User’s Manual
OL6000RT3U
OL8000RT3U
OL10000RT3U
CyberPower Systems (USA), Inc.
4241 12th Avenue East Suite 400 Shakopee, MN 55379
Phone: 877-297-6937
Fax: 952-403-0009
www.CPSww.com
K01-0000195-02
Copyright © 2011 CyberPower Systems, Inc.
IMPORTANT SAFETY INSTRUCTIONS
1
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual
thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC power
outlet with fuse or circuit breaker protection. DO NOT plug the UPS into
an outlet that is not grounded. If you need to power-drain this equipment,
turn off and unplug the unit.
CAUTION! The battery can power hazardous components inside the
unit, even when the AC input power is disconnected.
CAUTION! The UPS should be placed near the connected equipment
and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area, free of conductive
contaminants. (Please see specifications for acceptable temperature and
humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do
not remove cover. No user serviceable parts inside. Refer servicing to
qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric shock,
battery circuit is not isolated from AC power source; hazardous voltage
may exist between battery terminals and ground. Test before touching.
CAUTION! To reduce the risk of fire, connect the UPS to a branch
circuit with amperes (OL6000) / 50 amperes (OL8000) / 60 amperes 40
(OL10000) maximum over-current protection in accordance with the
National Electric Code, ANSI/NFPA 70.
CAUTION! The AC outlet where the UPS is connected should be close
to the unit and easily accessible.
CAUTION! Please use only -marked mains cable, (e.g. the mains UL
cable of your equipment), to connect the UPS to the AC outlet.
CAUTION! Please use only -marked power cables to connect any UL
equipment to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the
leakage current of the UPS and the connected equipment does not
exceed 3.5mA.
CAUTION! The OL8000/OL10000 models are permanently-connected
equipment and only qualified maintenance personnel may carry out
installations.
CAUTION! Do not unplug the unit from AC Power during operation, as
this will invalidate the protective ground insulation.
CAUTION! To avoid electric shock, turn off and unplug the unit before
installing the input/output power cord with a ground wire. Connect the
ground wire prior to connecting the line wires!
CAUTION! Do not use improper size power cord as it may cause an
d to your equipment and cause fire hazards. amage
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT
EQUIPMENT! Under no circumstances this unit should be used for
medical applications involving life support equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce
the risk of fire, do not use with or near aquariums. Condensation from
the aquarium can come in contact with metal electrical contacts and
cause the machine to short out.
CAUTION! Do not dispose of batteries in fire the battery may as
explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is
harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and high short
circuit current. The following precaution should be observed when
working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handle s.
CAUTION! The unit has a dangerous amount of voltage. When the
UPS indicators is on, the units may continue to supply power thus the
unit s outlets may have a dangerous amount of voltage even when it s not ’ ’
plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected
completely before conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before
any other cables are connected.
WARNING! (Fuses): To reduce the risk of fire, replace only with the
same type and rating of fuse.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO
DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE
HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR
DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR
SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND
THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED
PERSONNEL AWAY FROM BATTERIES!
Copyright © 2011 CyberPower Systems, Inc.
UNPACKING
2
Power module
Input / Output terminal block cover
(Only for OL8000RT3U/OL10000RT3U)
User’s manual Register card
Rackmount left rail * 2 sets Rackmount right rail * 2 sets
Phone line
USB communication cable
Serial Interface Cable (RS-232)
Battery module
Rackmount ears (Stands) (2) * 2 sets
Tie plate (1) * 1 set
Flat head screws M5X8L (8) * 2 sets :
Pan head screws M5X12L (12) * 2 sets :
Plastic washers (8) * 2 sets
Screw hole dust covers ( ) * 2 sets 10
Power cords
PowerPanel® Business Edition software CD


Product specificaties

Merk: CyberPower
Categorie: UPS
Model: OL10000RT3U
Kleur van het product: Zwart
Gewicht: 103000 g
Breedte: 433 mm
Diepte: 660 mm
Hoogte: 266.7 mm
Geluidsniveau: 55 dB
Gewicht verpakking: 126750 g
Materiaal behuizing: Staal
LED-indicatoren: Ja
Vormfactor: Rackmontage/toren
Afmetingen verpakking (BxDxH): 600 x 900 x 638 mm
Aantal USB 2.0-poorten: 1
Certificering: ETL
Geluidsalarm(en): Ja
Duurzaamheidscertificaten: RoHS
Meegeleverde software: PowerPanel
Uitgangsvermogen: 9000 W
Accu/Batterij oplaadtijd: 5 uur
Temperatuur bij opslag: -15 - 45 °C
Frequentie: 40/70 Hz
Luchtvochtigheid bij opslag: 0 - 95 procent
Hoogte, in bedrijf: 0 - 3000 m
Hoogte bij opslag: 0 - 15000 m
Power factor: 0.9
Seriële poort(en): 1
Beheerplatform: SNMP/HTTP
Efficientie: 95 procent
Rackcapaciteit: 6U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LCD
Type batterij: 12V/9AH
Aantal batterijcellen: 20
Aantal AC uitgangen: 4 AC-uitgang(en)
Golf protectie functies: Network, Telephone
Input-connectietype: Hardwire
Output power capacity: 10 kVA
Ingang operation voltage (min): 200 V
Ingang operation voltage (max): 240 V
Uitgang operation voltage (min): 200 V
Uitgang operation voltage (max): 240 V
Crest factor: 3:1
Typische backup tijd op halve lading: 11 min
Typische backup tijd op volledige lading: 4 min
Hot-swap batterij: Ja
Hoorbare alarmstanden: Batterijvervanging
Emergency Power Off (EPO): Ja
Output voltage THD: 5 procent
EMI/RFI geluidsfiltering: Ja
Spanningsbeveiliging: Ja
Koude start: Ja
Output-aansluitingen: 3 xNEMA L6-30R & 1 x Hardware Terminal Block