Safety and
superior
sound quality
VOICE ALARM SYSTEM
VX-3000
2TOA Voice alarm system
We are experts in combining safety and sound. From pro-
fessional sound reproduction to complex site supervision,
TOA voice alarm systems offer built-in versatility and reliabil-
ity. Our systems are extremely flexible, easy to expand and,
in addition to their permanent monitoring function, also offer
outstanding audio quality.
In order to achieve maximum safety, it is not only necessary
to configure systems optimally, but also to consider com-
plementary topics such as acoustics or security concepts.
Whether in our training center in Hamburg or in your rooms
we offer a successful combination of know ledge and prac-
tice in voice evacuation and acoustics. We regularly hold
seminars and workshops for the entire spectrum of sound
technology.
But not enough – our services for you
also include:
β€’ Provision of technical documenta-
tion (drawings, manuals, specifica-
tions, etc.)
β€’ Planning support
β€’ Acoustic simulation and consulting
β€’ Project-related product configuration
β€’ Support during installation and com-
missioning
β€’ Repairs and technical customer ser
vice
3
TOA Voice alarm system
VX-3000 Series
Combined highly integrated voice alarm, public
address and BGM system.
Safety is an important issue more than ever.
Our VX-3000 is a reliable and energy-saving voice alarm sys-
tem certified on the European Standard EN54-16. It combines
a lot of functions for PA/VA/BGM applicatons in one single unit
frame. The reduction in the number of components required
allows for a non-complex design and a much quicker and eas-
ier installation together with space saving and a reduction in
cable runs and complexity. This enables rapid system configu-
ration and makes the VX-3000 a cost-effective system.
It includes low loss modular class D amplifiers with 3 differ-
ent output ratings. These can easily be removed or mount-
ed simply by unplugging them so there is no need for special
tools. By using low loss modular class D amplifiers and mod-
ern power supply switching technology, the system becomes
much more energy efficient and enables low operating costs.
Due to its flexible and scalable system architecture, the
VX-3000 system can be used for both small and large ap-
plications, with up to 1280 remote microphones, 640 audio
sources and 2560 speaker lines. The system can be installed
centralised as well as de-centralised, latter can reduce the
cabling cost drastically. Different Ethernet switches provide a
redundant network and a maximum distance between parts
of the VA system of 30 km.
The automatic emergency announcements (pre-recorded
messages) can be arranged in three phases, for example
broadcasting a coded message first, then a warning and at
the end an evacuation message. A simultaneous broadcast
of warning and evacuation messages is also possible and can
be initiated by a single activation. Since version 5 the system
allows the setting of a sequential evacuation which is required
sometimes in a big building complex.
The two remote microphone models can be set for normal,
emergency and both modes with a different setting for the talk
button (implemented zone selection or not, PPT or lock mode).
In emergency mode, emergency messages can manually be
assigned to broadcast areas. Built-in chimes or individually re-
corded chimes or tones can be set before and after paging,
and different tones for normal and emergency broadcasts.
The input and output channels provide comprehensive DSP
settings, please refer to the frame descriptions.
Different access levels (since version 5) restrict the access to
the setting software according to the operator’s education
level. So the advanced user level allows the end user the set-
ting of the built-in timer (since version 5) and changing audio
files for general broadcasts, such as pause chimes in schools
and factories, or general or advertisement announcements in
shopping areas.
Also, the VX-3000 system passed the test on EN 50121-4 suc-
cessfully. This standard covers the high EMC requirements for
installations in railway stations. Please contact TOA Electron-
ics Europe for further information.
Maximum System Capacity
Output Power 320,000 W
Speaker Zones 2560
Remote Mics 1280


Product specificaties

Merk: Toa
Categorie: Receiver
Model: VX-015DA
Kleur van het product: Zwart
Gewicht: 1400 g
Breedte: 79 mm
Diepte: 91 mm
Hoogte: 358.2 mm
Connectiviteitstechnologie: Bedraad
Stroomverbruik (in standby): 1.3 W
DC voltage input: 31 V
Aansluiting voor netstroomadapter: Ja
Materiaal: Staal
Bedoeld voor: Optreden/podium
Audio-uitgangskanalen: 1.0 kanalen
Frequentiebereik: 40 - 16000 Hz
Signaal/ruis-verhouding: 100 dB
Totale harmonische vervorming (THD): 1 procent
Stroomverbruik (typisch): 150 W
Piekvermogen per kanaal: 40 W
Versterker klasse: D