CyberPower CP1500EPFCLCD Handleiding
CyberPower
UPS
CP1500EPFCLCD
Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower CP1500EPFCLCD (2 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 19 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/2
EN
CP550/ 13900/ 00/1500EPFCLCD
User’s Manual
K01- -030000460
This manual contains important safety instructions. Please read and follow all instructions carefully during
installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or
operate your UPS.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker
protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to -energize this de
equipment, turn o and unplug the UPS.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does
not sell products for life support or medical applications. use in any circumstance that would aect DO NOT
the operation safety of life support equipment, medical applications, or patient care. and
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is
disconnected.
CAUTION! To prevent the risk of re or electric shock, install in a temperature and humidity controlled indoor
area, free of conductive contaminants. (Please see specications for acceptable temperature and humidity
range).
CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. There
are no user serviceable parts inside, except for the battery.
CAUTION! To avoid electrical shock, turn o the unit and unplug it from the AC power source before
servicing the battery or installing a computer component.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of re, do not use with or near
aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause
the machine to short out.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of re or electric shock, do not
use the unit on any transportation such as airplanes or ships. The eect of shock or vibration caused during
transit and the damp environment can cause the unit to short out.
UNPACKING
The box should contain the following:
(1) UPS Unit 1; (2) USB Cable x User Manual 1; ) Function Setup Guide x 1 ; (5 Power Cord x 1; (3) x (4 )
(Type and quantity may dier from models.)
OVERVIEW
The 1300/1500EPFCLCD provides automatic voltage regulation for inconsistent utility power. CP550/900/
The 900/1300/1500EPFCLCD features Joules of surge protection, and provides battery backup CP550/ 405
during power outages. The 900/1300/1500EPFCLCD s consistent power to your computer CP550/ ensure
system and its included software will automatically save your open les and shut down your computer
system during a utility power loss.
SUPPORTS Active PFC POWER SUPPLIES
This CyberPower UPS system supports High Eciency power supplies with Active Power Factor Correction
(Active PFC). Active PFC is used to improve the eciency of power delivery. The current US Energy Star®
Program Requirements for Computers mandates Active PFC for all power supplies over 100 watts.
Additionally, programs such as 80 Plus® are often used to identify high eciency power supplies with Active
PFC.
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Make sure that the total Volt-Amp (VA) requirements of your computer, monitor, and peripheral
equipment does not exceed t 550VA/he 900VA/ VA/ . 1300 1500VA
2. Ensure that the equipment plugged into the battery power-supplied/surge outlets does not exceed the
UPS unit's rated capacity ( A/350W for CP550EPFCLCD, 550V 900VA/540W for CP900EPFCLCD,
1300 780VA/ W for CP1300EPFCLCD, VA/ W for CP1500EPFCLCD). If the rated unit capacities 1500 900
are exceeded, an overload condition may occur and cause the UPS unit to shut down the circuit or
breaker to trip.
DESCRIPTION
1. Power Switch
Used as the master on/o switch for equipment connected to the battery power supplied outlets.
2. Power On Indicator
This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of
surges and spikes.
3. LCD Module Display
High resolution and intelligent LCD display shows all the UPS information with icons and messages. For
more information, please check the “Definitions for Illuminated LCD Indicators” section.
4. Display Switch
The switch can be used to select the LCD display contents including Input Voltage, Output Voltage and
Estimated Run Time. The toggle frequency is set to one time per 0.5 second. Press the switch to roll
down the function menu. Pressing the switch for 2 seconds will turn the LCD display on or o while in
AC/Utility power mode.
5. Silence Alarm Switch
The toggle frequency is set to one time per 0.5 second. Press the switch to roll up the function menu.
Holding the switch for more than 2 seconds will silence the buzzer.
6. Control Switch
Press the Control switch for 3 seconds in AC/Utility Power Mode to perform a Self Test of the battery.
7. USB Charging Ports
The USB Power ports provide 5V 1A power output. 2.
8. Communication Protection Ports RJ45
Communication protection ports will protect network cable from surge and spikes.
9. USB Port to PC
This port allows connection and communication from the USB port on the computer to the UPS unit. The
UPS communicates its status to the PowerPanel
® Personal Edition software.
10. Serial Port to PC
This port allows connection and communicat from the DB-9 serial on the computer to the UPS unit. es
The UPS communicates its status to the PowerPanel® Personal Edition software.
NOTE: Only one of these two ports can be used as communication and control of the UPS unit at one
time.
11. Battery and Surge Protected Outlets
The unit has several battery powered/surge suppression outlets for connected equipment to ensure
temporary uninterrupted operation of your equipment during a power failure. Check the type and quantity
of outlets for different models in the following table. (DO NOT plug a laser printer, paper shredder,
copier, space heater, vacuum, sump pump or other large electrical devices into the Battery and “
Surge Protected Outlets The power demands of these devices may overload and damage the ”.
unit.)
Model
NEMA
DE
UK
AU
FR
Outlet
Type
Quantity
8
6
2
4
6
6
*CP900EPFCLCD-AU has 3 Battery and Surge Protected Outlets and 3 Surge protected outlets
12. Circuit Breaker
Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection.
13. AC Input
Connect the AC Power cord to a properly wired and grounded outlet.
1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8
hours is recommended to ensure that the battery's maximum charge capacity is achieved. Charge loss
may occur during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC
outlet. The unit will charge in both the on and o position.
Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment.
The rst time you turn the UPS , you will need to have it connected to AC power or it will not power up. on
2. If you will use the software, connect the USB cable to the USB port on the UPS.
3. With the UPS unit o and unplugged, connect the computer, monitor, and any externally powered data
storage device (Zip drive, Jazz drive, Tape drive, etc. )into the battery power supplied outlets. DO NOT
plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the
battery power supplied outlets. The power demands of these devices will overload and possibly damage
the unit.
4. To protect network cable, connect a network cable from the wall jack outlet to the IN jack of the UPS. Then
connect network cable from the OUT jack on the UPS to the mputer or network device. co
5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g.
air conditioner, refrigerator, copier, etc. Avoid using extension cords.
6. Depress the power switch to turn the unit on. The power on indicator light will illuminate and the unit will
"beep".
7. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this,
turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Wait
10 seconds. Make sure the circuit breaker is depressed and then turn the UPS on.
8. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the
battery will automatically recharge.
9. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
10. To store your UPS for an extended period, cover it and store with the battery fully
charged. Recharge the battery every three months to ensure battery life.
11.
CyberPower’s Green Commitment
CyberPower is dedicated to the development of green products, and has adopted
Green practices throughout its business, including: membership in Climate Savers
Computing Initiative (CSCI), accordance with the Restriction on Hazardous
Substances (RoHS), Waste Electrical and Electronic Equipment (WEEE) protocols,
as well as ISO 14001 and IECQ QC080000. CyberPower pledges to provide the
advanced energy solution for the environment and become a leading eco-friendly
organization in the UPS industry.
Reduce Energy Cost with GreenPower UPSTM Technology
CyberPower’s goal is not only to provide eco-friendly products but also to bring the best value for consumers.
The advanced energy-saving design improves the operating efciency and eliminates waste energy
consumption As a result, consumers will enjoy signicant energy cost savings with the adoption of.
GreenPower UPSTM technology.
BASIC OPERATION
INSTALLING YOUR UPS SYSTEM
IMPORTANT SAFETY INSTRUCTIONS
BATTERY REPLACEMENT
HARDWARE INSTALLATION GUIDE
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
CP550/900EPFCLCD
CP1300/1500EPFCLCD
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
Service the battery under the supervision of personnel knowledgeable of batteries and their
precautions.
CAUTION! Use only the specied type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a re, as they
may explode. Follow all local ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and
may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following
precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. lay tools or other metal parts on top of battery or any battery terminals. DO NOT
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground.
CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of
such shock will be reduced if such grounds are removed during installation and maintenance (applicable to a
UPS and a remote battery supply not having a grounded circuit)
BATTERY REPLACEMENT PROCEDURE:
1. Turn o and unplug all connected equipment.
2. Turn the UPS o and unplug it from the AC power source.
3. Turn the UPS on its side.
4. Remove the retaining screw located on the bottom of the UPS.
5. Slide the battery compartment cover completely o of the unit.
6. Remove the batteries from the compartment.
7. Disconnect the battery wires from the batteries.
8. CP FCLCD: Install the replacement batteries by connecting the red wire (+) and black wire (-) to 550/900EP
the same color connectors from the battery pack.
CP1300/1500EPFCLCD: Install the replacement batteries by connecting the wire bundle (composed of one
red wire and one black wire) to the connector from the battery pack.
9. Put the batteries back into the compartment.
10. Slide back the battery compartment cover and tighten the retaining screw.
11. Recharge the UPS for 8- hours to fully charge the battery. 16
REMINDER: Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Almost any ed
retailer that sells lead-acid batteries collects used batteries for recycling.
CP EPFCLCD550/900
CP1300 / 1500EPFCLCD
1. ONLINE: The UPS is supplying utility power to
connected equipment.
2. BATTERY: When a severe brownout or blackout
occurs, this icon appears and an alarm sounds (two
short beeps followed by a pause) to indicate the UPS
is operating from its internal batteries. During a
prolonged brownout or blackout, the alarm will sound
continuously to indicate the UPS’s batteries are
nearly out of power. You should save les and turn off
your equipment immediately or allow the software to
shut the system down.
3. Energy-Saving: The UPS in energy-saving bypass
mode. See “CyberPower GreenPower UPSTM
Technology” section for more information.
4. LOAD capacity / Sensitivity setup: This meter displays the approximate output load level (in 20%
increments) of the UPS battery outlets. It can also be sensitivity setup meter if you are in programming
mode. It is to control the sensitivity of the UPS to switch to Battery Mode by selecting UPS shutdown
voltage range. The higher the sensitivity, the easier the UPS will switch to Battery Mode.
5. BATTERY capacity: This meter displays the approximate charge level (in 20% increments) of the
UPS’s internal battery. During a blackout or severe brownout, the UPS switches to battery power, the
BATTERY icon appears, and the charge level decreases.
6. FAULT: This icon appears if there is a problem with the UPS. Press the POWER button to turn off the
UPS.
F01: Battery Mode or AC/Utility Power Mode Overload fault (Unplug at least one piece of equipment
from battery outlets and turn the UPS on again.)
F02: Battery Output Short fault (Turn on the UPS again.)
F03: Charger Fault (Contact CyberPower Systems for support.)
F04: Internal Fault (Contact CyberPower Systems for support.)
7. OVER LOAD: This icon appears and an alarm sounds to indicate the battery-supplied outlets are
overloaded. To clear the overload, unplug some of your equipment from the battery-supplied outlets
until the icon turns o and the alarm stops.
8. SCHEDULE: Users can setup the schedule to turn on and shut down the computer and UPS through
PowerPanel® Personal Edition software. The LCD display will show how much time that the UPS is
about to turn on or shut down.
9. ESTIMATED RUNTIME: This displays the run time estimate of the UPS with current battery capacity
and load.
10. OUTPUT meter: This meter measure, in real time, the AC voltage that the UPS system is providing to
the computer, such as normal AC line mode, AVR mode, and battery backup mode. (Note: The
OUTPUT meter shows the status of the battery backup outlets in terms of load, frequency, and voltage.)
11. INPUT meter: This meter measures the AC voltage that the UPS system is receiving from the utility
wall outlet. The UPS is designed, through the use of automatic voltage regulation, to continuously
supply connected equipment with stable, 0 output voltage. In the event of a complete power loss, 220/23
severe brownout, or over-voltage, the UPS relies on its internal battery to supply consistent 220/230
output voltage. The INPUT meter can be used as a diagnostic tool to identify poor-quality input power.
12. EVENT: This meter records the number of power outages.
13. MUTE: This icon appears whenever the UPS is in silent mode. The buzzer does not beep during silent
mode until the battery reaches low capacity.
14. AVR (Automatic Voltage Regulation): This icon appears whenever your UPS is automatically
correcting low AC line voltage without using battery power. This is a normal, automatic operation of your
UPS, and no action is required on your part.
For more information about functions setup, please refer to the Function Setup Guide.
Model
CP550EPFCLCD
CP900EPFCLCD
CP1300EPFCLCD
CP1500EPFCLCD
Capacity
550VA/350W
900VA/ 540W
1300VA/ 780W
1500VA/ 900W
Input
Frequency Range
50/60Hz +/- 3 Hz (Auto Sensing)
AVR Function
Yes
Output
On Battery Output
Voltage
230Vac +/- % 10
On Battery Output
Frequency
50/60Hz -1% +/
Overload Protection
On Utility: Circuit Breaker, On Battery: Internal Current Limiting
Surge Protection
Lightning / Surge
Protection
Yes
Network Protection
RJ45
Operating
Temperature
0 C to C 40
Physical
Maximum
Dimensions(LxWxH)
275 x 100 x 230 mm
370 x 100 265 mm x
Weight (kg)
6.6 kg
7.1 kg
10.4 kg
11.3 kg
Battery
Battery
Sealed Maintenance Free Lead Acid Battery
Typical Recharge
Time
8 hours
Charging
Current(Max.)
0.6A
User Replaceable
Yes
Status Indicators
Indicators
Power On, LCD Display
Audible Alarms
On Battery, Low Battery, Overload
Communication
PowerPanel®Personal
Edition Software
Windows 10 / 8 / 7 / Vista / XP / 2000, Server2012 / 2008 / 2003, Linux
Management
Auto-Charger
Yes
Auto-Restart
Yes
USB interface
Yes
Certications
Certications
CE, EAC, RCM
Problem
Possible Cause
Solution
Circuit breaker button is
projecting from the back of
the unit.
Circuit breaker has tripped
due to an overload.
Turn the UPS o and unplug at least one
piece of equipment. Wait 10 seconds, reset
the circuit breaker by depressing the button,
and then turn the UPS on.
The UPS does not perform
expected runtime.
Battery not fully charged.
Recharge the battery by leaving the UPS
plugged in.
Battery is slightly worn out.
Contact CyberPower Systems about
replacement batteries.
The UPS will not turn on.
The on/off switch is designed
to prevent damage by rapidly
turning it off and on.
Turn the UPS o. Wait 10 seconds and
then turn the UPS on.
The battery is worn out.
Contact CyberPower Systems about
replacement batteries.
Mechanical problem.
Contact CyberPower Systems.
PowerPanel® Personal
Edition is inactive.
The USB cable is not
connected.
Connect the USB / serial cable to the UPS
unit and an open USB / serial port on the
back of the computer. You must use the
cable that came with the unit.
The unit is not providing
battery power.
Shutdown your computer and turn the
UPS o. Wait 10 seconds and turn the
UPS back on. This should reset the unit.
Additional troubleshooting information can be found at www.cyberpower.com
For more information, visit www.cyberpower.com
Manufacturer: Cyber Power Systems Inc.
11F., No.26, Jinzhuang Rd., Neihu Dist., Taipei City 114, Taiwan
All rights reserved. Reproduction without permission is prohibited.
TECHNICAL SPECIFICATIONS
TROUBLESHOOTING
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
Product specificaties
Merk: | CyberPower |
Categorie: | UPS |
Model: | CP1500EPFCLCD |
Kleur van het product: | Zwart |
Gewicht: | 10900 g |
Breedte: | 100 mm |
Diepte: | 370 mm |
Hoogte: | 265 mm |
Snoerlengte: | 1.83 m |
Gewicht verpakking: | 13000 g |
Breedte verpakking: | 195 mm |
Diepte verpakking: | 466 mm |
Hoogte verpakking: | 370 mm |
Materiaal behuizing: | Kunststof |
LED-indicatoren: | Batterijvervanging |
Vormfactor: | Tower |
USB-poort: | Ja |
Meegeleverde kabels: | Input power cable, Phone (RJ-11), USB cable |
Aantal USB 2.0-poorten: | 2 |
Soort serieële aansluiting: | RS-232 |
Ondersteund aantal accu's/batterijen: | 1 |
Certificering: | CE, EAC, RCM |
RS-232 port: | 1 |
Geluidsalarm(en): | Ja |
Responstijd: | 4 ms |
Duurzaamheidscertificaten: | RoHS |
Uitgangsvermogen: | 900 W |
Accu/Batterij oplaadtijd: | 8 uur |
Temperatuur bij opslag: | -15 - 45 °C |
Frequentie: | 50/60 Hz |
Compatibele besturingssystemen: | Windows 7/Vista/XP/2000/ME/98, Windows Server\n2003/2008, Mac OS, Linux |
Luchtvochtigheid bij opslag: | 0 - 95 procent |
Mac-compatibiliteit: | Ja |
Hoogte, in bedrijf: | 0 - 3000 m |
Hoogte bij opslag: | 0 - 1500 m |
Seriële poort(en): | 1 |
Modem (RJ-11) poort: | 1 |
Stekker: | C14 stekker |
Bedrijfstemperatuur (T-T): | 0 - 40 °C |
Relatieve vochtigheid in bedrijf (V-V): | 0 - 95 procent |
Batterijtechnologie: | Sealed Lead Acid (VRLA) |
Type beeldscherm: | LCD |
Code geharmoniseerd systeem (HS): | 85078000 |
Surge energy rating: | 405 J |
Aantal AC uitgangen: | 6 AC-uitgang(en) |
Stopcontacttypes: | Type F |
Golf protectie functies: | Network, Telephone |
Output power capacity: | 1.5 kVA |
Ingang operation voltage (min): | 170 V |
Ingang operation voltage (max): | 270 V |
Uitgang operation voltage (min): | 230 V |
Uitgang operation voltage (max): | 230 V |
UPS-topologie: | Line-interactive |
Aantal input fases: | 1 |
Typische backup tijd op halve lading: | 11 min |
Typische backup tijd op volledige lading: | 3 min |
Seriële interface: | Ja |
Output frequentie: | 50/60 Hz |
Hoorbare alarmstanden: | Batterijvervanging |
Uitgangsspanningsregeling: | 10 procent |
Aantal output fases: | 1 |
EMI/RFI geluidsfiltering: | Ja |
Spanningsbeveiliging: | Ja |
Golfvorm: | Zuivere sinus |
Vervangings-batterij cartridge: | RBP0016 |
USB-poorttype: | USB Type-A |
Aantal type F-uitgangen: | 6 |
Heb je hulp nodig?
Als je hulp nodig hebt met CyberPower CP1500EPFCLCD stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS CyberPower
15 November 2024
7 November 2024
7 November 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
24 September 2024
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Tripp Lite
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
18 November 2024
17 November 2024
17 November 2024
17 November 2024
16 November 2024
15 November 2024
14 November 2024
14 November 2024
12 November 2024
22 Oktober 2024