CyberPower Smart App Sinewave PR500LCDRT1U Handleiding
CyberPower
UPS
Smart App Sinewave PR500LCDRT1U
Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower Smart App Sinewave PR500LCDRT1U (2 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 23 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/2
Smart App Sinewave Series
PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U
User’s Manual
K01-0000323-01
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read
and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install,
or operate.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an
outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower
Systems does not sell products for life support or
medical applications. DO NOT use in any circumstance that would affect operation or safety of any life support equipment, with any medical
applications, or patient care.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
CAUTION! For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive
contaminants. Please see specifications for acceptable temperature and humidity range.
CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no serviceable parts inside,
except for the battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
computer component.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from
the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following.
(1) UPS Unit; (1) User's Manual for UPS; (2) Rack Mount Brackets; (2) Wall Mount Brackets; (2) Stands (1) Emergency Power Off Cable (gray) (1)
PowerPanel® Business Edition Software CD; (1) Serial Interface Cable (RJ45/DB-9); (1) USB A+B type cable; (1) Warranty Registration Card.
OVERVIEW
The provides automatic voltage regulation for PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U
inconsistent utility power. The features 1030 Joules PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U
of surge protection, and provides battery backup during power outages. The PR500LCDRT1U
/PR750LCDRT1U/PR1000LCDRT1U ensures consistent power to your computer system and its included
software will automatically save your open files and shutdown your computer system during a utility power
loss.
AUTOMATIC VOLTAGE REGULATOR(AVR)
The stabilizes inconsistent utility power. The incoming utility power may be damaging to PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U
important data and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An Automatic
Voltage Regulator automatically increases low or decreases high voltage to a consistent, computer safe 110/120V. The unit powerful sealed
lead-acid batteries will provide power only if the incoming voltage drops below 80v or increases above 150V.
SYSTEM BLOCK DIAGRAM
HARDWARE INSTALLATION GUIDE
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours
is recommended to ensure that the battery's maximum charge capacity is achieved. Charge loss may occur
during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit will
charge in both the on and off position.
2. If you will use the software, connect the serial interface cable to the serial port on the UPS and the computer. If
you would like to use USB cable, please connect the USB cable on the UPS then connect the USB cable to your
computer.
3. With the UPS unit off and unplugged, connect your computer, monitor, and any externally powered data
storage device (Hard drive, Tape drive, etc.) into the battery power supplied outlets. DO NOT plug a laser
printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power
demands of these devices will overload and possibly damage the unit.
4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air
conditioner, refrigerator, copier, etc.). Avoid using extension cords.
5. Depress the power switch to turn the unit on. The power on indicator light will illuminate. If an overload is
detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and
unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the
circuit breaker is depressed and then turn the UPS on.
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
7. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the
battery every three months to ensure battery life.
8. Professional Rack Mount UPS provides one RJ45 and one USB port to allow connection and communication
between the UPS and computers or equipment. The Primary computers (with PowerPanel® Business Edition
installed) are the computers that you will use to control the UPS and make any changes to the operation of the
UPS. When there is a power failure, the computer which connects to Primary port will start to shutdown after a
user controlled delay. PowerPanel® Business Edition will save and close any open files prior to shutting the
system down.
9. EPO (Emergency Power Off) Port:
The feature is for the application to enable emergency power shutdown. Use the gray cable provided to connect
the UPS to a normally closed or normally open contact switch according to the circuit diagram. EPO function is
provided in the UPS. EPO remote switch which is a Push-Back button installed computer room outside by a
phone line and not connected any other equipment.
FRONT / REAR PANEL DESCRIPTION
1 Power Switch.
Master on/off switch for equipment connected to the UPS.
2. Power On Indicator
Indicates the power is on.
3. LCD Module Display
LCD shows all the UPS information with icons and messages.
4 LCD Display Toggle Button .
The button can be used to toggle between different data displays
on the LCD.
5 Battery Backup and Surge Protected Outlets .
Provides six battery powered, surge protected and AVR outlets
for connected equipment and ensures temporary uninterrupted
operation of connected equipment during a power failure.
Surge Only
Surge only outlet provide surge protection without backup and
AVR function.
Critical /Non-critical
When the UPS is overloaded, the circuit breakers will be tripped
to interrupt the power supply to the uncritical outlets while
continuing to supply the critical outlets. As well, as the battery
capacity depletes under the threshold value, the uncritical outlets
will be shut down and provide energy for critical outlets. The
threshold can be determined and set by users. Non-critical
outlets can also be turned on/off manually through the software
package provided.
6 Input Power Cord .
Heavy-duty, extra long power cord.
7 Input Circuit Breaker .
Resettable circuit breakers provide Input optimal overload
Protection.
Contact your dealer, or email tech@cpsww.com. Refer to replacement battery pack number for , for RB0690X2A PR500LCDRT1U RB0670X4A
PR750LCDRT1U RB0690X4B PR1000LCDRT1U and for .
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of
personnel knowledgeable of batteries and their precautions. Servicing the battery should only be performed by trained personnel.
Replacement of batteries located in an OPERATOR ACCESS AREA.
CAUTION! When replacing batteries, replace with the same number of the following battery: for HR9-6FR(BB) PR500LCDRT1U and
PR1000LCDRT1U,BP7-6FR(BB) for PR750LCDRT1U.
CAUTION! Risk of Energy Hazard, 6V, maximum 8 Ampere-hour batteries. Before replacing batteries, remove conductive jewelry such as
chains, wrist watches, and rings. High energy through conductive materials could cause severe burns.
CAUTION! Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions.
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in
accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as they may explode. Follow all local
ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED
BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit)
BATTERY REPLACMENT PROCEDURE:
Line mode
Select SW
Press
UPS Status Display Capacity Display Digital Value Display
Load
Cap
Battery
Cap
Input
Voltage
Output
Voltage
Run
Time
% of
Load
% of
Battery
Initial V X -- X V V
1st V X -- X V V
2nd
V X -- X V V
3rd V X -- X V V
4th V X -- X V
5th
(return) V X -- X V V
(overload) V X -- V -- -- -- -- -- V --
Battery Mode
Select SW
Press
UPS Status Display Capacity Display Digital Value Display
Load
Cap
Battery
Cap
Input
Voltage
Output
Voltage
Run
Time
% of
Load
% of
Battery
Initial X V -- X V V
1
st X V -- X V V
2
nd
X V -- X V V
3
rd X V -- X V V
4
th X V -- X V
5th
(return) X V -- X V V
Press>4sec
(sound disable)
X V V X -- -- -- -- -- --
Press>4sec
again(sound enable)
X V X X -- -- -- -- -- -- --
overload X V -- V -- -- -- -- V --
“V” illuminated , “X” Not illuminated, “— “ either
IMPORTANT SAFETY WARNINGS
INSTALLING YOUR UPS SYSTEM
1. Remove two screws and right side
front panel.
2. Disconnect the black and red cable.
LCD STATUS DEFINITION
BATTERY REPLAC
E
MENT
8 USB port .
USB communication port for management software.
9. Serial Port
Serial port allows connection and communication between the UPS and the
computer.
10. SNMP/HTTP Network slot
Remove the cover panel to install optional RMCARD that allows remote
monitoring and control UPS on networks.
11. Site Wire Fault Indicator
This LED will illuminate to warn the user that a wiring problem exists within
the AC receptacle, such as a bad ground, missing ground or reversed
wiring. If illuminated, disconnect all equipment and contact an electrician to
ensure outlet is properly wired.
12. EPO (Emergency Power Off) port
The interface can be used to connect to switches for emergency power off.
BASIC OPERATION
When you first receive the
unit, plug in the unit to fully
charge the battery.
Unplug the unit and turn Power
Off when first connecting your
computer and peripherals.
3. Remove two retaining
screws and pull
out battery cabin.
.
*Note:Both USB and Serial can not be used simultaneously.
Install PowerPanel
® Business
Edition software on the primary
computer connected to UPS with
either a serial cable or USB cable.
1 2
3
LIMITED WARRANTY AND CONNECTED EQUIPMEN
T
GUARN
T
EE
TECHNICAL SPECIFICATIONS
TROUBLE SHOOTIMG
LCD
SETUP FUCTIONS
Set-up Mode
Step 1: The machine enters Set-Up Mode after holding the Display toggle for 10 seconds.
Step 2: By pressing the Display toggle, users can switch between setup functions. User configurable functions are as follows:
a. Sensitivity: Set the level of tolerance for UPS. Increase the UPS compatibility for local utility power condition.
High: The UPS will turn to battery power more often to provide the steady power supply to the connected equipment.
Low: The UPS will tolerate more fluctuations and turn to battery power less often.
b. Battery Lifetime: Show the batteries already used time. Reset the logger when battery module replacement or first time
installation.
c. Firmware Version: Show the UPS version number.
The settable items are sorted by unit as in the following table:
Step 3: Press and hold the toggle for 4 seconds. When the icons blink, the
value of each item can be changed by slightly pressing the toggle.
Step 4: To save the value and return to general mode, press and hold the toggle for 4 seconds.
Note: If the machine is left idle for over 30 seconds during setup, it will turn off the backlight and return to general mode automatically.
Note: If user wants to return to general mode without saving changes, there are two methods:
1. Wait for the backlight to turn off
2. Press and hold the “Display” toggle for 10 seconds
Problem Possible Cause Solution
Outlet do not provide power
to equipment
Circuit breaker has tripped
due to an overload.
Turn the UPS off and unplug at least one piece of equipment.
Wait 10 seconds, reset the circuit breaker by depressing the
button, and then turn the UPS on.
Batteries are discharged Recharge the unit for at least 4 hours
Unit has been damaged by a
surge or spike.
Contact CyberPower Systems about replacement batteries at
tech@cpsww.com
Uncritical outlets have
turned off automatically
due to an overload
Push the toggle button to make the uncritical outlets turn on.
The UPS does not perform
expected runtime.
Battery not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is degraded Contact CyberPower Systems about replacement batteries at
tech@cpsww.com
The UPS will not turn on.
The on/off switch is designed
to prevent damage by rapidly
turning it off and on.
Turn the UPS off. W ait 10 seconds and then turn the
UPS on.
The unit is not connected to
an AC outlet. The unit must be connected to a 110/120v outlet.
The battery is worn out. Contact CyberPower Systems about replacement batteries at
tech@cpsww.com
Mechanical problem. Contact CyberPower Systems at tech@cpsww.com
PowerPanel® Personal
Edition is inactive
The serial cable or USB cable
is not connected.
Connect the cable to the UPS unit. You must use the cable that
came with the unit.
The cable is connected to the
wrong port. Try another port of your computer
The unit is not providing
battery power.
Shutdown your computer and turn the UPS off. Wait 10
seconds and turn the UPS back on. This should reset
the unit.
The serial cable is not the
cable that was provided
with the unit.
You must use the cable included with the unit for the
software
Additional troubleshooting information can be found at www.cyberpowersystems.com/support.htm
Model PR500LCDRT1U PR750LCDRT1U PR1000LCDRT1U
Capacity(VA) 500 750 1000
Capacity(Watts) 400 600 800
Input
Input Plug Type NEMA 5-15P
Input Voltage Range 80Vac-150Vac
Input Frequency Range 60Hz+/-3Hz(auto sensing)
Output
On Battery Output Voltage Pure Sine Wave at 120Vac+/-5%
On Battery Output Frequency 60Hz+/-1%
Transfer Time(Typical) 4 ms
Overload Protection On Utility: Circuit Breaker, On Battery: Internal Current Limiting
Surge Protection and Filtering
Lightning/Surge Protection Yes
Physical
Output Receptacles (6)NEMA 5-15R+(1)NEMA 5-15R Surge Only
Dimensions(in) 1U Rack, 17.25’’ x 9.1’’ x 1.75’’
1U Rack, 17.25’’ x 16.8’’ x 1.75’’
Weight (lb) 19.8 30.7 35.9
Battery
Battery Model RB0690X2A RB0670X4A RB0690X4B
Hot Swappable Battery Yes
Warning Diagnostics
Indicators Power On, Wiring Fault, LCD Display (Using Battery, AVR, Load Level, Battery Level)
Audible Alarms On Battery, Low Battery, Overload
Environmental
Operating Temperature 32oF to 104oF ( 0oC to 40 oC )
Operating Relative Humidity 0 to 95% Non-Condensing
Operating Elevation 0-10000 feet (0-3000 meters)
Communication
PowerPanel
®Business Edition Windows 98/ME/NT/2000/XP/Vista/7
Management
Self-Test Manual Self-Test
Auto-Charger/ Auto-Restart Yes
COM Interface True RS232 x1
Built-in USB Interface Yes
SNMP/ HTTP Network Slot Yes
Safety Approvals UL1778,cUL107,FCC Part 15 Class A,CSA
GreenPower UPS™
The CyberPower GreenPower UPS™ cuts UPS energy costs by up to 75% compared to the conventional UPS
circuits. Conventional UPS systems pass power through a transformer to provide normal output voltage to protected
devices. By contrast, the GreenPower UPS™ circuitry bypasses the transformer when utility power is normal,
significantly increasing the power efficiency of the UPS. As a result, a GreenPower UPS™ produces less heat and
uses less energy reducing energy costs.
When utility power is abnormal, the GreenPower UPS™ operates like a normal UPS. Since utility power operates
normally 88% of the time, the GreenPower UPS™ operates primarily in its cost-cutting bypass mode.
Read the following terms and conditions carefully before using the CyberPower PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U (the
"Product"). By using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and
Connected Equipment Guarantee (together referred to as this "Warranty"). If you do not agree to the terms and conditions of this Warranty, you
should return the Product for a full refund prior to using it.
Who is Providing this Warranty?
CyberPower Systems (USA), Inc. ("CyberPower") provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers equipment that was
connected to the Product and damaged because of the failure of the Product.
What is the Period of Coverage?
This warranty covers the Product for three years and connected equipment for as long as you own the Product.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
How Do You Get Service?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379 or send us an
e-mail message at claims@cpsww.com for instructions.
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all
applicable insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number.
3. You must provide a dated Proof-of-Purchase receipt (or other proof of the original purchase) and provide a description of the defect.
4. Pack and ship the product with a dated Proof- of-Purchase receipt to CyberPower and, if requested, the item(s) of Connected Equipment, a
repair cost estimate for the damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number
on the shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and shipment,
and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable
to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you
paid for the Product (purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the connected
equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value
(NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or another a third-party valuation
guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to $400,000 for
PR500LCDRT1U/PR750LCDRT1U/PR1000LCDRT1U .
Who Pays For Shipping?
We pay when p2-we send items to you; you pay when you send items to us.
What Are Some Things This Warranty Does Not Cover?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost
as a result of the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the
equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with
items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.
What Other Limitations Apply?
1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded
outlets (including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other
connectors.
2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected
to the Product and not "daisy-chained" together in serial fashion with any extension cords, another Product or device similar to the Product, surge
suppressor, or power tap. Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any
license, instruction manual, or warnings provided with the Product and the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product's VA capacity.
What are the Limitations?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses from lightning
or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside
the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or Undertake Any Liability in Any Event for
Any of the Following:
1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt
power lines in the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines or
Base 10/100T Ethernet lines, when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or
reception, by CATV or RF transmission or fluctuations, or by transients in such transmission.)
3. Damage from any circumstance described as excluded above with respect to the Product.
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or the
Connected Equipment.
5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee. CyberPower excludes
any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND
ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty benefits regarding "Connected Equipment" under this
Warranty], loss of profits, business interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation may not apply to you.
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments
requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury, or
severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, "High Risk
Activities"). CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower
does not authorize use of any Product in any High Risk Activities or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF
THE PRODUCT.
What is the Fine Print?
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN
55379; call us at (877) 297-6937; or send us an e-mail message at claims@cpsww.com.
Recycle Policy
CyberPower Systems encourages environmentally sound methods for disposal and recycling of its UPS products.
Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state.
FCC Notice
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference that
may cause undesired operation.
WARNING!! This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
Shielded signal cables must be used with this product to ensure compliance with the Class A FCC limits.
Items Unit
1 Sensitivity
2 Battery Lifetime Year
3 Firmware Version
CYBERPOWER GREENPOWER
UPS
™
TECHNOLOGY
The Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada
Product specificaties
Merk: | CyberPower |
Categorie: | UPS |
Model: | Smart App Sinewave PR500LCDRT1U |
Kleur van het product: | Zwart |
Gewicht: | 8981 g |
Breedte: | 438.15 mm |
Diepte: | 241.3 mm |
Hoogte: | 44.45 mm |
Snoerlengte: | 3 m |
Gewicht verpakking: | 11475 g |
Breedte verpakking: | 528.32 mm |
Diepte verpakking: | 335.28 mm |
Hoogte verpakking: | 157.48 mm |
LED-indicatoren: | Ja |
Vormfactor: | Rackmontage/toren |
Aantal USB 2.0-poorten: | 1 |
Ondersteund aantal accu's/batterijen: | 2 |
Geluidsalarm(en): | Ja |
Duurzaamheidscertificaten: | RoHS, ENERGY STAR |
Uitgangsvermogen: | 400 W |
Accu/Batterij oplaadtijd: | 6 uur |
Temperatuur bij opslag: | -15 - 45 °C |
Stroomspanning bescherming: | Overbelasting |
Frequentie: | 57/63 Hz |
Luchtvochtigheid bij opslag: | 0 - 95 procent |
Spanning: | 120 V |
Veiligheid: | UL1778, CSA C22.2 NO.107.3-05, FCC DOC Class A |
Hoogte, in bedrijf: | 0 - 3000 m |
Hoogte bij opslag: | 0 - 15000 m |
Power factor: | 0.8 |
Seriële poort(en): | 1 |
Stekker: | NEMA 5-15P |
Rackcapaciteit: | 1U |
Bedrijfstemperatuur (T-T): | 0 - 40 °C |
Batterijtechnologie: | Sealed Lead Acid (VRLA) |
Type beeldscherm: | LCD |
Surge energy rating: | 1030 J |
Aantal AC uitgangen: | 7 AC-uitgang(en) |
Stopcontacttypes: | NEMA 5–15R |
Output power capacity: | 0.5 kVA |
Ingang operation voltage (min): | 80 V |
Ingang operation voltage (max): | 150 V |
Uitgang operation voltage (min): | - V |
Uitgang operation voltage (max): | 120 V |
UPS-topologie: | Line-interactive |
Typische backup tijd op halve lading: | 12 min |
Typische backup tijd op volledige lading: | 3 min |
Hot-swap batterij: | Ja |
Output frequentie: | 60 Hz |
Emergency Power Off (EPO): | Ja |
EMI/RFI geluidsfiltering: | Ja |
Golfvorm: | Sinus |
Automatic Voltage Regulation (AVR): | Ja |
Heb je hulp nodig?
Als je hulp nodig hebt met CyberPower Smart App Sinewave PR500LCDRT1U stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS CyberPower
15 November 2024
7 November 2024
7 November 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Tripp Lite
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
18 November 2024
17 November 2024
17 November 2024
17 November 2024
16 November 2024
15 November 2024
14 November 2024
14 November 2024
12 November 2024
22 Oktober 2024