Skilled professionals must prove
profound knowledge in the following areas:
• Connecting to installation networks
• Connecting several electrical devices
• Laying electric cables
• Connecting and establishing KNX networks
• Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in
death or serious injury.
RISK OF FATAL INJURY FROM ELECTRIC SHOCK
The output may carry electrical current even when the
load is switched off.
• When working on the device: Always disconnect the
device from the supply by means of the fuse in the in-
coming circuit.
• Even if the manual switch is in the „OFF“ position, a
KNX telegram can switch the connections to being
live at any time. Before working on the device, always
diconnect the fuse in the incoming circuit from the
supply.
Failure to follow these instructions will result in
death or serious injury.
en
L 2L 1
The switch actuator REG-K/2x230/16 with manual mode
(referred to below as the actuator) can switch two loads
via separate, floating make contacts.
You can also manually switch the connected loads with
manual switches on the actuator without bus voltage.
The actuator has a bus coupler. It is installed on a DIN rail
TH 35 according to EN 60715, with the bus connection
made via a bus connecting terminal. It is supplied with
power from the bus voltage. A data rail is not required.
ABus connection terminal, max. 4 core pairs
BProgramming LED (red)
CProgramming button
DCable cover
EOperating LED „RUN“ (green)
FManual switch
GScrew terminals
1Set the actuator onto the DIN rail.
The device may be damaged!
• Always operate the product in compliance with the
specified technical data.
• Only install devices with at least basic insulation next
to the device.
Failure to follow these instruction can result in
equipment damage.
Getting to know the actuator
Connections, displays and operating
elements
Mounting the actuator
L L 2L L 1
KNX
1 2
D
C
AB
E
F
G
1
2
2Connect KNX.
¼WARNING
Risk of death from electric shock. The device
can become damaged.
Safety clearance must be guaranteed in accord-
ance with IEC 60664--1. There must be at least 4
mm between the individual cores of the 230 V
supply cable and the KNX line A.
3Connect the bus voltage.
4Wait at least 30 seconds.
5Switch the relays of the channels on and off manu-
ally once with the manual switches.
6Connect the load.
The cables to the loads as well as the system voltages
(L1, L2 or L3) are connected via screw terminals for max.
16 A. Every two L connections are bridged internally.
7Connect the mains voltage.
Now you can check the functionality of the actuator and
the connected loads without having to load the applica-
tion from the ETS (See the section "Operating the actua-
tor").
RISK OF FATAL INJURY FROM ELECTRIC SHOCK
Voltage may be present at the outputs when the mains
voltage is connected to the system.
If subjected to strong vibrations during transportation,
the switch contacts might change to the enabled state.
After connecting the bus voltage, set the relays of the
channels to the position desired simply by switching
„On/Off“ or by changing the manual switch to „OFF“.
Failure to follow these instructions will result in
death or serious injury.
The device may be damaged!
• Protect the switch contacts with a series-connected
16 A circuit breaker.
Failure to follow these instruction can result in
equipment damage.
1 2
34
5 mm
230 V
4 mm
A
1
2
KNX
16 A
L1
16 A 16 A
L2 L3 N
V6473-561-02 11/21
1Press the programming button.
The programming-LED lights up.
2Load the physical address and application into the
device from the ETS.
The programming LED goes out.
The operation LED lights up: The application was loaded
successfully, the device is ready for operation.
Normally, you control connected devices using push-
buttons or by remote control. However, you can manually
switch each of the actuator‘s channels on and off directly
at the manual switches.
Putting the actuator into operation
Operating the actuator
Technical data
External auxiliary volt-
age: None
Power supply from
bus: DC 24 V / max. 10 mA
Insulation voltage: AC 4 kV between bus / mains
voltage
Switch contact: 2 x make contact, floating
Nominal voltage: AC 100–240 V ±10%
Operation voltage: min. AC 90 V – max. AC 265 V
Mains frequency: 50–60 Hz ±10%
Nominal current: 16 A, inductive load cosφ=0,6
Connected load
Incandescent
lamps: 1600 W at AC 100 V
3600 W at AC 230 V
3840 W at AC 240 V
with 10,000 switching cycles
Halogen lamps: 1086 W at AC 100 V
2500 W at AC 230 V
2608 W at AC 240 V
with 10,000 switching cycles
Fluorescent lamps: 1086 VA at AC 100 V
2500 VA at AC 230 V
2608 VA at AC 240 V
parallel compensated
with 5,000 switching cycles
Capacitive load: 16 A, 200 µF at AC 100 V
16 A, 200 µF at AC 230 V
16 A, 200 µF at AC 240 V
with 5,000 switching cycles
Fuse: The switch contact must be pro-
tected by 16 A series-connected
circuit breaker.
Switching frequency: max. 10 per minute at nominal
load
Ambient temperature:
Operation: -5 °C to +45 °C
Max. humidity: 93 %, no moisture condensation
Environment: can be used at up to
2000 m above sea level (MSL)
Operating elements: 1 programming button
2 manual switches
Display elements: 1 red LED: programming check
1 green LED: ready for operation
„RUN“
Connections
Bus: via two 1 mm pins for bus con-
necting terminal
Outer conductor: 2x 3-gang screw terminal for
each max. 2.5 mm2
EC directives: Low voltage directive 2006/95/
EC
EMC-directive 2004/108/EC
Device width: 2,5 modules = approx. 45 mm
Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Cus-
tomer Care Centre in your country.
se.com/contact
Schneider Electric -Contact
Schneider Electric Limited
Telford, TF3 3 BL, UK
UK Representative
Stafford Park 5


Product specificaties

Merk: Schneider
Categorie: Niet gecategoriseerd
Model: MTN647393

Heb je hulp nodig?

Als je hulp nodig hebt met Schneider MTN647393 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Schneider

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd