OVERVIEW
The CP825AVRLCDG/CP685AVRLCDG/
CP800AVR/CP685AVRG provides complete
power protection from utility power that is
not always consistent. The CP825AVRLCDG/
CP685AVRLCDG/CP800AVR/CP685AVRG
features 1030 Joules of surge protection. The
unit provides long lasting battery backup
during power outages with maintenance free
batteries. The CP825AVRLCD/CP685AVRLDG/
CP800AVR/CP685AVRG ensures consistent
power to your computer system and includes
software that will automatically save your
open files and shutdown your computer sys-
tem during a utility power loss.
HOW TO DETERMINE THE POWER REQUIRE-
MENTS OF YOUR EQUIPMENT
1. Ensure that the equipment plugged
into the UPS does not exceed the UPS
unit’s rated capacity (825VA/450W for
CP825AVRLCDG, 800VA/450W
for CP800AVR, 685VA/390W for
CP685AVRLCDG, CP685AVRG). If the rated
capacities of the unit are exceeded, an
overload condition may occur and cause
the UPS unit to shut down or the circuit
breaker to trip.
2. There are many factors that can aect
the amount of power that your electronic
equipment will require. For optimal system
performance keep the load below 80% of
the unit’s rated capacity.
HARDWARE INSTALLATION GUIDE
1. Your new UPS
may be used
immediately
upon receipt.
However, after
receiving a
new UPS, to ensure the battery’s maximum
charge capacity, it is recommended that
you charge the battery for at least 8 hours.
Your UPS is equipped with an auto-charge
feature. When the UPS is plugged into an AC
outlet, the battery will automatically charge
whether the UPS is turned on or turned o.
Note: This UPS is designed with a safety fea-
ture to keep the system from being turned
on during shipment. The first time you turn
the UPS on, you will need to have it connect-
ed to AC power or it will not power up.
2. With the UPS unit turned o and un-
plugged, connect your computer, monitor,
and any other peripherals requiring battery
backup into the battery power supplied
outlets. Plug the other peripheral equip-
ment (eg. printer, scanner, speakers, etc.)
into the full-time surge protection outlets.
DO NOT plug a laser printer, paper shred-
der, copier, space heater, vacuum cleaner,
sump pump, or other large electrical device
into the “Battery and Surge Protected Out-
lets”. The power demands of these devices
will overload and possibly damage the unit.
3. Plug the UPS into a 2-pole, 3-wire grounded
receptacle (wall outlet). Make sure the wall
branch outlet is protected
by a fuse or circuit break-
er and does not service
equipment with large
electrical demands (e.g.
air conditioner, refrigerator, copier, etc.).
The warranty prohibits the use of extension
cords, outlet strips, and surge strips in con-
junction with the UPS unit.
4. Press the power switch to turn the unit on.
The Power On indicator light will illuminate
green and the unit will “beep” once.
5. If an overload is detected, an audible alarm
will sound and the unit will emit one long
beep. To correct this, turn the UPS o and
unplug at least one piece of equipment
from the battery power supplied outlets.
Make sure the circuit breaker is depressed
and then turn the UPS on.
6. To maintain optimal battery charge,
leave the UPS plugged into an AC outlet
at all times.
7. To store the UPS for an extended period
of time, cover it and store with the battery
fully charged. While in storage, recharge
the battery every three months to ensure
optimal battery life.
8. Ensure the wall outlet and UPS are locat-
ed near the equipment being attached for
proper accessibility.
YOUR ULTIMATE ALLY IN POWER
Cyber Power Systems (USA), Inc.
4241 12th Avenue East, Suite 400 | Shakopee, MN 55379 | CyberPowerSystems.com
AVR UPS SERIES
CP825AVRLCDG / CP685AVRLCDG / CP800AVR / CP685AVRG
USER MANUAL
FEATURES
1. Power Switch
2. Power On Indicator
3. Mode Switch
For CP825AVRLCDG / CP685AVRLCDG
4. Fault Indicator
5. Mute Button
For CP800AVR / CP685AVRG
6. LCD module display
For CP825AVRLCDG / CP685AVRLCDG
7. Battery and Surge Protected Outlets
8. Full-Time Surge Protection Outlets
9. USB Port
10. Communication Protection Ports
For CP825AVRLCDG
11. Serial Port
12. Circuit Breaker and Reset
13. Ground Screw
14. Outlets Designed for AC Adapters
Thank you for purchasing a CyberPower product. This UPS is designed to provide unsurpassed
power protection, operation, and performance during the lifetime of the product. Please take
a few minutes to register your product at: www.CyberPowerSystems.com/registration. Regis-
tration certifies your product’s warranty, confirms your ownership in the event of a product loss
or theft, and entitles you to free technical support. Register your product now to receive the
benefits of CyberPower ownership.
CAUTION! To prevent the risk of fire or
electric shock, install in a temperature and
humidity controlled indoor area free of
conductive contaminants. (Please see
specifications for acceptable temperature
and humidity range).
CAUTION! To reduce the risk of electric shock,
do not remove the cover except to service the
battery. Turn o and unplug the unit before
servicing the batteries. There are no user ser-
viceable parts inside except for the battery.
CAUTION! Hazardous live parts inside can be
energized by the battery even when the AC
input power is disconnected.
CAUTION! The UPS must be connected to an
AC power outlet with fuse or circuit breaker
protection. Do not plug into an outlet that is
not grounded. If you need to de-energize this
equipment, turn o and unplug the unit.
CAUTION! To avoid electric shock, turn o the
unit and unplug it from the AC power source
before connecting equipment to the unit.
CAUTION! To reduce the risk of fire, connect
only to a circuit provided with 20 amperes
maximum branch circuit over current protec-
tion in accordance with the National Electric
Code, ANSI/NFPA 70.
CAUTION! Not for use in a computer room as
defined in the Standard for the Protection of
Electronic Computer / Data Processing Equip-
ment, ANSI/NFPA 75.
CAUTION! Do not dispose of batteries in a fire.
The batteries may explode.
CAUTION! Do not open or mutilate batteries.
Released electrolyte is harmful to the skin and
eyes. It may be toxic.
DO NOT USE FOR MEDICAL
OR LIFE SUPPORT EQUIPMENT!
CyberPower Systems does not sell products
for life support or medical applications. DO
NOT use in any circumstance that would aect
operation and safety of life support equip-
ment, any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS!
To reduce the risk of fire or electric shock, do
not use with or near an aquarium. Condensa-
tion from the aquarium can cause the unit to
short out.
DO NOT USE THE UPS
ON ANY TRANSPORTATION!
To reduce the risk of fire or electric shock, do
not use the unit on any transportation such
as airplanes or ships. The eect of shock or
vibration caused during transit and the damp
environment can cause the unit to short out.
PRODUCT REGISTRATION
IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully
during installation and operation of the unit. Read this manual thoroughly before attempting to
unpack, install, or operate your UPS.
INSTALLING YOUR UPS SYSTEM - continued
UNPACKING
Inspect the UPS upon receipt.
The box should contain the following:
(a) UPS unit
(b) User’s manual
(c) USB A+B type cable
PowerPanel® Personal software is
available on our website. Please visit
www.cyberpowersystems.com and go
to the Software Section for a free download.
AUTOMATIC VOLTAGE REGULATOR
The CP825AVRLCDG/CP685AVRLCDG/
CP800AVR/CP685AVRG stabilizes inconsistent
utility power to nominal levels that are safe for
equipment. Unstable utility power can be dam-
aging to important data and hardware.
With Automatic Voltage Regulation (AVR),
damaging voltage levels
are corrected to safe
levels. AVR automatically
increases low utility power
to a consistent and safe
110/120 volts.
BASIC OPERATION
INSTALLING YOUR UPS SYSTEM
1. Power Switch:
Used as the master on/o switch for equip-
ment connected to the battery power sup-
plied outlets. To turn the UPS ON, press the
power button for approximately 2 seconds
- you will hear a constant tone (1 second) -
and release after a short beep.
To turn the UPS OFF, press the power
button for approximately 2 seconds - you
will hear a constant tone (1 second) - and
release after two short beeps.
Alarm setting (For CP825AVRLCDG/
CP685AVRLCDG): The audible alarm can
be turned O or On by double clicking
the POWER button. The default setting is
for the Alarm On. To turn the Alarm O,
double click the button. You will hear two
short beeps when the Alarm is turned o.
To turn the Alarm back On, double click the
button. You will hear a single short beep
when the Alarm is turned on. *When the
Alarm is turned O, there will be no audible
notification when the UPS reaches a low
battery state.
2. Power On Indicator:
This LED is illuminated when the utility
power is normal and the UPS outlets are
providing power, free of surges and spikes.
3. Mode Switch
(For CP825AVRLCDG/CP685AVRLCDG):
Press the Mode Switch for approximately
3 seconds to enter setup mode to view
options: Utility High/low Voltage range,
sensitivity setup, LCD sleep ON/OFF, bat-
tery test, buzzer ON/OFF, and low battery
alarm. When an option is selected, wait for
8 seconds for the setting to be confirmed.
After the setting has been confirmed the
LCD screen will leave setup mode and go
back to status display. If there is no action
for 8 seconds during setup, the LCD will
also leave setup mode and go back to the
status display.
4. Fault Indicator:
This LED is illuminated if there is a problem
with the UPS.
5. Mute Button
(For CP800AVR/CP685AVRG):
Press the button for 2 seconds to enable
the audible alarm (beeps once) or disable
(beeps twice) the audible alarm.
6. LCD module display
(For CP825AVRLCDG/CP685AVRLCDG):
LCD display shows all the UPS information
using icons and messages. For more infor-
mation please review the “Definitions for
Illuminated LCD Indicators” section.
7. Battery and Surge Protected Outlets:
The unit has four battery powered and
surge protected outlets to ensure tempo-
rary uninterrupted operation of your equip-
ment during a power failure.
8. Full-Time Surge Protection Outlets:
The unit has four surge suppression outlets.
9. USB Port:
The USB port allows connection and com-
munication between the USB port on the
computer and the UPS unit.
10. Communication Protection Ports
(For CP825AVRLCDG):
Communication protection ports, bidirec-
tional, will protect a 10/100/1000 Ethernet
connection (RJ45).
11. Serial Port:
Serial Port allow for bi-directional commu-
nication among the UPS and the comput-
er.The UPS can control the computers
shutdown in case of an emergency, and at
the same time, the computer can monitor
the UPS and alter its various programmable
parameters.
12. Circuit Breaker and Reset:
Located on the side of the UPS, the
circuit breaker provides overload and
fault protection.
13. Ground Screw:
The ground screw is used for any
equipment that needs a chassis ground
connection.
14. Outlets Designed for AC Adapters:
The UPS unit has four widely-spaced out-
lets. AC power adapters can be plugged
into the UPS without overlapping or block-
ing adjacent outlets.
2
3 4
CP825AVRLCDG
CP685AVRLCDG
CP800AVR
CP685AVRG
Replacement of batteries located
in an OPERATOR ACCESS AREA
1. When replacing batteries, replace with
the same number of the following battery:
CyberPower/RB1290 for CP825AVRLCDG,
CP800AVR; CyberPower/RB1270B for
CP685AVRLCDG, CP685AVRG.
2. Risk of Energy Hazard, 12V, CAUTION!
maximum 9 Ampere-hour battery. Before
replacing batteries, remove conductive
jewelry such as chains, wrist watches, and
rings. High energy through conductive
materials could cause severe burns.
3. CAUTION! Do not dispose of batteries in a
fire. The batteries may explode.
4. CAUTION! Do not open or mutilate batter-
ies. Released material is harmful to the skin
and eyes. It may be toxic.
5. CAUTION! A battery can present a risk of
electrical shock and high short circuit cur-
rent. The following precautions should be
observed when working on batteries:
(1) Remove watches rings, or other metal
objects.
(2) Use tools with insulated handles.
CAUTION - RISK OF EXPLOSION IF BATTERY
IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING
TO LOCAL REGULATIONS.
TROUBLESHOOTING - continued
Problem Possible Cause Solution
Circuit breaker button is
projecting from the back of the
unit.
Circuit breaker has been tripped
due to an overload.
Turn the UPS o and unplug at
least one piece of equipment.
Wait 10 seconds, reset the circuit
breaker by pressing the button,
and then turn the UPS on.
The UPS does not perform
expected runtime.
Battery not fully charged. Recharge the battery by leaving
the UPS plugged in.
Battery is worn out.
Contact CyberPower Systems
about replacement batteries at:
cyberpowersystems.com/support.
Additional troubleshooting information can be found at “Support” at www.CyberPowerSystems.com
LOAD CAPACITY Meter: This meter displays
the approximate output load level of the UPS
battery outlets in 20% increments.
SENSITIVITY Meter: This meter displays the
sensitivity level of the UPS. It is to control the
sensitivity of the UPS to switch to Battery
Mode by selecting UPS shutdown voltage
range. When the sensitivity is increased, the
UPS will switch to Battery Mode with less
input power variation.
FAULT: The following number appears if there
is a problem with the UPS. Press the POWER
button to turn the UPS o.
DEFINITIONS FOR ILLUMINATED LED INDICATORS TECHNICAL SPECIFICATIONS - continued - continued
REPLACING THE BATTERY
TROUBLESHOOTING
Problem Possible Cause Solution
The UPS will not turn on.
The on/o switch is designed
to prevent damage from rapidly
turning it o and on.
Turn the UPS o. Wait 10 seconds
and then turn the UPS on.
The unit is not connected to an
AC outlet.
The unit must be connected to a
120V 60Hz outlet.
The battery is worn out.
Contact CyberPower Systems
about replacement batteries at:
cyberpowersystems.com/support.
Mechanical problem. Contact CyberPower Systems at:
cyberpowersystems.com/support.
PowerPanel® Personal is inactive
(all icons are gray).
The USB cable is not connected.
Connect the USB cable to the UPS
unit and an open USB port on the
back of the computer.
The USB cable is connected to a
bad USB port.
Check for a dierent USB port and
plug the cable in.
The unit is not providing
battery power.
Shutdown your computer and turn
the UPS o. Wait 10 seconds and
turn the UPS back on. This should
reset the unit.
The USB power ports are not
providing power to the connect-
ed devices.
The USB power port has Over Cur-
rent Protection design. When the
total current of connected devices
is over 2.1A, the USB power ports
will stop providing power to the
connected devices.
Turn the UPS o and unplug at
least one piece of device connect-
ed to the USB power port and
then turn the UPS on.
TECHNICAL SPECIFICATIONS
Advanced Energy-Saving Design
The GreenPower UPS™ has a high-eciency charger, which makes it the most energy-ecient UPS in its class. The advanced high-frequency
charging system significantly improves charging eciency and conserves energy. As a result of this advanced design, the GreenPower UPS™
uses less energy compared to competitive models. The GreenPower UPS™ is manufactured in accordance with the Restriction on Hazardous
Substances (RoHS) directive making it one of the most environmentally-friendly UPS systems on the market today.
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
G
REEN
P
OWER
UPS
Energy-Saving Tec hnolo gy
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment o and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment to an outlet on a circuit dierent from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Warning: Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Canadian Compliance Statement
CAN ICES-3 (B)/NMB-3(B)
FCC COMPLIANCE STATEMENT
Please visit www.CyberPowerSystems.com for a copy of the Limited Warranty and Connected Equipment Guarantee.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
CyberPower is the warrantor under this Limited Warranty. For further information please feel free to contact CyberPower at:
Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379;
call us at (877) 297-6937; or submit a web ticket online at cyberpowersystems.com/support.
Cyber Power Systems (USA), Inc. encourages environmentally sound methods for disposal and recycling of its UPS products.
Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state.
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
© 2022 CyberPower Systems (USA), Inc. PowerPanel® Personal is a trademark of Cyber Power Systems(USA) Inc.
All rights reserved. All other trademarks are the property of their respective owners.
6
7 8
5
INPUT Voltage Meter: This meter measures
the AC voltage that the UPS system is re-
ceiving from the utility wall outlet. The UPS
is designed to continuously supply connect-
ed equipment with stable output voltage. In
the event of a complete power loss, severe
planned power suppression, or over-voltage,
the UPS relies on its internal battery to supply
consistent 110/120 output voltage. The INPUT
voltage meter can be used as a diagnostic tool
to identify poor-quality input power.
OUTPUT Voltage Meter: This meter measure,
in real time, the AC voltage that the UPS
system is providing to the computer during
normal AC/Utility Power mode, and battery
backup mode.
ESTIMATED RUNTIME: This displays the run
time estimate of the UPS with the current
battery capacity and load.
NORMAL Icon: This icon appears when the
UPS is working under normal conditions.
BATTERY Icon: During a severe planned pow-
er suppression or power outage, this icon ap-
pears and an alarm sounds (two short beeps
followed by a pause) to indicate the UPS is
operating from its internal batteries. During
a prolonged
planned power
suppression or
power outage,
the alarm will
sound con-
tinuously to
indicate the
UPS’s batter-
ies are nearly out of power. You should save
files and turn o your equipment immediately
or allow the software to shut the system down.
OVER LOAD Icon: This icon appears and an
alarm sounds to indicate the battery-supplied
outlets are overloaded. To clear the overload,
unplug some of your equipment from the bat-
tery-supplied outlets until the icon turns o
and the alarm stops.
BATTERY CAPACITY Meter: This meter
displays the approximate charge level of the
UPS’s internal battery in 20% increments.
During a power outage or severe planned
power suppression, the UPS switches to bat-
tery power (the BATTERY icon appears) and
the battery charge level decreases.
continued
DEFINITIONS FOR ILLUMINATED LED INDICATORS
TO REPLACE THE BATTERY
1. Turn o and unplug all connected equipment.
2. Unplug it from the AC power source.
3. Turn the UPS upside down.
4. Remove the 1 retaining screw.
5. Slide the battery compartment cover completely
o of the unit.
6. Remove the battery from the compartment.
7. Disconnect the battery cables from the battery.
8. Install the replacement battery by connecting the red
wire and black wire to the positive (+) and negative (-)
terminal of the battery.
9. Put the battery back into the compartment.
10. Slide back the battery compartment cover and tighten the retaining screw.
11. Charge the unit for 8 hours to fully charge the battery.
REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly.
Most retailers that sell lead-acid batteries collects used batteries for recycling, as required by
local regulations.
The LCD display indicates a variety of UPS operation-
al conditions. All descriptions apply when the UPS is
plugged into an AC outlet and turned on or when the
UPS is on battery.
Series CP825AVRLCDG CP685AVRLCDG CP600AVR CP685AVR
Model CP825AVRLCDa CP685AVRLCDGa CP800AVRa CP685AVRa
Capacity 825 VA/450 W 685 VA/390 W 800 VA/450 W 685 VA/390 W
Nominal Input Voltage 120 V
Input Frequency 60 Hz ± 3 Hz
On-Battery Output Voltage 120 VAC ± 5%
On-Battery Output Frequency 60 Hz ± 3 Hz
Max. Load for UPS Outlets 825 VA/450 W 685 VA/390 W 800 VA/450 W 685 VA/390 W
Max. Load for Full-time
Surge Protection Outlets 12 Amps
On-Battery Output Wave Form Simulated Sine Wave
Surge Protection 1030 J
Operating Temperature + 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity 0 to 90% non-condensing
DEFINITIONS FOR LED INDICATORS & AUDIBLE ALARMS
POWER WIRING FAULT ALARM
CONDITION
On O O Normal
On O
Beep
twice every
30 seconds
Utility Failure - Battery Mode: The UPS is providing power to
battery power-supplied outlets from its battery.
On O
Rapid
beeping every
1/2 second
Utility Failure - Low Battery: The UPS is providing battery pow-
er. Rapid beeping indicates the unit will run out of power soon.
On/O
Flash once
every 5
seconds
Constant tone
Battery Mode or AC/Utility Power Mode Overload Fault:
Occurs when connected equipment exceeds the rating of
battery outlets of the unit. Please unplug at least one piece
of equipment from battery outlets..
O
Flash twice
every 5
seconds
Constant tone
Battery Output Short Fault: Please unplug at least one
piece of equipment from battery outlets and turn on the
UPS again. If the fault still exists, please contact Cyber-
Power Systems for support.
On
Flash 3
times every
5 seconds
Constant tone Charger Fault: Contact CyberPower Systems for support.
Series CP825AVRLCDG CP685AVRLCDG CP600AVR CP685AVR
Model CP825AVRLCDa CP685AVRLCDGa CP800AVRa CP685AVRa
Size (W x H x D) 11.02” x 6.81” x 3.47” / (100 x 280 x 355 mm)
Net Weight 12.74 lbs. 11.62 lbs. 12.74 lbs. 11.62 lbs.
Typical Battery Recharge Time 8 hours typical from total discharge
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles
Recommended Battery Sealed Maintenance Free Lead Acid Battery
Safety Approvals UL1778(UPS), cUL107, FCC/DoC Class B
SYSTEM FUNCTION BLOCK DIAGRAM
Input Output
Battery Mode
Normal Mode
EMI
Filter
Surge
Suppressor
Inverter
Charger
AC / DC
Battery
AVR


Product specificaties

Merk: CyberPower
Categorie: UPS
Model: CP685AVRG
Kleur van het product: Zwart
Gewicht: 5300 g
Breedte: 11 mm
Diepte: 3.5 mm
Hoogte: 6.8 mm
LED-indicatoren: Ja
Vormfactor: Compact
USB-poort: Ja
Meegeleverde kabels: Stroomingangskabel
Accu/Batterij voltage: 12 V
Geluidsalarm(en): Ja
Responstijd: 4 ms
Duurzaamheidscertificaten: RoHS
Uitgangsvermogen: 390 W
Batterij capaciteit: 7 Ah
Accu/Batterij oplaadtijd: 8 uur
Frequentie: 57/63 Hz
Veiligheid: UL1778, cUL 107.3, FCC DOC Class B
Seriële poort(en): 1
Stekker: NEMA 5-15P
Bedrijfstemperatuur (T-T): 0 - 35 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent
Batterijtechnologie: Sealed Lead Acid (VRLA)
Aantal batterijcellen: 1
Surge energy rating: 1030 J
Aantal AC uitgangen: 8 AC-uitgang(en)
Output power capacity: 0.685 kVA
Ingang operation voltage (min): 90 V
Ingang operation voltage (max): 140 V
Uitgang operation voltage (min): 120 V
Uitgang operation voltage (max): 120 V
UPS-topologie: Line-interactive
Typische backup tijd op halve lading: 11 min
Typische backup tijd op volledige lading: 2 min
Seriële interface: Ja
Output frequentie: 50/60 Hz
Hoorbare alarmstanden: Low battery alarm, Overload alarm
Uitgangsspanningsregeling: 5 procent
Spanningsbeveiliging: Ja
Golfvorm: Sinus
Automatic Voltage Regulation (AVR): Ja
Vervangings-batterij cartridge: RB1270B