Description
Operation
The ATS-10providesthemainsvoltagemonitoringandautomatictransferswitching.Intheeventofamains
voltagefailure,theremotestartrelayoutputisenergizedandtheunitautomaticallytransferstheloadfromthe
mainstothegenerator.Microprocessortechnologyallowsexactmeasurement,setpointadjustmentandtiming
functionswiththeparameterstobesimplyprogrammedanddisplayedfromthefrontpanel.
The ATS-10automatictransferswitchcandetectfailureofanyphaseofthemainssupply.Ifatleastoneofthe
mainsphasevoltagesgoesoutsidesetlimits,theunitoperatesasfollows:
- The ledturnsfromgreentored. Themainscontactoroutputisdeenergizedandthe
green ledisextinguished.
- TheremotestartoutputisenergisedaftertheRemoteStartDelayparameterhasexpired. Thegenerator
startmodulereceivesthissignalandinitiatestheenginestart.
-IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1);Whenthegeneratorvoltageiswithinset
limits,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorunwithout
loaduntiltheEngineHeatingPeriodparameterisexpired. Afterthistime,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
IftheUnitUsage Typeparameter(P00)isselectedas1(Type-2);WhentheEnginerunningsignalis
present,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorun
withoutloaduntiltheLoadgen.signalispresent.Ifthissignalispresent,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
- Thegeneratorcontactoroutputwillbeenergizedandtheyellow ledwill
illuminatesteadilywhentheGeneratorContactorDelayparameterisexpired.
-Ifthemainsvoltagereturntowithinlimits,the ledwillturntogreenandtheunitwaits
fortheMainsReturndelayparameterforthemainsvoltagestabilization.
-WhentheMainsReturnDelayparameterisexpired,theyellow ledis
extinguishedandthegeneratorcontactoroutputisdeenergized. Thenthegreen
ledwillstartblinkingandthentheunitwillwaitfortheMainscontactorDelayparameter.
-WhentheMainscontactorDelayparameterisexpired,thegreen ledwill
illuminatesteadilyandthemainscontactoroutputisenergized. Thentheremotestartoutputisdeenergized.
- Theunitisreadyforanewmainsfailure.
The ATS-10hasgota TEST modefeature. Thismodeallowsthegeneratingsettobetestedwithouttakingthe
load. ThismodeisalsocalledEmergencybackupmodewhichkeepsthegeneratingsetrunningandmakesa
quicktransferifamainsfailureoccurs.
Inthismode, Theremotestartoutputwillbeenergizedbutnoloadtransferwilltakeplaceunlesstheoccurrenceof
amainsfailure.Ifamainsfailureoccurs,theloadwillbetransferredtothegeneratingset.Ifthemainsvoltage
returntowithinlimitsandtheMainsReturnDelayparameterisexpired,theloadwillbetransferredtothemains,
butthegeneratingsetwillbekeptrunning. Theremotestartoutputwillonlydeenergizedwhenthe Testmodeis
cancelled.
MainsVoltageOkay
MainsContactorClosed
GeneratorRunning
GeneratorContactor
Closed
GeneratorRunning
GeneratorContactor
Closed
GeneratorContactorClosed
MainsVoltageOkay
GeneratorContactorClosed
MainsContactorClosed
MainsContactorClosed
1
Automatic Transfer Switch, 72x72 DIN Size
ATS-10
Automatic Transfer Switch
72 x 72 DIN Size
IntroductionBrochure.ENG ATS-1001V0207/16
2
Automatic Transfer Switch, 72x72 DIN Size
Specifications
EquipmentUse Electricalcontrolequipmentforgeneratingsets
Housing&Mounting 72mmx72mmx95mm(includingconnectors)DIN43700plastichousingforpanelmounting
PanelCut-out 69mmx69mm
Protection NEMA4X(IP65atfrontpanel,IP20atrearside)
Weight Approximately0.27kg
EnvironmentalRating Standard,indooratanaltitudeoflessthen2000meterswithnon-condensinghumidity
Operating/Storage Temperature -25ºCto+70ºC/-40ºCto+85ºC
Operating/StorageHumidity 90%max.(Non-condensing)
InstallationOverVoltageCat. IIappliances,portableequipment
PollutionDegree II,Normalofficeorworkplace,non-conductivepollution
ModeofOperation Continuous
EMC EN-61000-6-4,EMCgenericemissionstandardforindustrialequipment
EN-61000-6-2,EMCgenericimmunitystandardforindustrialequipment
ElectricalSafety EN-61010-1,safetyrequirementsforelectricalequipmentformeasurement,controland
laboratoryuse
BatterySupplyVoltage( )Z8-32V max.Operatingcurrentis240mAZ
CrankingDropouts Batteryvoltagecanbe0V formax.100msnduringcranking(batteryvoltageshouldbeZ
atleastnominalvoltagebeforecranking)
MainsVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
GeneratorVoltageMeasurement
35-300VL-N RMSV(@15.6-99.9Hz). Accuracy:1%FS.Resolution:1V
Display 4Digits,7segmentsLEDdisplayshowing:
MainsVoltage(Phase-PhaseandPhase-Neutral)
AlternatorVoltage.( )
IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1)
ProgramParameters
StatusIndicators TEST ModeLED
MainsContactorClosedLED
GeneratorContactorClosedLED
ContactSensingInputs LoadGeneratorSignal(NO)
EngineRunningSignal(NO)
RelayOutputs RemoteStartRelay(1NO+1NC.12A@32V )Z
MainsContactorRelay(1NC.5A@250V )V
GeneratorContactorRelay(1NO.5A@250V )V
MainsVolgageOkayLED
GeneratorRunningLED
PROGModeLED
3
Automatic Transfer Switch, 72x72 DIN Size
Maximum15mm/0.590inch
83.5mm/3.287inch11.5mm/0.452inch
72mm
72mm
Dimensions
PanelCut-Out
V GENV.L12 VL23 VL31
TEST
PROG
TEST
ATS-10
69mm/2.72inch
69mm/2.72inch


Product specificaties

Merk: Emko
Categorie: Niet gecategoriseerd
Model: ATS-10

Heb je hulp nodig?

Als je hulp nodig hebt met Emko ATS-10 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Emko

Emko

Emko EZM-9920 Handleiding

16 November 2024
Emko

Emko ESM-3712-H Handleiding

16 November 2024
Emko

Emko ATS-10 Handleiding

16 November 2024
Emko

Emko EPM-3790 Handleiding

16 November 2024
Emko

Emko EPM-7790 Handleiding

16 November 2024
Emko

Emko EAOM-11.2 Handleiding

16 November 2024
Emko

Emko proop7L Handleiding

14 Maart 2024
Emko

Emko GENCHARGER Handleiding

28 Februari 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd