ENDA ATC9311
ANALOG THERMOSTAT withDIGITAL DISPLAY
ControloutputstateLED
(Lightisonwhencontroloutputisenergised)
Setkey
Adjustingknob
Temperaturedisplay
200
250
400
300
350
100
150
50
0
°C
ENDA ATC9311
OUT
SET
glassindustry,chemistryandpharmacy,drinksindustry,dryingplant,
paperindustry,foodindustry,baker`splant,plasticindutry
Applicationareas
TechnicalSpecifications
*96x96mmsized.
*Digitaldisplayformeasuredtemperatureandsetvalue.
*SelectableOn-Offortimeproportionalcontrol.
*Fe-CuNi“J”typethermocoupleinput.
*Outputrelayisdeenergiedinthecaseofsensorfailure.
*Easysettingprocedure.
HOUSING
Housingtype Suitableforflush-panelmounting.
Dimensions W96xH96xD50mm
Weight Approx.340g(afterpacking)
Enclosurematerial Selfextinguishingplastics
CONTROL
Controltype Single-setpointcontrol
On-Off/timeproportional(optional)Controlalgorithm
A/Dconverter 9bits
Proportionalband
Controlperiod
Hysteresis
2%(fortimeporportionalcontrol)
10second(fortimeproportionalcontrol)
4 (forOn-Offcontrol)°C
ELECTRICAL CHARACTERISTICS
Supply 230V AC+10%-20%,50/60Hzor24V AC 10%,50/60Hz±
Powerconsumption Max.5VA
Thermocouple“J”type/1.5mm²screw-terminalconnection.
Input/Wiring
0...400°C
1°C
Foradjustment 4%,fordisplay 0,5%(offullscale)or 1digit.± ± ±
3digits,7.62mm,7sevensegmentLED
Scale
Sensitivity
Accuracy
Dataretention
EMC
Safetyrequirements
EN61326-1:1997, A1:1998, A2:2001(ForEMCtestsperformancecriterionBis
satisfied.)
EEPROM(>10years)
EN61010-1:2001 (Pollutiondegree2,overvoltagecategoryII)
OUTPUT
Controloutput Relay:250V AC,2A (forresistiveload),NO+NCor12VDC20mA logicoutput
Mechanical30.000.000operation;electrical300.000operationLifeexpentancyforrelay
Dimensions
50mm
14mm
SET
OUT
200
250150 °C
96mm
57mm
300100
35050
4000
ENDA ATC9311
99mm
Flush
mounting
adaptor
Depth
Rubber
packing
Panel
Panelcut-out
Note: Panelthickness
shouldbe
max.10mm.
105mm
99mm
90.5mm
90.5mm
Readthisdocumentcarefullybeforeusingthisdevice. Theguaranteewillbe
expiredbydamagingofthedeviceifyoudon'tattenttothedirectionsintheuser
manual. Alsowedon'tacceptanycompansationsforpersonalinjury,material
damageorcapitaldisadvantages.
ThankyouforchoosingENDA ATC9311temperaturecontroller.
ENVIRONMENTAL CONDITIONS
Height Max.2000m
80 upto31 decreasinglinearly50 at40% %°C °C.
Ambient/storagetemperature
Max.relativehumidity
0...+50 /°C-25...+70°C,withoutcondense
Ratedpollutiondegree AccordingtoEN60529Frontpanel:IP60
Rarepanel:IP20
Donotusethedeviceinlocationssubjecttocorrosiveandflammablegases.
english
Whilecleaningthedevice,don`tusesolvents(thinner,benzine,acidetc.)orcorrosivematerials
uptodate:01022014,modificationreservedandcanbechangeanytimepreviousnotice!
RoHS
conform
1./2 ATC9311-E
Processtemperaturevalueisseen.
Iftimeproportionalcontrolwasselected, isseen.
IfOn-Offcontrolwasselected, and areseen.
Whenthedeviceisenergised,selectedcontrolformisseenonthedisplay.
Ifthedeviceisenergisedwhileholding key,contolformchagesandtherelatedmessage
isseenonthedisplay.
If keyispressed,setvalueisseen.
When keyisreleased,processtemperatureisseenagain.
Temperaturedisplay
ATC9311ProgrammingDiagram
Selectingcontrolform
ErrorMessages
Setvalue
Ifthismessageisseen,itmeanstemperaturesesorwasnotdisconnected
orovertemperatureconditionwasoccured.Whenthismessageisseen,
Ifthismessageisseen,itmeansthedevicehasacalibrationerror.Inthis
case,thedeviceshouldbesenttoyourtrader.ortoanearestENDA local
representativeforcalibrationandtesting.Whenthismessageisseen,the
controloutputisdeenergised.
SET
SET
SET
SET
Connectiondiagram
Supplyvoltage
230V AC+%10-%20
24V AC %10±
Ordercode
ATC9311
ATC9311-SSR
ATC9311-24
ATC9311-24-SSR
Controloutput
Relay
Logicoutput
Relay
Logicoutput
ENDA ATC9311isintendedforinstallationincontrolpanels.Makesurethatthedeviceis
usedonlyforintentedpurpose.
Duringaninstallation,allofthecablesthatareconnectedtothedevicemustbefreeof
energy. Thedevicemustbeprotectedagainstinadmisiblehumidity,vibrations,severe
soilingandmakesurethattheoperationtemperatureisnotexceeded. Allinputand
outputlinesthatarenotconnectedtothesupplynetworkmustbelaidoutasshielded
andtwistedcables.Thesecablesshouldnotbeclosetothepowercablesor
components. Theshieldingmustbegroundedontheinstrumentside.
Theelectricalconnectionsmustbecarriedonbya
qualifiedstaffandmustbeaccordingtotherelevantlocallyapplicableregulations.
SENSORINPUT :
Usesuitablecompansationcables.Don'tusejointedcables.
Payattentiontothepolaritiesofthe
thermocouplecablesasshowninthefigurebelow.
TC
-
+
-
+
7
8
230V ACSupply
Mainswitch
Cablesize:1,5mm²
Fuse
F100mA 250V AC
N
L
Fusemust
beconnected!
184-253V AC
50/60Hz 5VA
Supply:
NOTE:
5
4
Logicoutputoftheinstrument ATC9311-SSR
iselectrically insulatedfromthe
internalcircuits. Therefore,whenusinga
groundingthermo-couple,donotconnect
thelogicoutputterminalstotheground.
not
1)Cablesforsupplymustbe
IEC60799orIEC60245conform.
2)Mainswitchshouldbewithin
easyreachandshouldbe
indicated!
Note:
Note:
Thetimeproportionalfunctioncontrolsatemperatureareanearthe
SET value.Outofthistemperaturrangetherelayis“OFF”byoverthe
SET valueor“ON”undertheSET value.
IftheprocessvalueapproximatedtoSET value,the“ON”timefromthe
relaywillbeshortly. Theprocesstemperaturewillbepreventtoswing
orwillbeverysmall.
196°C 200°C
SET-value
Proportionalband8°C
204°C
2%fromscale400°C=8°C
Thefusefortheloadisnotconsidered!
E-mail:info@suran-elektronik.de
Internet:www.suran-elektronik.de
Tel.: +49(0)7451/625617
Fax:+49(0)7451/6250650
SURAN Industrieelektronik
DettingerStr.9/D-72160Horba.N
Terminalconnection Terminalconnection
INDUSTRIAL ELECTRONICSENDA
ATC9311-230VAC
ANALOGTHERMOSTAT
SN:XXXXXXXXX
1 2 763 4 5
OUTPUT
250V AC2A
RESISTIVELOAD
230V AC+10%-20%
50/60Hz 5VA
8
+
-
Fe-Const
TC
1 2 763 4 5 8
+
-
LOGICOUT
12VDC20mA
230V AC+10%-20%
50/60Hz5VA
INDUSTRIAL ELECTRONICSENDA
ATC9311-230VAC
ANALOGTHERMOSTAT
-SSR
SN:XXXXXXXXX
+
-
Fe-Const
TC
2./2 ATC9311-E


Product specificaties

Merk: Enda
Categorie: Thermostaat
Model: ATC9311