INSTALLATION AND OPERATION MANUAL
©2023 Cyber Power Systems, Inc. All rights reserved. K01-0000914-01
SAVE THESE INSTRUCTIONS
Please read this manual and follow the instructions for installation and operation.
©2023 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners. II
Warning: High voltage – Risk of Electric Shock
Caution - Important Instructions: Must always be followed.
Do Not Discard: The UPS or UPS batteries in trash. The batteries
contain lead acid. For more information, contact your local recycling
or hazardous waste facility.
Information, advice, help
See applicable user manual
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
The Smart App Online 8-10KVA UPS models that are covered in this manual are intended for
installation in an environment within 32°F to 104°F (0°C to 40°C), free of conductive contaminants.
SPECIAL SYMBOLS
©2023 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners. III
SAFETY INSTRUCTIONS CONT.
PERSONAL SAFETY
CAUTION
To reduce the risk of fire, connect the UPS to a branch circuit with 60 amperes
(8,000 VA)/70 amperes (10,000 VA) maximum over-current protection in
accordance with the National Electric Code, ANSI/NFPA 70.
The AC electrical service where the UPS is connected should be close to the unit
and easily accessible.
Please use only UL-marked mains cable, (e.g. the mains cable of your equipment),
to connect the UPS to the AC outlet.
Please use only UL-marked power cables to connect any equipment to the UPS.
When installing the equipment, ensure that the sum of the leakage current of the
UPS and the connected equipment does not exceed 3.5mA.
Do not unplug the unit from AC power during operation, as this will disconnect the
protective ground insulation.
Do not use an improper size power cord as it may cause damage to your
equipment and cause fire hazards.
Make sure everything is turned off and disconnected completely before conducting
any maintenance, repairs or shipment.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT
SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS
OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY
PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS.
KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
FOR PERMANENTLY CONNECTED EQUIPMENT, A READILY ACCESSIBLE
DISCONNECT DEVICE SHALL BE INCORPORATED IN THE BUILDING
INSTALLATION WIRING.