Lowell strives to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without prior notication.
©2023 Lowell Manufacturing Co., 100 Integram Dr., Pacic MO 63069, USA / tel. 800.325.9660 / tel. 636-257-3400 / www.lowellmfg.com
Spec 1229
Model RPC-30-SHW | Rev. 1-11-2023 | pg. 1/2
REMOTE POWER CONTROLS can be combined with a variety of switches or sequencers for an intrinsically
safe, low voltage method of controlling AC power to equipment at remote locations. Controlling power
distribution without directly accessing equipment minimizes the potential for unauthorized access, while
simplifying activation and deactivation of equipment.
Note: RPCs require an external trigger for activation (order separately).
Ideal for Lowell switches featuring main-
tained closure (order separately):
RPSB-P Black wall plate w/rocker switch
RPSW-P White wall plate w/rocker switch
RPSW-KP White wall plate w/key switch
RPSB-R Rack panel w/rocker switch
RPSB-KR Rack panel w/key switch
Model No.
RPC-30-SHW
Remote Power Control
actives remote equipment external trigger required
FEATURES
CHASSIS: Steel chassis (8.00"L x 3.25"W x
2.75"H) with black finish and mounting holes.
POWER:
Power Rating: 125VAC 60Hz 30A
Outlet: NEMA L5-30R (includes mating NEMA
L5-30P plug)
: 1/2" non-metallic exible conduit (6 ft.) Hardwired
SURGE PROTECTION:
Maximum Surge Current: 20,000A
VPR (UL 1449-3): 400V
Response Time: 1 nanosecond
EMI/RFI Noise Reduction: 20dB@100kHz
Protection Mode: Line to Neutral
Ground Contamination: None
ACTIVATION: The RPC must be connected to an
external control for activation and deactivation
(choose one):
Dry Contact Closure: Connect to SPST switch,
power sequencer, or independent control sys-
tem with dry contact closure.
: Contact Coil Rating
- Voltage: 24VDC
- Current: 37.5mA
Voltage Trigger (5-24V AC or DC 5mA):
DSP connection.
ORIGIN: Made in the U.S.A. with global components
THIRD PARTY APPROVAL: ETL Listed to
UL60065 (U.S. and Canada)
INSTALLATION: The RPC is typically installed
near the equipment to be controlled. Low voltage
cable is run from its terminal strip to a control
switch (or other control method).
Systems can be configured with multiple RPCs
controlled by a single "Maintained Closure"
switch or voltage trigger source.
Systems can also be congured with a single
RPC controlled by multiple "Momentary Closure"
switches and Lowell's MSM2 module (which
converts momentary closure to maintained).
COMPATIBLE DEVICES: (order separately)
SPST Switch (RPS Series): Low voltage wall-
mount or rack-mount switch:
Switch with maintained closure con-
nects directly to RPC.
Switch with momentary closure requires
Lowell conversion module MSM2
placed between the switch and RPC.
Power Sequencer (SEQ Series): A low volt-
age sequencer can be used with the RPC
for time-delayed activation and deactivation
of connected equipment. Lowell standalone
sequencers will require a switch for activation,
while Lowell rack-mount sequencers include a
switch. See product spec sheets for information.
Certied
US Steel
Made In USA
with Global
Components
A&E SPECIFICATIONS:
The device for remotely controlling AC power shall be Lowell model RPC-30-SHW, which shall feature a
8.00"L x 3.25"W x 2.75"H steel chassis with black powder epoxy finish, 125VAC 60Hz 30A power rating,
NEMA L5-30R outlet, L5-30P plug, 6 ft. non-metallic flexible conduit, and basic surge protection up to
20,000A. The unit shall require an external trigger for activation (not included).
INTERNAL USE ONLY: PN 24327
Lowell strives to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without prior notication.
©2023 Lowell Manufacturing Co., 100 Integram Dr., Pacic MO 63069, USA / tel. 800.325.9660 / tel. 636-257-3400 / www.lowellmfg.com
Spec 1229
Model RPC-30-SHW | Rev. 1-11-2023 | pg. 2/2
Norm
Test
Act ivated
Power
Input 5v-24v
AC or DC
+24VDC Out
Common
Switch
GG
Surge Prote ction A ct ive
When Lit (-S models only)
R
GREEN LED (surge protection)
ON = protection active
OFF = protection compromised Connect
equipment
to be controlled
by RPC
1/2” non-metallic
exible conduit (6 ft.)
Snap-in
connector
RED LED (AC power indicator)
ON = power applied to unit
OFF = no power to unit
TEST SWITCH
TEST = AC power applied to outlets (bypassing external controls)
NORM = external control connections enabled
GREEN LED (outlet power indicator)
ON = power applied to outlets
OFF = no power to outlets
RPC DIAGRAM:
10-gauge wire
(THHN)
Connect to
appropriate
125VAC
power source
Line (black)
Neutral (white)
Ground (green)
( + )
( – )
No Conn.
No Conn.
Voltage
Input
RPC TYPICAL CONTROL METHODS
(low voltage, limited current Class 2 wiring):
5V-24V, AC or DC, 5mA
ON = voltage applied
OFF = voltage removed
Switch Schematic
Switch Switch SPST
LED
2.2K 1/2W Resistor Common
+24V Out
No Conn.
Follow polarity indicators, if any, on sequencer/controller
(rating: 24V, 37.5mA)
ON = connection applied (closed)
OFF = connection removed (open)
No Conn.
No Conn.
( + )
Com ( – )
+24VDC Output (250mA max.)
Switch
Common
Trigger Input (5V-24V AC or DC)
+24VDC Out (250mA max.)
Switch
Common
Trigger In (5V-24V AC or DC) +24VDC Out (250mA max.)
Switch
Common
Trigger In (5V-24V AC or DC)
EXAMPLE 1: SPST switch with MAINTAINED closure.
See Lowell RPS Series models listed on pg. 1.
Lowell
SPST Switch
with MAINTAINED
closure
EXAMPLE 2: Sequencer or Control System.
Lowell SEQ Series sequencer or control system by others.
Sequencer
or Control
System
EXAMPLE 3: Voltage Input.
Voltage input from external control system (by others).
ADD Resistor, 4.7 K 1/2W min.
(not included).
EXAMPLE 4: Fire Alarm Panel Interface.
Application Example: RPC controls power to music/paging system.
A signal from Fire Alarm Panel forces music/paging system OFF
so an alarm can be heard.
Alarm
System
Normally Closed (N.C.) line
from Fire Alarm System.
Closed loop from Fire Alarm
Panel holds RPC ON. When loop
is opened by Fire Alarm Panel,
the RPC turns OFF.
Normally Open (N.O.) line
from Fire Alarm System.
Voltage from +24V Out,
through a resistor,* to
Trigger In holds power to
outlet ON. Shorting Trigger In
to Com via Fire Alarm Panel contact
closure forces power to outlet OFF.
+24VDC Out (250mA max.)
Switch
Common
Trigger In (5V-24V AC or DC)
No Conn.
No Conn.
Alarm
System +24VDC Out (250mA max.)
Switch
Common
Trigger In (5V-24V AC or DC)
No Conn.
SERIES OVERVIEW
Model No. Chassis Outlets Input Power Rating Surge Suppression ConnectionsExternal Activation Required
RPC-15 Standalone NEMA 5-15R (2) 6' attached cord 125VAC 60Hz 15A --- Dry contact closure Terminal Strip
RPC-15-S Standalone NEMA 5-15R (2) 6' attached cord 125VAC 60Hz 15A Dry contact closure Terminal StripYes
RPC-15-SCD-RJ Standalone NEMA 5-15R (2) 6' attached cord 125VAC 60Hz 15A Dry contact closure or VT* TS or RJ45Yes
RPC-15-U Standalone IEC C13 (2) 6' detachable cord (2) 100-240VAC 50/60Hz 15A --- Dry contact closure or VT* Terminal Strip
RPC-20-CD Standalone NEMA 5-20R (2) 6' attached cord 125VAC 60Hz 20A --- Dry contact closure or VT* Terminal Strip
RPC-20-SCD Standalone NEMA 5-20R (2) 6' attached cord 125VAC 60Hz 20A Dry contact closure or VT* Terminal StripYes
RPC-20-SCD-RJ Standalone NEMA 5-20R (2) 6' attached cord 125VAC 60Hz 20A Dry contact closure or VT* TS or RJ45Yes
RPC-3N1 Standalone NEMA 5-15R (8) 6' attached cord 125VAC 60Hz 15A --- Dry contact closure Terminal Strip
RPC-4CD Rack-mount NEMA 5-15R (8) 6' attached cord 125VAC 60Hz 15A --- Dry contact closure Terminal Strip
RPC-20-HW Standalone NEMA 20A (2) 6'  exible whip 125VAC 60Hz 20A --- Dry contact closure or VT* Terminal Strip
RPC-20-SHW Standalone NEMA 20A (2) 6'  exible whip 125VAC 60Hz 20A Dry contact closure or VT* Terminal StripYes
RPC-30-SHW Standalone Twistlock 30A (1) 6'  exible whip 125VAC 60Hz 30A Dry contact closure or VT* Terminal StripYes
* VT indicates the RPC can also accept a voltage trigger provided by an independent control system.
T H I S
SPEC


Product specificaties

Merk: Lowell
Categorie: Niet gecategoriseerd
Model: RPC-30

Heb je hulp nodig?

Als je hulp nodig hebt met Lowell RPC-30 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Lowell

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd