The control unit 0-10 V REG-K/1-gang with manual
mode (refered to below as control unit) dims and
switches fluorescent lamps using electronic ballasts with
a 0-10 V/1-10 V interface and LV halogen lamps using
transformers with a 0-10 V/1-10 V interface.
|The control voltage range can be set with the ETS
via a parameter.
You can also manually switch the connected loads with
the manual switch on the control unit without bus volt-
age.
The control unit has a bus coupler. It is installed on a DIN
rail TH 35 according to EN 60715, with the bus connec-
tion made via a bus connecting terminal. A data rail is not
required.
SpaceLogic KNX Control unit 0-10 V
REG-K/1-gang with manual mode
Operating instructions
Art. no. MTN647091
For your safety
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR
ARC FLASH
Safe electrical installation must be carried out only by
skilled professionals. Skilled professionals must prove
profound knowledge in the following areas:
• Connecting to installation networks
• Connecting several electrical devices
• Laying electric cables
• Connecting and establishing KNX networks
• Safety standards, local wiring rules and regulations
Failure to follow these instructions will result in
death or serious injury.
The device may be damaged!
• Always operate the product in compliance with the
specified technical data.
• Only install devices with at least basic insulation next
to the device.
Failure to follow these instruction can result in
equipment damage.
Getting to know the control unit
en
A Bus connecting terminal
B Programming-LED (red)
C Programmier button
D Cable cover
E Operating-LED „RUN“ (green)
F Manual switch
G Channel terminals for load voltage
HOutputs 1–10 V
1 Set the control unit onto the DIN rail.
2 Connect KNX.
¼WARNING
Risk of death from electric shock. The device
can become damaged.
Safety clearance must be guaranteed in accord-
ance with IEC 60664--1. There must be at least 4
mm between the individual cores of the 230 V
supply cable and the KNX line A.
¼WARNING
Risk of death from electric shock. The device
could become damaged.
Disconnect the mains voltage before connecting
the device to the load.
Terminals may not be inserted under load.
Connections, displays and operating
elements
Mounting the control unit
C
AB
E
F
G
H
D
1
2
1 2
34
5 mm
230 V
4 mm
A
¼DANGER
Risk of death from electric shock.
Voltage may be present at the outputs when the
mains voltage is connected to the system.
If subjected to strong vibrations during transpor-
tation, the switch contacts might change to the
enabled state.
After connecting the bus voltage, set the relays of
the channels to the position desired simply by
switching „On/Off“ or by changing the manual
switch to „OFF“.
3 Connect the bus voltage.
4 Connect the load.
5 Connect the load voltage.
1 Press the programming button.
The programming-LED lights up.
2 Load the physical address and application into the
device from the ETS.
The programming LED goes out.
The operation LED lights up: The application was loaded
successfully, the device is ready for operation.
A Control unit
B Electronic ballast with 0-10 V / 1-10 V inter-
face
C Fluorescent lamp
D Eletronic transformer with 0-10 V / 1-10 V con-
trol input
E LV halogen lamps
F to other devices with 0-10 V / 1-10 V interface
Putting the control unit into operation
KNX
+ -
NL1
L
-
+
0-10V
0-10V
12V AC
A
-
+
L
N
-
+
L
N
F
D
B
0-10V
C
E
16 A
V6470-561-02 11/21
Technical data
Power supply from
bus: DC 24 V / approx. 17.5 mA
Insulation voltages: AC 4 kV bus / mains voltage and
bus / 0–10 V
AC 4 kV 0–10 V / mains voltage
Switch contact: Make contact, floating
Nominal voltage: AC 100–240 V ±10%
Operation voltage: min. AC 90 V – max. AC 265 V
Mains frequency: 50–60 Hz ±10%
Nominal current: 16 A, inductive load cosφ = 0,6
Connected load
Incandescent
lamps: 1600 W at AC 100 V
3600 W at AC 230 V
3840 W at AC 240 V
Halogen lamps: 1086 W at AC 100 V
2500 W at AC 230 V
2608 W at AC 240 V
NV halogen lamps: 869 VA at AC 100 V
2000 VA at AC 230 V
2086 VA at AC 240 V
via electronic transformer
Fluorescent lamps: 1600 VA at AC 100 V
3600 VA at AC 230 V
3840 VA at AC 240 V
uncompensated
1086 VA at AC 100 V
2500 VA at AC 230 V
2608 VA at AC 240 V
parallel compensated
Capacitive load: 1600 W, 200 µF at AC 100 V
3600 W, 200 µF at AC 230 V
3840 W, 200 µF at AC 240 V
Fuse: The switch contact must be pro-
tected by 16 A seies-connected
circuit breaker.
Service life: > 50.000 switching cycles at
nominal load
0–10 V / 1–10 V Inter-
face: 0–10 V for dimming electronic
ballasts
Loading capacity: max. 100 mA (max. 50 electronic
ballasts, depending on EB)
Min. control voltage: 0 V
Ambient temperature:
Operation: -5 °C to +45 °C
Max. humidity: 93 %, no moisture condensation
Environment: can be used at up to
2000 m above sea level (MSL)
Operating elements: 1 programming button
1 manual switch
Display elements: 1 red LED: programming check
1 green LED: ready for operation
„RUN“
Connections
Bus: via two 1 mm pins for bus con-
necting terminal
Live conductor and
switch output: 3-gang screw terminal for max.
2.5 mm2
1–10 V-output: 2-gang pluggable screw terminal
for max. 2,5 mm2
EC directives: Low voltage directive 2006/95/
EC
EMC-directive 2004/108/EC
Device width: 2.5 modules = approx. 45 mm
Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Cus-
tomer Care Centre in your country.
se.com/contact
Schneider Electric -Contact
Schneider Electric Limited
Telford, TF3 3 BL, UK
UK Representative
Stafford Park 5


Product specificaties

Merk: Schneider
Categorie: Niet gecategoriseerd
Model: MTN647091

Heb je hulp nodig?

Als je hulp nodig hebt met Schneider MTN647091 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Schneider

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd

Festo

Festo VPPI Handleiding

21 November 2024
Festo

Festo SFAB Handleiding

21 November 2024
Festo

Festo SFAH Handleiding

21 November 2024
Festo

Festo DRRD-12 Handleiding

21 November 2024
Festo

Festo SDE3 Handleiding

21 November 2024
Festo

Festo SFTE Handleiding

21 November 2024
Festo

Festo CRVZS-5 Handleiding

21 November 2024