Enda ET2412 Handleiding

Enda Thermostaat ET2412

Lees hieronder de 📖 handleiding in het Nederlandse voor Enda ET2412 (2 pagina's) in de categorie Thermostaat. Deze handleiding was nuttig voor 23 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
ET2412-230
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
680407715299
Made in Turkey
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
C1
A1
SET
°C
SET
ET2412
ENDA
°F C1 A1
77mm
ENDA 2412 ON/OFF HEAT CONTROLLER ET
Thank you for choosing ON/OFF Heat Controller.ENDA ET2412
Read this document carefully before using this device. The guarantee will be expired by device
demages if you don't attend to the directions in the user manual. Also we don't accept any
compensations for personal injury, material damage or capital disadvantages.
77 x 35mm sized.
Single NTC sensor input.
Zero point input shift.
Selectable heating or cooling control for C1 relay output.
Upper and lower setpoint limits can be adjusted.
Temperature unit can be selected as °C or °F.
CE marked according to European Norms.
A1 Relay output for alarm control.
Selectable independent, deviation and band alarm types.
In the case of sensor failure, relay state can be set to
ON or OFF.
ENDA ET2412 is intended for installation within control panels. Make sure that the device is used only for
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be protected against
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded.
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables.
These cables should not be close to the power cables or components. The installation and electrical connections must
be carried out by a qualied sta and must be according to the relevant locally applicable regulations.
CONNECTION DIAGRAM
ET2412-012-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 68 04 07 715 3 12
Made in Turkey
C1
1 2 3 4 5 6 7 8 9 10 11 12
NTC
ET2412-024-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 68 04 07 715 3 05
Made in Turkey
1 2 3 4 5 6 7 8 9 10 11 12
NTC
ET2412-230-08
DIGITAL THERMOSTAT
250V AC 8A
RESISTIVE LOAD
8 68 04 07 715 2 99
Made in Turkey
1 2 3 4 5 6 7 8 9 10 11 12
NTC
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
A1
C1
A1
C1
A1
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
5
6
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identication of the
relevant instrument and it should be easily
accessible by the operator.
230V AC +%10 -%20, 50/60Hz 24V AC %10or 12/ /DC
Max. 3 VA
Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.
EN 61326-1: 2013 (Performance criterion B is satised for EN 61000-4-3)
EEPROM ( 10 )Min. years
Max. 100ohm
EN 61010-1: 20 (Pollution degree 2, overvoltage category II)10
12 bit , sampling time.resolution 100ms
Max. 2000m
Do not use the device in locations subject to corrosive and ammable gasses.
Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
0 ... +50 / -25... +70
°C °C without icing( )
According to EN60529; Front panel: IP65 Rear panel : IP20
S alc e Range Accuracy
EN 60751
- ... 0 °C -76.0...302.0°F60.0 15 .0
Âą 1% (for full scale) Âą 1 Digit
Supply
HOUSING
Housing Type
Dimensions
Weight
Enclosure Materials
CONTROL
ontrolC Type
Control Algorithm
A/D Converter
Hysteresis
INPUT
Height
Ambient/Storage temperature
Relative Humidity
Protection Class
Input Type
NTC Sensor Resistance
61mm 5mm
2
Connection
Cable Panel
Rubber
Packing
71,5mm
1
250V AC, 8A ( ), NO and NC control output.resistive load
OUTPUT
Life Expectancy for Relay
C1 Output
TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
ELECTRICAL CHARACTERISTICS
Power onsumptionC
Wiring
Indicator
EMC
Safety Requirements
Data Retention
Line Resistance
4 digits, 12.5mm, 7 segment red LED
Single and alarm .-setpoint control
Adjustable between 0.1 and 20.0°C/F.
according to DIN 43 700.Suitable for ush-panel mounting
5 1W77xH3 xD6 mm
Approx. 215g (A )fter packing
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Dimensions
For removing mounting clamps:
-Push the ush-mounting clamp
in direction as shown in the
gure below.Then,pull
out the clamp in direction .
1
2
Depth
Flush mounting
clamp
Flush mounting
clamp Panel cut-out Note:1) Panel thickness should
be maximum 7mm.
2) If there is no 60mm free
space at the back side of
the device,it would be
dicult to remove it from
the panel.
t
30. Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC. Mio.
A1 Output
250V AC, 8A ( ), NO control output.resistive load
Order Code : ET2412 - -
1 2
1 - Supply Voltage
230... 230V AC
24........24V AC
.....
110........110V AC
0 /DC
012........12V AC/DC
SM.........7-24VAC/9-30VDC
2 - Relay Current Selection
08.....8A Relay Output
SET
°C
SET
ET2412
ENDA
°F C1 A1
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
up to date: 25.03.2019, modication reserved and can be change any time previous notice !
ET2412-E-25032019
1. / 2
english
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
SET SET
A1.ty = .
Please see A1 Output Format Table for
settings.
Alarm type selection
a1..sc. A1.Cn.
nonE
P.yEs
P. no
= Security menu access
level
= Invisible.
= Can be modied.
Visible but can’t be modied. =
A.1.L.L.
A1.H.L.
A1.ty.
A1.Hy.
oFFs.
C.tyP.
Unit.
d.P.
C1.Cn. A1.Cn. ConF. SECu.
S.Cod.
C1.sc.
A1..sc.
Co..sc.
C.S.sc.
A.S.sc.
SET SET SET SET
Programming Menu
Default
Value
-60
P.YES
P.YES
P.YES
P.YES
P.YES
0
150
in.A.L.
2
HEAt
°C
no
0
Programming Diagram
SET
100
110
SET
When this button is pressed
message is appeared
and temperature setpoint
adjustment mode is entered.
C.SEt
Measured temperature C1 Set value
A1 Set value
105 C1.SE.
A1.SE.
101
111
102
112
101
111
Default value
100
110
If no key is pressed within 3 seconds, Running Mode is entered.
Running Mode
A1 OUTPUT FORMATS
Independent Alarm
A1.ty. in.A.l.=
A1.ty. in.A.H.=
Deviation Alarm
=A1.ty. dE.a.l.
=A1.ty. dE.a.H.
Band larmA
=A1.ty. bi.A.l.
=A1.ty. bi.A.H.
ASV
SV
SV
SV+ASV
SV+ASV
SV-ASV
OFF OFF
OFF
OFF OFF
OFF
-300
300
+300
300
ON ON
ON
ON ON
ON
SV = C1 output setpoint ASV = A1 output setpoint
(ASV in. =-300, ASV . = +300)M Max
(ASV in. = 0, ASV . = +300)M Max
(ASV . =
ASV . = )
Min Beginning of Scale
Max End of Scale SV =C1 output setpoint ASV = A1 output setpoint
a1,Hy. A1.Hy.
A1.Hy.A1.Hy.
SET
C1.E.S.
A1.E.S.
off
off
Temperature setpoint value is adjusted with buttons then,
when one of these buttons are pressed for the rst time, blinking
setpoint value appears.
If no key is pressed within 3 seconds, Running Mode is entered.
Entering Running Mode in Programming Mode :
In Programmin Mode, if no keys are pressed for 20 seconds information is saved automatically
and Running Mode is entered. Alternatively, if and keys are pressed together,
Programming Menu is entered. In the Programming Menu, if key is pressed while holding
down key, then Running Mode is entered.
SET
If key is pressed while holding down key,
then Programming Menu is entered.
C1.Hy. = Output hysteresis value.
It can be adjusted between and
.
0.1
20.0 °C
C1..L.L.
C1..H.L.
C1.Hy.
Default
Value
-60
150
2
C1..L.L.= Control set point lower limit
for C1 output.
It can be adjusted between -60.0 and
parameter value.C1.H.L.
C1H.L.= Control set point upper limit
for C1 output.
It can be adjusted between 150.0 and
parameter value.C1.L.L.
S.Cod = Access code for security menu.
This parameter should be .412
SET
When , key is
pressed for 4 seconds while
holding down key, then
is seen on display and the
device is returned to factory
settings.
s.co. = 0
d.PAr.
C1..sc. C1,Cn.
nonE
P.yEs
P. no
=
=
= Can be m ed
Visible but can’t be modied
Security menu access
level.
Invisible.
odi .
= .
..Co.sc. ConF.
nonE
P.yEs
P. no
= Conguration menu
access level.
= Invisible.
= Can be modied.
Visible but can’t be modied. =
C.S.sc.
P.yEs
P. no
= security access
level.
=
.
C1 set value
Can be modied.
= Visible but can’t be modied
C.S.sc.
P.yEs
P. no
= security access
level.
=
.
Alarm set value
Can be modied.
= Visible but can’t be modied
C.typ. = Control type selection.
C.typ. HEAt
C.typ. CooL
=
=
Heating control is selected.
Cooling control is selected.
Unit = Temperature unit selection.
Unit. °C °F = Can be selected as or
d.P. = Decimal point display selection.
If , decimal value is not dotted.
If = , decimal value is dotted.
d.P.. no
d.P. YES
=
oFFS. = Oset .
Zero point shift value is added to the
measured value. This feature is used for
eliminating the measuring probe distance
errors. It can be adjusted between - and
°C.
value
20.0
20.0
C1.E.S.
on
off
= C1 Output state in case of sensor
failure.
= Output is ON in case of sensor
failure.
= Output is OFF in case of sensor
failure.
A1..L.L.= Control set point lower limit for
A1 output.
It can be adjusted between -60.0 and
parameter value.A1.H.L.
A1H.L.= Control set point upper limit for
A1 output.
It can be adjusted between 150.0 and
parameter value.A1.L.L.
A1.Hy. = .
.
A1çikisi histerisiz degeri
0.1 ile 20.0 °C arasinda ayarlanabilir
A1.E.S.
on
off
= A1 Output state in case of
sensor failure.
= Output is ON in case of sensor
failure.
= Output is OFF in case of sensor
failure.
Default
Value
Default
Value
ERROR MESSAGES
pfa
____
Sensor is broken
Temperature value is
higher than the scale
Temperature value is
lower than the scale
----
Modication Of Parameter Diagram
Wh holding key, parameter and
using keys the requested value can be adjusted.
ile down value blinks by
,
SET SET SET
SET
If key is pressed and held 0.6 seconds, the value of the
selected parameter increases rapidly. If waited enough,the
value increases a hundred at each step. After 1 second,
following the release of the key, initial increasing condition is
returned. The same procedure is valid for the decrementing.
ET2412-E-25032019
2. / 2


Product specificaties

Merk: Enda
Categorie: Thermostaat
Model: ET2412

Heb je hulp nodig?

Als je hulp nodig hebt met Enda ET2412 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Thermostaat Enda

Handleiding Thermostaat

Nieuwste handleidingen voor Thermostaat