DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
680407715299
Made in Turkey
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
C1
A1
SET
°C
SET
ET2412
ENDA
°F C1 A1
77mm
ENDA 2412 ON/OFF HEAT CONTROLLER ET
Thank you for choosing ON/OFF Heat Controller.ENDA ET2412
Read this document carefully before using this device. The guarantee will be expired by device
demages if you don't attend to the directions in the user manual. Also we don't accept any
compensations for personal injury, material damage or capital disadvantages.
77 x 35mm sized.
Single NTC sensor input.
Zero point input shift.
Selectable heating or cooling control for C1 relay output.
Upper and lower setpoint limits can be adjusted.
Temperature unit can be selected as °C or °F.
CE marked according to European Norms.
A1 Relay output for alarm control.
Selectable independent, deviation and band alarm types.
In the case of sensor failure, relay state can be set to
ON or OFF.
ENDA ET2412 is intended for installation within control panels. Make sure that the device is used only for
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be protected against
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded.
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables.
These cables should not be close to the power cables or components. The installation and electrical connections must
be carried out by a qualiîed staî and must be according to the relevant locally applicable regulations.
CONNECTION DIAGRAM
ET2412-012-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 68 04 07 715 3 12
Made in Turkey
C1
1 2 3 4 5 6 7 8 9 10 11 12
NTC
ET2412-024-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 68 04 07 715 3 05
Made in Turkey
1 2 3 4 5 6 7 8 9 10 11 12
NTC
ET2412-230-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 68 04 07 715 2 99
Made in Turkey
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
A1
C1
A1
C1
A1
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
5
6
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identiîcation of the
relevant instrument and it should be easily
accessible by the operator.
230V AC +%10 -%20, 50/60Hz 24V AC %10or 12/ /DC
Max. 3 VA
Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.
EN 61326-1: 2013 (Performance criterion B is satisîed for EN 61000-4-3)
EEPROM ( 10 )Min. years
Max. 100ohm
EN 61010-1: 20 (Pollution degree 2, overvoltage category II)10
12 bit , sampling time.resolution 100ms
Max. 2000m
Do not use the device in locations subject to corrosive and îammable gasses.
Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
0 ... +50 / -25... +70
°C °C without icing( )
According to EN60529; Front panel: IP65 Rear panel : IP20
S alc e Range Accuracy
EN 60751
- ... 0 °C -76.0...302.0°F60.0 15 .0
Âą 1% (for full scale) Âą 1 Digit
Supply
HOUSING
Housing Type
Dimensions
Weight
Enclosure Materials
CONTROL
ontrolC Type
Control Algorithm
A/D Converter
Hysteresis
INPUT
Height
Ambient/Storage temperature
Relative Humidity
Protection Class
Input Type
NTC Sensor Resistance
61mm 5mm
2
Connection
Cable Panel
Rubber
Packing
71,5mm
1
250V AC, 8A ( ), NO and NC control output.resistive load
OUTPUT
Life Expectancy for Relay
C1 Output
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
ELECTRICAL CHARACTERISTICS
Power onsumptionC
Wiring
Indicator
EMC
Safety Requirements
Data Retention
Line Resistance
4 digits, 12.5mm, 7 segment red LED
Single and alarm .-setpoint control
Adjustable between 0.1 and 20.0°C/F.
according to DIN 43 700.Suitable for îush-panel mounting
5 1W77xH3 xD6 mm
Approx. 215g (A )fter packing
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Dimensions
For removing mounting clamps:
-Push the îush-mounting clamp
in direction as shown in the
îgure below.Then,pull
out the clamp in direction .
1
2
Depth
Flush mounting
clamp
Flush mounting
clamp Panel cut-out Note:1) Panel thickness should
be maximum 7mm.
2) If there is no 60mm free
space at the back side of
the device,it would be
diîcult to remove it from
the panel.
t
30. Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC. Mio.
A1 Output
250V AC, 8A ( ), NO control output.resistive load
Order Code : ET2412 - -
1 2
1 - Supply Voltage
230... 230V AC
24........24V AC
.....
110........110V AC
0 /DC
012........12V AC/DC
SM.........7-24VAC/9-30VDC
2 - Relay Current Selection
08.....8A Relay Output
SET
°C
SET
ET2412
ENDA
°F C1 A1
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
up to date: 25.03.2019, modiîcation reserved and can be change any time previous notice !
ET2412-E-25032019
1. / 2
english
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
SET SET
A1.ty = .
Please see A1 Output Format Table for
settings.
Alarm type selection
a1..sc. A1.Cn.
nonE
P.yEs
P. no
= Security menu access
level
= Invisible.
= Can be modiîed.
Visible but canât be modiîed. =
A.1.L.L.
A1.H.L.
A1.ty.
A1.Hy.
oFFs.
C.tyP.
Unit.
d.P.
C1.Cn. A1.Cn. ConF. SECu.
S.Cod.
C1.sc.
A1..sc.
Co..sc.
C.S.sc.
A.S.sc.
SET SET SET SET
Programming Menu
Default
Value
-60
P.YES
P.YES
P.YES
P.YES
P.YES
0
150
in.A.L.
2
HEAt
°C
no
0
Programming Diagram
SET
100
110
SET
When this button is pressed
message is appeared
and temperature setpoint
adjustment mode is entered.
C.SEt
Measured temperature C1 Set value
A1 Set value
105 C1.SE.
A1.SE.
101
111
102
112
101
111
Default value
100
110
If no key is pressed within 3 seconds, Running Mode is entered.
Running Mode
A1 OUTPUT FORMATS
Independent Alarm
A1.ty. in.A.l.=
A1.ty. in.A.H.=
Deviation Alarm
=A1.ty. dE.a.l.
=A1.ty. dE.a.H.
Band larmA
=A1.ty. bi.A.l.
=A1.ty. bi.A.H.
ASV
SV
SV
SV+ASV
SV+ASV
SV-ASV
OFF OFF
OFF
OFF OFF
OFF
-300
300
+300
300
ON ON
ON
ON ON
ON
SV = C1 output setpoint ASV = A1 output setpoint
(ASV in. =-300, ASV . = +300)M Max
(ASV in. = 0, ASV . = +300)M Max
(ASV . =
ASV . = )
Min Beginning of Scale
Max End of Scale SV =C1 output setpoint ASV = A1 output setpoint
a1,Hy. A1.Hy.
A1.Hy.A1.Hy.
SET
C1.E.S.
A1.E.S.
off
off
Temperature setpoint value is adjusted with buttons then,
when one of these buttons are pressed for the îrst time, blinking
setpoint value appears.
If no key is pressed within 3 seconds, Running Mode is entered.
Entering Running Mode in Programming Mode :
In Programmin Mode, if no keys are pressed for 20 seconds information is saved automatically
and Running Mode is entered. Alternatively, if and keys are pressed together,
Programming Menu is entered. In the Programming Menu, if key is pressed while holding
down key, then Running Mode is entered.
SET
If key is pressed while holding down key,
then Programming Menu is entered.
C1.Hy. = Output hysteresis value.
It can be adjusted between and
.
0.1
20.0 °C
C1..L.L.
C1..H.L.
C1.Hy.
Default
Value
-60
150
2
C1..L.L.= Control set point lower limit
for C1 output.
It can be adjusted between -60.0 and
parameter value.C1.H.L.
C1H.L.= Control set point upper limit
for C1 output.
It can be adjusted between 150.0 and
parameter value.C1.L.L.
S.Cod = Access code for security menu.
This parameter should be .412
SET
When , key is
pressed for 4 seconds while
holding down key, then
is seen on display and the
device is returned to factory
settings.
s.co. = 0
d.PAr.
C1..sc. C1,Cn.
nonE
P.yEs
P. no
=
=
= Can be m ed
Visible but canât be modiîed
Security menu access
level.
Invisible.
odiî .
= .
..Co.sc. ConF.
nonE
P.yEs
P. no
= Conîguration menu
access level.
= Invisible.
= Can be modiîed.
Visible but canât be modiîed. =
C.S.sc.
P.yEs
P. no
= security access
level.
=
.
C1 set value
Can be modiîed.
= Visible but canât be modiîed
C.S.sc.
P.yEs
P. no
= security access
level.
=
.
Alarm set value
Can be modiîed.
= Visible but canât be modiîed
C.typ. = Control type selection.
C.typ. HEAt
C.typ. CooL
=
=
Heating control is selected.
Cooling control is selected.
Unit = Temperature unit selection.
Unit. °C °F = Can be selected as or
d.P. = Decimal point display selection.
If , decimal value is not dotted.
If = , decimal value is dotted.
d.P.. no
d.P. YES
=
oFFS. = Oîset .
Zero point shift value is added to the
measured value. This feature is used for
eliminating the measuring probe distance
errors. It can be adjusted between - and
°C.
value
20.0
20.0
C1.E.S.
on
off
= C1 Output state in case of sensor
failure.
= Output is ON in case of sensor
failure.
= Output is OFF in case of sensor
failure.
A1..L.L.= Control set point lower limit for
A1 output.
It can be adjusted between -60.0 and
parameter value.A1.H.L.
A1H.L.= Control set point upper limit for
A1 output.
It can be adjusted between 150.0 and
parameter value.A1.L.L.
A1.Hy. = .
.
A1çikisi histerisiz degeri
0.1 ile 20.0 °C arasinda ayarlanabilir
A1.E.S.
on
off
= A1 Output state in case of
sensor failure.
= Output is ON in case of sensor
failure.
= Output is OFF in case of sensor
failure.
Default
Value
Default
Value
ERROR MESSAGES
pfa
____
Sensor is broken
Temperature value is
higher than the scale
Temperature value is
lower than the scale
----
Modiîcation Of Parameter Diagram
Wh holding key, parameter and
using keys the requested value can be adjusted.
ile down value blinks by
,
SET SET SET
SET
If key is pressed and held 0.6 seconds, the value of the
selected parameter increases rapidly. If waited enough,the
value increases a hundred at each step. After 1 second,
following the release of the key, initial increasing condition is
returned. The same procedure is valid for the decrementing.
ET2412-E-25032019
2. / 2
Product specificaties
Merk: | Enda |
Categorie: | Thermostaat |
Model: | ET2412 |
Heb je hulp nodig?
Als je hulp nodig hebt met Enda ET2412 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Thermostaat Enda
11 Juni 2024
18 Mei 2024
18 Mei 2024
17 Mei 2024
17 Mei 2024
17 Mei 2024
Handleiding Thermostaat
- Thermostaat Bosch
- Thermostaat Panasonic
- Thermostaat Bticino
- Thermostaat AEG
- Thermostaat ATAG
- Thermostaat Honeywell
- Thermostaat Junkers
- Thermostaat Nefit
- Thermostaat Remeha
- Thermostaat Siemens
- Thermostaat Vaillant
- Thermostaat ACV
- Thermostaat Agpo Ferroli
- Thermostaat Alecto
- Thermostaat Ambiano
- Thermostaat Amfra
- Thermostaat Arnold Rak
- Thermostaat ATTACK
- Thermostaat AVM
- Thermostaat AWB
- Thermostaat Basetech
- Thermostaat Berker
- Thermostaat Boneco
- Thermostaat Brennenstuhl
- Thermostaat Brink
- Thermostaat Bryant
- Thermostaat Buderus
- Thermostaat Bulex
- Thermostaat Daikin
- Thermostaat Danfoss
- Thermostaat De Dietrich
- Thermostaat Devi
- Thermostaat Devolo
- Thermostaat Dimplex
- Thermostaat Drayton
- Thermostaat Drayton Erie
- Thermostaat Easy Timer
- Thermostaat EasyTemp
- Thermostaat EBERLE
- Thermostaat Econo-Heat
- Thermostaat Elco
- Thermostaat Elektrobock
- Thermostaat Elgato
- Thermostaat Eliwell
- Thermostaat Elro
- Thermostaat ELV
- Thermostaat Emerson
- Thermostaat Emmeti
- Thermostaat Eneco
- Thermostaat EQ-3
- Thermostaat Eqiva
- Thermostaat Essent
- Thermostaat Etherma
- Thermostaat Eurotronic
- Thermostaat Extraflame
- Thermostaat Feller
- Thermostaat Ferguson
- Thermostaat Ferroli
- Thermostaat Finder
- Thermostaat GE
- Thermostaat Gira
- Thermostaat Go Green
- Thermostaat Google
- Thermostaat Grasslin
- Thermostaat Grohe
- Thermostaat Hager
- Thermostaat Hama
- Thermostaat Helios (Amfra)
- Thermostaat HomeMatic
- Thermostaat Hornbach
- Thermostaat HQ
- Thermostaat Hugo Muller
- Thermostaat Hunter
- Thermostaat ICY
- Thermostaat Intergas
- Thermostaat IR-V
- Thermostaat Itho
- Thermostaat Itho-Daalderop
- Thermostaat Landis Gyr
- Thermostaat Levica
- Thermostaat Lowes
- Thermostaat Magnum
- Thermostaat Max
- Thermostaat Muller
- Thermostaat Nest
- Thermostaat Netatmo
- Thermostaat Niko
- Thermostaat Nobo
- Thermostaat Noma
- Thermostaat Perel
- Thermostaat Plieger
- Thermostaat Plugwise
- Thermostaat Profile
- Thermostaat Rademacher
- Thermostaat Radson
- Thermostaat REMKO
- Thermostaat Renkforce
- Thermostaat RWE
- Thermostaat Salus
- Thermostaat Saunier Duval
- Thermostaat Schneider
- Thermostaat Silvercrest
- Thermostaat Somfy
- Thermostaat Stiebel Eltron
- Thermostaat Sygonix
- Thermostaat Tado
- Thermostaat Taurus
- Thermostaat Techno Line
- Thermostaat Technoline
- Thermostaat Tesla
- Thermostaat TFA
- Thermostaat Theben
- Thermostaat THERMAFLEX
- Thermostaat Thermy
- Thermostaat TP Link
- Thermostaat Trotec
- Thermostaat Truma
- Thermostaat UPM
- Thermostaat Vasco
- Thermostaat VDH
- Thermostaat Velleman
- Thermostaat Viessmann
- Thermostaat Wachendorff
- Thermostaat Watts
- Thermostaat Webasto
- Thermostaat Weishaupt
- Thermostaat Westfalia
- Thermostaat Wolf
- Thermostaat Worcester-Bosch
- Thermostaat Xavax
- Thermostaat Z-Wave
- Thermostaat Zehnder
- Thermostaat Johnson Control
- Thermostaat Jung
- Thermostaat Oertli
- Thermostaat OJ ELECTRONICS
- Thermostaat Orbis
- Thermostaat Oregon Scientific
- Thermostaat Otio
- Thermostaat Schwaiger
- Thermostaat Fenix
- Thermostaat Conrad
- Thermostaat CorberĂł
- Thermostaat EMOS
- Thermostaat King
- Thermostaat Cotech
- Thermostaat Avidsen
- Thermostaat Hive
- Thermostaat Kemot
- Thermostaat Coati
- Thermostaat Nexa
- Thermostaat SPC
- Thermostaat Baxi
- Thermostaat Aube
- Thermostaat Carrier
- Thermostaat Cepra
- Thermostaat Delta Dore
- Thermostaat ELKO
- Thermostaat Fantini Cosmi
- Thermostaat Heatmiser
- Thermostaat Heimeier
- Thermostaat Horstmann
- Thermostaat IMIT
- Thermostaat Oventrop
- Thermostaat Seitron
- Thermostaat TrickleStar
- Thermostaat TylĂś
- Thermostaat Vemer
- Thermostaat Warmup
- Thermostaat Fibaro
- Thermostaat Energenie
- Thermostaat Mikoterm
- Thermostaat Ariston Thermo
- Thermostaat Carel
- Thermostaat Busch-Jaeger
- Thermostaat EVE
- Thermostaat Optima
- Thermostaat Frico
- Thermostaat EQ3
- Thermostaat Homematic IP
- Thermostaat Computherm
- Thermostaat Wattio
- Thermostaat Crestron
- Thermostaat ORNO
- Thermostaat POER
- Thermostaat Heatit
- Thermostaat 2Heat
- Thermostaat Veria
- Thermostaat ThermoSmart
- Thermostaat Yokis
- Thermostaat Vimar
- Thermostaat PECO
- Thermostaat H-Tronic
- Thermostaat Intertechno
- Thermostaat Tru Components
- Thermostaat Emko
- Thermostaat Innogy
- Thermostaat Wallair
- Thermostaat Maico
- Thermostaat HomePilot
- Thermostaat Ouellet
- Thermostaat ChiliTec
- Thermostaat Tellur
- Thermostaat Jumo
- Thermostaat Qubino
- Thermostaat STI
- Thermostaat Gewiss
- Thermostaat Sinustec
- Thermostaat Rose LM
- Thermostaat MundoControl
- Thermostaat Bearware
- Thermostaat GENERAL Life
- Thermostaat Oreg
- Thermostaat Braeburn
Nieuwste handleidingen voor Thermostaat
18 December 2024
18 December 2024
17 December 2024
16 December 2024
16 December 2024
15 December 2024
11 December 2024
10 December 2024
9 December 2024
9 December 2024