Supermicro SuperServer 2028R-C1R Handleiding

Supermicro Server SuperServer 2028R-C1R

Lees hieronder de 📖 handleiding in het Nederlandse voor Supermicro SuperServer 2028R-C1R (146 pagina's) in de categorie Server. Deze handleiding was nuttig voor 26 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/146
S Super erver®
2028r-C1rT
2028r-C1r
uSer’S MANuAL
Revision 1.0b
The information in this User’s Manual has been carefully reviewed and is believed to be accurate.
The vendor assumes no responsibility for any inaccuracies that may be contained in this document,
makes no commitment to update or to keep current the information in this manual, or to notify any
person or organization of the updates. Please Note: For the most up-to-date version of this
manual, please see our web site at www.supermicro.com.
Super Micro Computer, Inc. ("Supermicro") reserves the right to make changes to the product
described in this manual at any time and without notice. This product, including software and
documentation, is the property of Supermicro and/or its licensors, and is supplied only under a
license. Any use or reproduction of this product is not allowed, except as expressly permitted by
the terms of said license.
IN NO EVENT WILL SUPERMICRO BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL,
SPECULATIVE OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OR INABILITY TO
USE THIS PRODUCT OR DOCUMENTATION, EVEN IF ADVISED OF THE POSSIBILITY OF
SUCH DAMAGES. IN PARTICULAR, SUPERMICRO SHALL NOT HAVE LIABILITY FOR ANY
HARDWARE, SOFTWARE, OR DATA STORED OR USED WITH THE PRODUCT, INCLUDING THE
COSTS OF REPAIRING, REPLACING, INTEGRATING, INSTALLING OR RECOVERING SUCH
HARDWARE, SOFTWARE, OR DATA.
Any disputes arising between manufacturer and customer shall be governed by the laws of Santa
Clara County in the State of California, USA. The State of California, County of Santa Clara shall
be the exclusive venue for the resolution of any such disputes. Super Micro's total liability for all
claims will not exceed the price paid for the hardware product.
FCC Statement: This equipment has been tested and found to comply with the limits for a Class
A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the manufacturer’s instruction manual, may cause harmful
interference with radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference, in which case you will be required to correct the interference at your
own expense.
California Best Management Practices Regulations for Perchlorate Materials: This Perchlorate
warning applies only to products containing CR (Manganese Dioxide) Lithium coin cells. “Perchlorate
Material-special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate”
WARNING: Handling of lead solder materials used in this
product may expose you to lead, a chemical known to
the State of California to cause birth defects and other
reproductive harm.
Manual Revision 1.0b
Release Date: December 22, 2017
Unless you request and receive written permission from Super Micro Computer, Inc., you may not
copy any part of this document.
Information in this document is subject to change without notice. Other products and companies
referred to herein are trademarks or registered trademarks of their respective companies or mark
holders.
Copyright © 2017 by Super Micro Computer, Inc.
All rights reserved.
Printed in the United States of America
iii
Preface
Preface
About This Manual
This manual is written for professional system integrators and PC technicians. It
provides information for the installation and use of the SuperServers 2028R-C1RT
and 2028R-C1R. Installation and maintainance should be performed by experienced
technicians only.
iv
SuperServer 2028R-C1R(T) User's Manual
Contents
Chapter 1 Introduction ..............................................................................1-1
1-1 Overview ......................................................................................................... 1-1
1-2 Serverboard Features ..................................................................................... 1-1
Processor 1-2 ........................................................................................................
Memory 1-2 ...........................................................................................................
SAS 1-2 ................................................................................................................
SATA .............................................................................................................. 1-2
PCI Expansion Slots ....................................................................................... 1-2
Rear I/O Ports ................................................................................................. 1-3
Other Features ................................................................................................ 1-4
1-3 Chassis Features ............................................................................................ 1-4
Drives 1-4 ..............................................................................................................
System Power ................................................................................................. 1-4
Front Control Panel ......................................................................................... 1-4
Cooling System ............................................................................................... 1-4
Mounting Rails ................................................................................................ 1-4
1-4 Contacting Supermicro .................................................................................... 1-5
1-5 Returning Merchandise for Service................................................................. 1-6
Chapter 2 Server Installation ...................................................................2-1
2-1 Unpacking the System .................................................................................... 2-1
2-2 Preparing for Setup ......................................................................................... 2-1
Choosing a Setup Location ............................................................................. 2-1
2-3 Warnings and Precautions .............................................................................. 2-2
Rack Precautions ............................................................................................ 2-2
Server Precautions .......................................................................................... 2-2
Rack Mounting Considerations ....................................................................... 2-3
Ambient Operating Temperature ................................................................ 2-3
Reduced Airow ......................................................................................... 2-3
Mechanical Loading ................................................................................... 2-3
Circuit Overloading ..................................................................................... 2-3
Reliable Ground ......................................................................................... 2-3
2-4 Checking the Setup ......................................................................................... 2-4
Completing the Conguration ......................................................................... 2-5
2-5 Installing the System into a Rack ................................................................... 2-6
Identifying the Sections of the Rack Rails ...................................................... 2-6
Releasing the Inner Rail ................................................................................. 2-7
v
Preface
Installing the Inner Rails on the Chassis ........................................................ 2-8
Installing the Outer Rails onto the Rack ......................................................... 2-9
Sliding the Chassis onto the Rack Rails ....................................................... 2-10
Chapter 3 System Interface ......................................................................3-1
3-1 Overview ......................................................................................................... 3-1
3-2 Control Panel Buttons ..................................................................................... 3-2
3-3 Control Panel LEDs ........................................................................................ 3-2
Overheating 3-3 .....................................................................................................
Overheat Temperature Setting ................................................................... 3-3
Responses 3-3 ..................................................................................................
3-4 Drive Carrier LEDs .......................................................................................... 3-4
3-5 Power Supply LEDs ........................................................................................ 3-4
Chapter 4 Standardized Warning Statements for AC Systems ............4-1
About Standardized Warning Statements ....................................................... 4-1
Warning Denition ........................................................................................... 4-1
Installation Instructions .................................................................................... 4-4
Circuit Breaker ................................................................................................ 4-5
Power Disconnection Warning ........................................................................ 4-6
Equipment Installation ..................................................................................... 4-8
Restricted Area ................................................................................................ 4-9
Battery Handling ............................................................................................ 4-10
Redundant Power Supplies .......................................................................... 4-12
Backplane Voltage ........................................................................................ 4-13
Comply with Local and National Electrical Codes ........................................ 4-14
Product Disposal ........................................................................................... 4-15
Hot Swap Fan Warning ................................................................................. 4-16
Power Cable and AC Adapter ...................................................................... 4-18
Chapter 5 Advanced Serverboard Setup ................................................5-1
5-1 Handling the Serverboard ............................................................................... 5-1
Precautions 5-1 .....................................................................................................
Unpacking 5-1 .......................................................................................................
5-2 Installing the Processor and Heatsink ............................................................ 5-2
Installing an LGA 2011 Processor ................................................................... 5-2
Installing a CPU Heatsink ............................................................................... 5-5
Removing the Heatsink .................................................................................. 5-5
5-3 Connecting Cables .......................................................................................... 5-6
Connecting Data Cables ................................................................................. 5-6
Connecting Power Cables .............................................................................. 5-6
Connecting the Control Panel ......................................................................... 5-6
vi
SuperServer 2028R-C1R(T) User's Manual
5-4 I/O Ports .......................................................................................................... 5-7
LAN Ports ........................................................................................................ 5-7
5-5 Installing Memory ............................................................................................ 5-8
Memory Support .............................................................................................. 5-9
Processor & Memory Module Population Conguration ............................ 5-9
5-6 Serverboard Details .......................................................................................5-11
Serverboard Quick Reference....................................................................... 5-12
5-7 Connector Denitions .................................................................................... 5-14
Front Control Panel ....................................................................................... 5-15
Input/Output Connectors ............................................................................... 5-17
Other Connectors .......................................................................................... 5-18
5-8 Jumper Settings ............................................................................................ 5-21
5-9 Onboard Indicators ........................................................................................ 5-23
5-10 SATA/SAS Connections ................................................................................ 5-25
5-11 Installing Software ......................................................................................... 5-26
SuperDoctor® 5 ............................................................................................. 5-27
5-12 Onboard Battery ............................................................................................ 5-29
Chapter 6 Advanced Chassis Setup ........................................................6-1
6-1 Static-Sensitive Devices .................................................................................. 6-2
Precautions 6-2 .....................................................................................................
Unpacking 6-2 .......................................................................................................
6-2 Hard Disk Drives ............................................................................................ 6-2
6-3 Peripheral Drive Installation ............................................................................ 6-5
6-4 Installing Expansion Cards ............................................................................ 6-6
6-5 Installing the Air Shroud .................................................................................. 6-7
Checking the Air Flow ..................................................................................... 6-7
6-6 System Fans ................................................................................................... 6-8
6-7 Installing the Serverboard ............................................................................. 6-10
I/O Shield ...................................................................................................... 6-10
Installing the I/O Shield ................................................................................. 6-10
Permanent and Optional Standoffs ................................................................6-11
6-8 Power Supply ................................................................................................ 6-12
Chapter 7 BIOS .........................................................................................7-1
7-1 Introduction ...................................................................................................... 7-1
Starting BIOS Setup Utility .............................................................................. 7-1
How To Change the Conguration Data ......................................................... 7-1
How to Start the Setup Utility ......................................................................... 7-2
7-2 Main Setup ...................................................................................................... 7-2
vii
Preface
7-3 Advanced Setup Congurations...................................................................... 7-4
7-4 Event Logs .................................................................................................... 7-39
7-5 IPMI ............................................................................................................... 7-41
7-6 Security Settings ........................................................................................... 7-43
7-7 Boot Settings ................................................................................................. 7-44
7-8 Save & Exit ................................................................................................... 7-46
Appendix A BIOS Error Beep Codes ..................................................... A-1
Appendix B System Specications ........................................................ B-1
viii
SuperServer 2028R-C1R(T) User's Manual
Notes
Chapter 1
Introduction
1-1 Overview
The 2028R-C1R(T) is a high-end server comprised of two main subsystems: the
SC213AC-R920LPB 2U server chassis and the X10DRH-C or X10DRH-CT dual
processor serverboard. The 2028R-C1R features four Gigabit LAN ports, and the
2028R-C1RT has four 10GBaseT LAN ports. Refer to the Supermicro web site for
information on operating systems that have been certied for use with the system
(www.supermicro.com).
In addition to the serverboard and chassis, various hardware components have
been included with the 2028R-C1R(T), as listed below:
Backplane (BPN-SAS3-213A)
Cooling: three fans (FAN-0126L4), one air shroud (MCP-310-29001-0N), two
heat sinks (SNK-P0048PS)
Mounting rails (MCP-290-00053-0N)
Note: For your system to work properly, please follow the links below to download
all necessary drivers/utilities and the user’s manual for your server.
Product manuals: http://www.supermicro.com/support/manuals/
Product drivers and utilities: ftp://ftp.supermicro.com
Product safety information:
http://www.supermicro.com/about/policies/safety_information.cfm
For support, email support@supermicro.com.
1-2 Serverboard Features
The SuperServer 2028R-C1R(T) is built around the X10DRH-C(T), a dual processor
serverboard based upon the Intel C612 Express chipset. Below are the main
features. Curent details are available on the Supermicro web site.
Chapter 1: Introduction
1-1
1-2
SuperServer 2028R-C1R(T) User's Manual
Processor
Each serverboard supports single or dual Intel Xeon E5-2600 v3/v4 processors in
Socket R3-LGA 2011. A complete listing of supported processors is available on
the Supermicro web site.
Memory
Each serverboard has 16 DIMM slots that can support up to 2 TB of Load
Reduced (LRDIMM) ECC registered memory or up to 512 GB of registered
(RDIMM) ECC modules. Memory type is 2400/2133/1866/1600 MHz DDR4. 72-
bit. DIMM sizes supported are RDIMM: 32 GB, 16 GB, 8 GB, 4 GB; LRDIMM: 64
GB, 32 GB. Refer to Section 5-6 before installing memory and the Supermicro
web site for recommended DIMMs.
SAS
An LSI 3108 SAS controller is included on the serverboard to support up to eight
SAS 3.0 ports with RAID 0, 1, 5, 6, 10, 50 and 60.
The SAS drives are hot-swappable if you set up RAID. Refer to RAID guidelines
on the Supermicro website.
SATA
A SATA controller is integrated into the C612 chipset to provide ten SATA 3.0 ports,
with RAID 0, 1, 5 and 10.
The SATA drives are hot-swappable if you set up RAID. Refer to RAID guidelines
on the Supermicro website.
PCI Expansion Slots
The serverboard has a total of seven PCI-E 3.0 slots: six x8 slots and one x16
slot. Note that both CPUs must be installed to make use of all the PCI slots. CPU1
controls Slot1-Slot3; CPU2 controls Slot4-Slot7.
Input/Output Ports
The I/O ports include two COM ports (one front, one rear), a VGA port, two USB 3.0
ports (rear), two USB 2.0 ports (rear), two more USB 2.0 ports (front), two Ethernet
LAN ports and a dedicated IPMI LAN port
X10DRH-C has two Gigabit LAN ports
X10DRH-CT has two 10GBaseT LAN ports
1-3
Chapter 1: Introduction
Figure 1-1. Intel C612 Express Chipset:
System Block Diagram
Note: This is a general block diagram and may not exactly represent
the features on your motherboard. See the previous pages for the
actual specications of your motherboard.
SPI
L 3 AN
RGRMII
Debug Card
FRONT PANEL
SYSTEM POWER
CTRL
FAN SPEED
PCI-E X1 G2
USB 2.0
PCH 612
6.0 Gb/S
USB 2.0
LPC
#1
#0
#5
#4
R E-VB-CGTL8211
#3
#2
R 5J4
BIOS
SPI
SPI
Temp Sensor
EMC1402-1 *2 at diff SMBUS
TPM HE ERAD
USB 3.0
BIOS
HE ERAD
SPI
AST 0240
BMC
RMII/NCSI
COM1
C toronnec
COM2
H derea
VGA CONN
BMC B t Fl hoo as
DDR3
5 PHASE
145W
P1
P1
P0
VR12.5
P0
QPI
9.6G
2 x PCI-E X8 G3 (LAN REVERSE)
2IMD2IMD
CPU1 CPU2
QPI
9.6G
5 PHASE
145W
VR12.5
X /I 0540 35
LAN1,2
PCI-E X8 G2
SLOT 4
SLOT 5
PCI-E X16
PCI-E X8
SLOT 6
PCI-E X8
PCI-E X8 G3
2 x PCI-E X8 G3
PCI-E X16 G3
#1 #2 #3#1 #3
#1-8 #2-8
#6
#7
#8#9
VCCP1 12v
PVCCIO
(1.05/0.95)
from 3.3v
PCI-E X8
SLOT 7
LSI
3108
PCI-E X8 G3
PCI-E X8
#2
SLOT 1
PCI-E X8
SLOT 2
PCI-E X8
SLOT 3
PCI-E X8 G3 (LAN REVERSE)
USB 0/1, 2/3
USB 4/5, 6, 7/8
I-SATA 0,1,2,3
S-SATA 7,8,9,10
SATADOM 5,6
#1-7
#1-6
#1-5
#1-4
#1-3
#1-2
1333/2133
DDR4
#1-1
#2-7
#2-6
#2-5
#2-4
#2-3
#2-2
1333/2133
#2-1
DDR4
SATAUSB2USB3
Other Features
Other onboard features that promote system health include voltage monitors, a
chassis intrusion header, Watch Dog, auto-switching voltage regulators, chassis
and CPU overheat sensors and hardware BIOS virus protection.
1-4
SuperServer 2028R-C1R(T) User's Manual
1-3 Chassis Features
The following is a general outline of the main features of the SC213AC-R920LPB
server chassis.
Drives
The SC213 chassis includes sixteen 2.5" hard drive bays. It can accomodate
eight SAS3 12Gbps drives and eight SATA3 6Gbps drives. The drives can be hot-
swappable if supported by the operating system and RAID. Hard drives must be
purchased separately. The drives are enabled through a backplane.
A DVD drive is optional.
System Power
The system includes two redundant hot-plug, high-efciency power supplies, each
rated at 920 Watts.
Front Control Panel
The control panel on the front of the chassis displays LEDs to indicate system
power, HDD activity, network activity, system overheat and power supply failure. A
main power button and a system reset button are also included.
Cooling System
The system supports three fans powered from the motherboard. These fans are 2U
high and are powered by 4-pin connectors. It also includes heats sinks for each CPU
and a mylar air shroud that directs the airow where cooling is needed.
Mounting Rails
The system includes a set of quick-release rails for mounting in a rack.
1-5
Chapter 1: Introduction
1-4 Contacting Supermicro
Headquarters
Address: Super Micro Computer, Inc.
980 Rock Ave.
San Jose, CA 95131 U.S.A.
Tel: +1 (408) 503-8000
Fax: +1 (408) 503-8008
Email: marketing@supermicro.com (General Information)
support@supermicro.com (Technical Support)
Website: www.supermicro.com
Europe
Address: Super Micro Computer B.V.
Het Sterrenbeeld 28, 5215 ML
's-Hertogenbosch, The Netherlands
Tel: +31 (0) 73-6400390
Fax: +31 (0) 73-6416525
Email: sales@supermicro.nl (General Information)
support@supermicro.nl (Technical Support)
rma@supermicro.nl (Customer Support)
Website: www.supermicro.nl
Asia-Pacic
Address: Super Micro Computer, Inc.
3F, No. 150, Jian 1st Rd.
Zhonghe Dist., New Taipei City 235
Taiwan (R.O.C)
Tel: +886-(2) 8226-3990
Fax: +886-(2) 8226-3992
Email: support@supermicro.com.tw
Website: www.supermicro.com.tw
1-6
SuperServer 2028R-C1R(T) User's Manual
1-5 Returning Merchandise for Service
A receipt or copy of your invoice marked with the date of purchase is required before
any warranty service will be rendered. You can obtain service by calling your vendor
for a Returned Merchandise Authorization (RMA) number. When returning to the
manufacturer, the RMA number should be prominently displayed on the outside of
the shipping carton, and mailed prepaid or hand-carried. Shipping and handling
charges will be applied for all orders that must be mailed when service is complete.
For faster service, RMA authorizations may be requested online (http://www.
supermicro.com/support/rma/).
Whenever possible, repack the chassis in the original Supermicro carton, using the
original packaging material. If these are no longer available, be sure to pack the
chassis securely, using packaging material to surround the chassis so that it does
not shift within the carton and become damaged during shipping.
This warranty only covers normal consumer use and does not cover damages
incurred in shipping or from failure due to the alteration, misuse, abuse or improper
maintenance of products.
During the warranty period, contact your distributor rst for any product problems.
Chapter 2: Server Installation
2-1
Chapter 2
Server Installation
This chapter outlines the procedure to install your system into a rack. If your system
is not already fully integrated with a drives, processors, or system memory refer to
the relevant chapter for details on installing components.
2-1 Unpacking the System
You should inspect the box in which your server was shipped and note if it was
damaged. If the server itself shows damage, le a claim with the carrier.
2-2 Preparing for Setup
Decide on a suitable location for the rack unit that will hold the server. It should be
in a clean, dust-free area that is well ventilated. Avoid areas where heat, electrical
noise and electromagnetic elds are generated. It must be near a grounded power
outlet.
The box in which the server was shipped includes two sets of rail assemblies, two
rail mounting brackets and mounting screws to install the system into the rack. The
installation procedure is provided later in this chapter. Please read this section and
"Warnings and Precautions" section before beginning the installation procedure.
Choosing a Setup Location
Leave enough clearance in front of the rack to enable you to open the front
door completely (~25 inches) and approximately 30 inches of clearance in the
back of the rack to allow for sufcient airow and ease in servicing.
This product is for installation only in a Restricted Access Location (dedicated
equipment rooms, service closets and the like).
This product is not suitable for use with visual display work place devices
acccording to §2 of the the German Ordinance for Work with Visual Display
Units.
2-2
SuperServer 2028R-C1R(T) User's Manual
2-3 Warnings and Precautions
Rack Precautions
Ensure that the leveling jacks on the bottom of the rack are fully extended to
the oor with the full weight of the rack resting on them.
In single rack installation, stabilizers should be attached to the rack. In mul-
tiple rack installations, the racks should be coupled together.
Always make sure the rack is stable before extending a component from the
rack.
You should extend only one component at a time. Extending two or more
simultaneously may cause the rack to become unstable.
Server Precautions
Review the electrical and general safety precautions in Chapter 4.
Determine the placement of each component in the rack you install the before
rails.
Install the heaviest server components on the bottom of the rack rst, and
then work up.
Use a regulating uninterruptible power supply (UPS) to protect the server from
power surges, voltage spikes and to keep your system operating in case of a
power failure.
Allow any hot plug drives and power supply modules to cool before touching
them.
Always keep the rack front door and all panels and components on the serv-
ers closed when not servicing to maintain proper cooling.
Chapter 2: Server Installation
2-3
Rack Mounting Considerations
Ambient Operating Temperature
If installed in a closed or multi-unit rack assembly, the ambient operating tempera-
ture of the rack environment may be greater than the ambient temperature of the
room. Therefore, consideration should be given to installing the equipment in an
environment compatible with the manufacturers maximum rated ambient tempera-
ture (Tmra).
Reduced Airow
Equipment should be mounted into a rack so that the amount of airow required
for safe operation is not compromised.
Mechanical Loading
Equipment should be mounted into a rack so that a hazardous condition does not
arise due to uneven mechanical loading.
Circuit Overloading
Consideration should be given to the connection of the equipment to the power
supply circuitry and the effect that any possible overloading of circuits might have
on overcurrent protection and power supply wiring. Appropriate consideration of
equipment nameplate ratings should be used when addressing this concern.
Reliable Ground
A reliable ground must be maintained at all times. To ensure this, the rack itself
should be grounded. Particular attention should be given to power supply connec-
tions other than the direct connections to the branch circuit (i.e. the use of power
strips, etc.).
Warning! To prevent bodily injury when mounting or servicing this unit in a
rack, you must take special precautions to ensure that the system remains
stable. The following guidelines are provided to ensure your safety:
This unit should be mounted at the bottom of the rack if it is the only unit in
the rack.
When mounting this unit in a partially lled rack, load the rack from the bot-
tom to the top with the heaviest component at the bottom of the rack.
If the rack is provided with stabilizing devices, install the stabilizers before
mounting or servicing the unit in the rack.
Slide rail mounted equipment is not to be used as a shelf or a work space.
2-4
SuperServer 2028R-C1R(T) User's Manual
Figure 2-1. Removing the Chassis Cover
2-4 Checking the Setup
Open the unit to make sure the motherboard is properly installed and all the con-
nections have been made.
Removing the Chassis Cover
1. Remove the two screws on each side of the cover, which secure the cover to
the chassis.
2. Press the release tabs to remove the cover from the locked position. Press both
tabs at the same time.
3. Once the top cover is released from the locked position, slide the cover toward
the rear of the chassis and up.
4. Before operating the server for the rst time, it is important to remove the
protective lm covering the top of the chassis, to allow for proper ventilation
and cooling.
Remove
Screw
Remove
Screw
1
2
1
1
1
1
1
2
1
3
Caution: Except for short periods of time, do not operate the server without the
cover in place. The chassis cover must be in place to allow proper airow and
prevent overheating.Lift the cover off the chassis.
Chapter 2: Server Installation
2-5
Completing the Conguration
Your server may or may not come with hard disk drives, processors or system
memory already installed. The following sections refer you to the procedures for
installing these components.
Checking the Components and Setup
To install processors and heatsinks into the motherboard, see Chapter 5 for
the procedure.
To install system memory DIMMs, refer to Chapter 5.
To install hard disk drives or optional peripheral drives, see the procedures in
Chapter 6.
To install expansion cards to the system, see Chapter 6.
Checking the Airow
Airow is provided by three 8-cm chassis cooling fans. The system compo-
nent layout was carefully designed to direct sufcient cooling airow to the
components that generate the most heat.
To install the air shroud that assists with air ow, see Chapter 6.
Make sure all power and data cables are properly connected and not blocking
the chassis airow. Also make sure that no cables are positioned in front of
the fans.
Providing Power
After installing or checking components and mounting your server in its rack, con-
nect the power.
1. Plug the power cords from the power supply units into a high-quality power strip
that offers protection from electrical noise and power surges. It is recommended
that you use an uninterruptible power supply (UPS).
2. Depress the power button on the front of the chassis.
2-6
SuperServer 2028R-C1R(T) User's Manual
2-5 Installing the System into a Rack
This section provides information on installing the chassis into a rack unit with the
rails provided. There are a variety of rack units on the market, which may mean
that the assembly procedure will differ slightly from the instructions provided. You
should also refer to the installation instructions that came with the rack unit you are
using. Note: This rail will t a rack between 26.8" and 36.4" deep.
Identifying the Sections of the Rack Rails
The chassis package includes two rail assemblies. Each assembly consists of three
sections: An inner rail that secures directly to the chassis, an outer rail that secures
to the rack, and a middle rail which extends from the outer rail. These assemblies
are specically designed for the left and right side of the chassis.
Figure 2-1. Identifying the Outer Rail, Middle Rai Rail
(Left Rail Assembly Shown)
Inner Rail
Rail Assembly
(Shown with Rails
Retracted)
This Side Faces
Outward
Locking Tab
Middle Rail
Outer Rail
Chapter 2: Server Installation
2-7
Figure 2-2. Extending and Releasing the Inner Rail
Releasing the Inner Rail
Each inner rail has a locking latch. This latch prevents the server from coming
completely out of the rack when when the chassis is pulled out for servicing.
To mount the rail onto the chassis, rst release the inner rail from the outer rails.
Releasing Inner Rail from the Outer Rails
1. Pull the inner rail out of the outer rail until it is fully extended as illustrated below.
2. Press the locking tab down to release the inner rail.
3. Pull the inner rail all the way out.
4. Repeat for the other outer rail.
1
1
1
2
1
3
2-8
SuperServer 2028R-C1R(T) User's Manual
Installing the Inner Rails on the Chassis
Installing the Inner Rails
1. Identify the left and right inner rails. They are labeled.
2. Place the inner rail rmly against the side of the chassis, aligning the hooks on
the side of the chassis with the holes in the inner rail.
3. Slide the inner rail forward toward the front of the chassis until the quick release
bracket snaps into place, securing the rail to the chassis.
4. Optionally, you can further secure the inner rail to the chassis with a screw.
5. Repeat for the other inner rail.
Figure 2-3. Installing the Inner Rails
3
2
Figure 6-4. Inner Rails Installed on the Chassis
Chapter 2: Server Installation
2-9
Figure 6-5. Extending and Mounting the Outer Rails
1
1
1
2
1
3
1
4
Installing the Outer Rails onto the Rack
Installing the Outer Rails
1. Press upward on the locking tab at the rear end of the middle rail.
2. Push the middle rail back into the outer rail.
3. Hang the hooks on the front of the outer rail onto the square holes on the front
of the rack. If desired, use screws to secure the outer rails to the rack.
4. Pull out the rear of the outer rail, adjusting the length until it just ts within the
posts of the rack.
5. Hang the hooks of the rear section of the outer rail onto the square holes on the
rear of the rack. Take care that the proper holes are used so the rails are level.
If desired, use screws to secure the rear of the outer rail to the rear of the rack.
6. Repeat for the other outer rail.
Stability hazard. The rack stabilizing mechanism must be in place, or the rack
must be bolted to the oor before you slide the unit out for servicing. Failure to
stabilize the rack can cause the rack to tip over.
Do not use a two post "telco" type rack.
2-10
SuperServer 2028R-C1R(T) User's Manual
Figure 6-6. Installing into a Rack
Ball-Bearing
Shuttle
Sliding the Chassis onto the Rack Rails
Warning: Mounting the system into the rack requires at least two people to
support the chassis during installation. Please follow safety recommendations
printed on the rails.
Installing the Chassis into a Rack
1. Extend the outer rails as illustrated above.
2. Align the inner rails of the chassis with the outer rails on the rack.
3. Slide the inner rails into the outer rails, keeping the pressure even on both
sides. When the chassis has been pushed completely into the rack, it should
click into the locked position.
4. Optional screws may be used to hold the front of the chassis to the rack.
Note: The gure above is for illustrative purposes only. Always install servers to
the bottom of the rack rst.
Caution: Do not pick up the server with the front handles. They are designed
to pull the system from a rack only.
Chapter 3: System Interface
3-1
Chapter 3
System Interface
3-1 Overview
The server includes:
A control panel on the front that houses power buttons and status monitoring
lights
Status lights on the externally accessible hard drives
Status lights for the power supply visible from the back of the chassis
Figure 3-1. Control Panel
SUPERSERVER 2028R-C1R(T) User's Manual
3-2
3-3 Control Panel LEDs
There are six LEDs that provide status information about the system.
Power: The main power switch is used to apply or remove power from the power
supply to the server system. Turning off system power with this button removes the
main power but keeps standby power supplied to the system. Therefore, you must
unplug system before servicing.
Reset: The reset button is used to reboot the system.
3-2 Control Panel Buttons
The chassis includes two push-buttons that control power to the system.
Power: Indicates power is being supplied to the system power supply units. This
LED should normally be illuminated when the system is operating.
HDD: Indicates activity on the hard drive when ashing.
NIC2: Indicates network activity on GLAN2 when ashing.
2
Chapter 3: System Interface
3-3
NIC1: Indicates network activity on GLAN1 when ashing.
Information LED: Alerts operator of several states, as noted in the table below.
Information LED
Status Description
Continuously on and red An overheat condition has occured.
(This may be caused by cable congestion.)
Blinking red (1Hz) Fan failure, check for an inoperative fan.
Blinking red (0.25Hz) Power failure, check for a non-operational power supply.
Solid blue Local UID has been activated. Use this function to locate
the server in a rack mount environment.
Blinking blue Remote UID is on. Use this function to identify the
server from a remote location.
Overheating
There are several possible responses if the system overheats.
Overheat Temperature Setting
Some backplanes allow the overheat temperature to be set at 45, 50, or 55 by
changing a jumper setting. For more information, consult the backplane user manual
at www.supermicro.com. (Click Support, then the Manuals link.)
Responses
If the server overheats:
1. Use the LEDs to determine the nature of the overheating condition.
1
NIC1: Indicates network activity on GLAN1 when ashing.
!
SUPERSERVER 2028R-C1R(T) User's Manual
3-4
2. Conrm that the chassis covers are installed properly.
3. Check the routing of the cables and make sure all fans are present and operating
normally.
4. Verify that the heatsinks are installed properly.
3-4 Drive Carrier LEDs
The chassis includes externally accessible SAS/SATA drives. Each drive carrier
displays two status LEDs on the front of the carrier.
Green: When illuminated, this LED indicates drive activity. It blinks on and off
when that particular drive is being accessed This function is controlled by the
backplane.
Red: When illuminated, this LED indicates a drive failure. You should be notied
by your system management software.
3-5 Power Supply LEDs
On the rear of the power supply module, an LED displays the status.
Solid Green: When illuminated, indicates that the power supply is on.
Solid Amber: When illuminated, indicates the power supply is plugged in and
turned off, or the system is off but in an abnormal state.
Blinking Amber: When blinking, this system power supply temperature has
reached 63C. The system will automatically power-down when the power supply
temperature reaches 70C and restarts when the power supply temperature
goes below 60C.
4-1
Chapter 4: Warning Statements for AC Systems
Chapter 4
Standardized Warning Statements for AC Systems
4-1 About Standardized Warning Statements
The following statements are industry standard warnings, provided to warn the user
of situations which have the potential for bodily injury. Should you have questions
or experience difficulty, contact Supermicro's Technical Support department
for assistance. Only certied technicians should attempt to install or congure
components.
Read this appendix in its entirety before installing or conguring components in the
Supermicro chassis.
These warnings may also be found on our web site at http://www.supermicro.com/
about/policies/safety_information.cfm.
Warning!
This warning symbol means danger. You are in a situation that could cause bodily
injury. Before you work on any equipment, be aware of the hazards involved with
electrical circuitry and be familiar with standard practices for preventing accidents.
Warning Denition
警告の定義
の警告サンは危険を意味
人身事故に可能性があのでれの機器動作
電気回路に危険性に注意準的な事故防止策に精通下さい。
此警告符号代表危险。
您正处于可能受到严重伤害的工作环境中。在您使用设备开始工作之前,必须充分意
识到触电的危险,并熟练掌握防止事故发生的标准工作程序。请根据每项警告结尾的
声明号码找到此设备的安全性警告说明的翻译文本。
此警告符號代表危險。
您目前所處的工作環境可能讓您受傷。您使用任何設備之前,請注意觸電的危險,
並且要熟悉預防事故發生的標準工作程序。請依照每一注意事項後的號碼找到相關
的翻譯說明內容。
4-2
SuperServer 2028R-C1R(T) User's Manual
Warnung
WICHTIGE SICHERHEITSHINWEISE
Dieses Warnsymbol bedeutet Gefahr. Sie benden sich in einer Situation, die zu
Verletzungen führen kann. Machen Sie sich vor der Arbeit mit Geräten mit den
Gefahren elektrischer Schaltungen und den üblichen Verfahren zur Vorbeugung
vor Unfällen vertraut. Suchen Sie mit der am Ende jeder Warnung angegebenen
Anweisungsnummer nach der jeweiligen Übersetzung in den übersetzten
Sicherheitshinweisen, die zusammen mit diesem Gerät ausgeliefert wurden.
BEWAHREN SIE DIESE HINWEISE GUT AUF.
INSTRUCCIONES IMPORTANTES DE SEGURIDAD
Este símbolo de aviso indica peligro. Existe riesgo para su integridad física. Antes
de manipular cualquier equipo, considere los riesgos de la corriente eléctrica y
familiarícese con los procedimientos estándar de prevención de accidentes. Al
nal de cada advertencia encontrará el número que le ayudará a encontrar el texto
traducido en el apartado de traducciones que acompaña a este dispositivo.
GUARDE ESTAS INSTRUCCIONES.
IMPORTANTES INFORMATIONS DE SÉCURI
Ce symbole d'avertissement indique un danger. Vous vous trouvez dans une
situation pouvant entraîner des blessures ou des dommages corporels. Avant
de travailler sur un équipement, soyez conscient des dangers liés aux circuits
électriques et familiarisez-vous avec les procédures couramment utilisées pour
éviter les accidents. Pour prendre connaissance des traductions des avertissements
gurant dans les consignes de sécuritraduites qui accompagnent cet appareil,
référez-vous au numéro de l'instruction situé à la n de chaque avertissement.
CONSERVEZ CES INFORMATIONS.
הרהזא תורהצה ןונקת
הלבח ינפמ שמתשמה תא ריהזהל תנמ לע ,היישעתה ינקת יפ לע תורהזא ןה תואבה
הכימת תקלחמ םע רשק רוציל שי ,יהשלכ היעבב תולקתיה וא תולאש שיו הדימב .תירשפ
.םיביכרה תא רידגהל וא ןיקתהל םיאשר דבלב םיכמסומ םיאנכט .ורקימרפוס לש
.ורקימרפוס יזראמב םיביכרה תרדגה וא תנקתה ינפל ואולמב חפסנה תא אור
4-3
Warning Statements for AC Systems
  
!
      .      
   .       
        
   .
          

BELANGRIJKE VEILIGHEIDSINSTRUCTIES
Dit waarschuwings symbool betekent gevaar. U verkeert in een situatie die
lichamelijk letsel kan veroorzaken. Voordat u aan enige apparatuur gaat werken,
dient u zich bewust te zijn van de bij een elektrische installatie betrokken risico's
en dient u op de hoogte te zijn van de standaard procedures om ongelukken te
voorkomen. Gebruik de nummers aan het eind van elke waarschuwing om deze te
herleiden naar de desbetreffende locatie.
BEWAAR DEZE INSTRUCTIES
. !        

           

   
   
     

  
4-4
SuperServer 2028R-C1R(T) User's Manual
Installation Instructions
Warning!
Read the installation instructions before connecting the system to the power source.
Warnung
Vor dem Anschließen des Systems an die Stromquelle die Installationsanweisungen
lesen.
¡Advertencia!
Lea las instrucciones de instalación antes de conectar el sistema a la red de
alimentación.
Attention
Avant de brancher le système sur la source d'alimentation, consulter les directives
d'installation.
設置手順書
を電源接続す前に設置手順書をお読み下
      .
Waarschuwing
Raadpleeg de installatie-instructies voordat u het systeem op de voedingsbron
aansluit.
警告
将此系统连接电源前,请先阅读安装说明。
警告
將系統與電源連接前,請先閱讀安裝說明。
.חתמ רוקמל תכרעמה רוביח ינפל הנקתה תוארוה תא אורקל
        
4-5
Chapter 4: Warning Statements for AC Systems
Circuit Breaker
Warning!
This product relies on the building's installation for short-circuit (overcurrent)
protection. Ensure that the protective device is rated not greater than: 250 V, 20 A.
ーキレー
製品は短絡(過電流)保護装置が建物での設置前提ています
保護装置の定格が250 V20 Aないを確認下
Warnung
Dieses Produkt ist darauf angewiesen, dass im Gebäude ein Kurzschluss-
bzw. Überstromschutz installiert ist. Stellen Sie sicher, dass der Nennwert der
Schutzvorrichtung nicht mehr als: 250 V, 20 A beträgt.
¡Advertencia!
Este equipo utiliza el sistema de protección contra cortocircuitos (o sobrecorrientes)
del edicio. Asegúrese de que el dispositivo de protección no sea superior a: 250
V, 20 A.
Attention
Pour ce qui est de la protection contre les courts-circuits (surtension), ce produit
dépend de l'installation électrique du local. Vériez que le courant nominal du
dispositif de protection n'est pas supérieur à :250 V, 20 A.
警告
产品(过载电流)保护由建筑物的供电系统提供,确保短路保护设备的额定电
流不大于250V,20A
警告
產品(過載電流)保護由建築物的供電系統提供,確保短路保護設備的額定電
流不大於250V,20A
יכ אדוול שי .ילמשח רצק תעינמל םינבמב תנקתומה הנגה לע ךמתסמ
250VDC, 20A-מ רתוי אל אוה ילמשחה רצקה ינפמ ןגמה רישכמ
4-6
SuperServer 2028R-C1R(T) User's Manual
Power Disconnection Warning
電源切断の警
ンポ付けたはめにシー内部に
の電源はすべてソー切断され、電源コーは電源モジルか
外す必要があ
警告
在你打开机箱并安装或移除内部器件前,必须将系统完全断电,并移除电源线。
警告
在您打開機殼安裝或移除內部元件前,必須將系統完全斷電,並移除電源線。
Warnung
Das System muss von allen Quellen der Energie und vom Netzanschlusskabel
getrennt sein, das von den Spg.Versorgungsteilmodulen entfernt wird, bevor es
auf den Chassisinnenraum zurückgreift, um Systemsbestandteile anzubringen oder
zu entfernen.
Warning!
The system must be disconnected from all sources of power and the power cord
removed from the power supply module(s) before accessing the chassis interior to
install or remove system components.
!
   ()     
.    250V(), 20A() 
  .
Waarschuwing
Dit product is afhankelijk van de kortsluitbeveiliging (overspanning) van
uw electrische installatie. Controleer of het beveiligde aparaat niet groter
gedimensioneerd is dan 220V, 20A.
        

20A, 250V :         
4-7
Chapter 4: Warning Statements for AC Systems
¡Advertencia!
El sistema debe ser disconnected de todas las fuentes de energía y del cable
eléctrico quitado de los módulos de fuente de alimentación antes de tener acceso
el interior del chasis para instalar o para quitar componentes de sistema.
Attention
Le système doit être débranché de toutes les sources de puissance ainsi que de
son cordon d'alimentation secteur avant d'accéder à l'intérieur du chassis pour
installer ou enlever des composants de systéme.
!
        
       
.
Waarschuwing
Voordat u toegang neemt tot het binnenwerk van de behuizing voor het installeren
of verwijderen van systeem onderdelen, dient u alle spanningsbronnen en alle
stroomkabels aangesloten op de voeding(en) van de behuizing te verwijderen
ילמשח קותינ ינפמ הרהזא
הרהזא!
קפסהמ ילמשחה לבכ תא ריסהל שיו למשחה תורוקמ לכמ תכרעמה תא
םיביכר תרסה וא תנקתה ךרוצל זראמה לש ימינפה קלחל השי
           
 
         
4-8
SuperServer 2028R-C1R(T) User's Manual
Equipment Installation
機器の設置
レーグを受け定された人だけが置の設置、交換、たはサーを許可
Warning!
Only trained and qualied personnel should be allowed to install, replace, or service
this equipment.
Warnung
Das Installieren, Ersetzen oder Bedienen dieser Ausrüstung sollte nur geschultem,
qualiziertem Personal gestattet werden.
¡Advertencia!
Solamente el personal calicado debe instalar, reemplazar o utilizar este equipo.
Attention
Il est vivement recommandé de confier l'installation, le remplacement et la
maintenance de ces équipements à des personnels qualiés et expérimentés.
!
      ,     
.
警告
只有经过培训且具有资格的人员才能进行此设备的安装、更换和维修。
警告
只有經過受訓且具資格人員才可安裝、更換與維修此設備。
!הרהזא
.דויצה רובע תוריש תתל וא דויצה תא ףילחהל ,ןיקתהל יאשר דבלב ךמסומ
            
4-9
Chapter 4: Warning Statements for AC Systems
ス制限区域
ユニは、ス制限区域に設を想定
ス制限区域は、特別なール前、そののセキの手用い
み出入可能です
Warning!
This unit is intended for installation in restricted access areas. A restricted access
area can be accessed only through the use of a special tool, lock and key, or other
means of security. (This warning does not apply to workstations).
Restricted Area
Waarschuwing
Deze apparatuur mag alleen worden geïnstalleerd, vervangen of hersteld door
geschoold en gekwaliceerd personeel.
Warnung
Diese Einheit ist zur Installation in Bereichen mit beschränktem Zutritt vorgesehen.
Der Zutritt zu derartigen Bereichen ist nur mit einem Spezialwerkzeug, Schloss und
Schlüssel oder einer sonstigen Sicherheitsvorkehrung möglich.
¡Advertencia!
Esta unidad ha sido diseñada para instalación en áreas de acceso restringido.
Sólo puede obtenerse acceso a una de estas áreas mediante la utilización de una
herramienta especial, cerradura con llave u otro medio de seguridad.
Attention
Cet appareil doit être installée dans des zones d'accès réservés. L'accès à une
zone d'accès réservé n'est possible qu'en utilisant un outil spécial, un mécanisme
de verrouillage et une clé, ou tout autre moyen de curité.
警告
此部件应安装在限制进出的场所,限制进出的场所指只能通过使用特殊工具、锁和钥
匙或其它安全手段进出的场所。
警告
此裝置僅限安裝於進出管制區域,進出管制區域係指僅能以特殊工具、鎖頭及鑰匙或
其他安全方式才能進入的區域。
4-10
SuperServer 2028R-C1R(T) User's Manual
Battery Handling
Warning!
There is the danger of explosion if the battery is replaced incorrectly. Replace the
battery only with the same or equivalent type recommended by the manufacturer.
Dispose of used batteries according to the manufacturer's instructions
경고!
이 장치는 접근이 제한된 구역에 설치하도록 되어있습니다. 특수도구, 잠금 장치 및
키, 또는 기타 보안 수단을 통해서만 접근 제한 구역에 들어갈 수 있습니다.
Waarschuwing
Dit apparaat is bedoeld voor installatie in gebieden met een beperkte toegang.
Toegang tot dergelijke gebieden kunnen alleen verkregen worden door gebruik te
maken van speciaal gereedschap, slot en sleutel of andere veiligheidsmaatregelen.
電池の取扱い
電池交換が正行われなかた場合、破裂の危険性が 交換す電池は
ーが推奨す型、たは同等ののを使用下 使用済電池は製造元の指示に
処分
警告
电池更换不当会有爆炸危险。请只使用同类电池或制造商推荐的功能相当的电池更
换原有电池。请按制造商的说明处理废旧电池。
警告
電池更換不當會有爆炸危險。請使用製造商建議之相同或功能相當的電池更換原有
電池。請按照製造商的說明指示處理廢棄舊電池。
תלבגומ השיג םע רוזא
!הרהזא
תרזעב תנתינ השיגה .השיג תלבגה םהב שיש םירוזאב הדיחיה תא ןיקתהל שי
(.דכו לוענמ ,חתפמ( דבלב החטבא ילכ'
. 


4-11
Chapter 4: Warning Statements for AC Systems
Warnung
Bei Einsetzen einer falschen Batterie besteht Explosionsgefahr. Ersetzen Sie die
Batterie nur durch den gleichen oder vom Hersteller empfohlenen Batterietyp.
Entsorgen Sie die benutzten Batterien nach den Anweisungen des Herstellers.
Attention
Danger d'explosion si la pile n'est pas remplacée correctement. Ne la remplacer
que par une pile de type semblable ou équivalent, recommandée par le fabricant.
Jeter les piles usagées conformément aux instructions du fabricant.
¡Advertencia!
Existe peligro de explosn si la batea se reemplaza de manera incorrecta.
Reemplazar la batería exclusivamente con el mismo tipo o el equivalente
recomendado por el fabricante. Desechar las baterías gastadas según las
instrucciones del fabricante.
경고!
배터 올바르게 체되 않으 폭발의 위험이 있습. 기존 배터
동일하거나 제조사에서 권장하는 동등한 종류의 배터리로만 교체해야 합니다.
제조사의 내에 따라 사용된 배터리를 처리하주십시오.
Waarschuwing
Er is ontplofngsgevaar indien de batterij verkeerd vervangen wordt. Vervang de
batterij slechts met hetzelfde of een equivalent type die door de fabrikant aanbevolen
wordt. Gebruikte batterijen dienen overeenkomstig fabrieksvoorschriften afgevoerd
te worden.
!הרהזא
ףילחהל שי .הניקת אל ךרדב הפלחוהו הדימב הללוסה לש ץוציפ תנכס תמייק
.תצלמומ ןרצי תרבחמ םאותה גוסב הללוסה תא
.ןרציה תוארוה יפל עצבל שי תושמושמה תוללוסה קוליס
          
 
          
       
4-12
SuperServer 2028R-C1R(T) User's Manual
Warnung
Dieses Gerät kann mehr als eine Stromzufuhr haben. Um sicherzustellen, dass
der Einheit kein trom zugeführt wird, müssen alle Verbindungen entfernt werden.
¡Advertencia!
Puede que esta unidad tenga más de una conexión para fuentes de alimentación.
Para cortar por completo el suministro de energía, deben desconectarse todas las
conexiones.
Attention
Cette uni peut avoir plus d'une connexion d'alimentation. Pour supprimer toute
tension et tout courant électrique de l'unité, toutes les connexions d'alimentation
doivent être branchées.
Redundant Power Supplies
Warning!
This unit might have more than one power supply connection. All connections must
be removed to de-energize the unit.
冗長電源装置
のユニは複数の電源装置が接続る場合が
ユニの電源をためにはすべ接続なけばな
警告
此部件连接的电源可能不止一个,必须将所有电源断开才能停止给该部件供电。
警告
此裝置連接的電源可能不只一個,必須切斷所有電源才能停止對該裝置的供電。
דחא קפסמ רתוי םייק םא
!הרהזא
ןקורל תנמ לע םירוביחה לכ תא ריסהל שי .קפס לש דחא רוביחמ רתוי שי הדחיל
.הדיחיה תא
4-13
Chapter 4: Warning Statements for AC Systems
Backplane Voltage
の電圧
ステムの稼働中は危険な電圧たは電力が、レーン上かかてい
修理す際に注意
警告
当系统正在进行时,背板上有很危险的电压或能量,进行维修时务必小心。
警告
當系統正在進行時,背板上有危險的電壓或能量,進行維修時務必小心。
Warnung
Wenn das System in Betrieb ist, treten auf der Rückwandplatine gehrliche
Spannungen oder Energien auf. Vorsicht bei der Wartung.
¡Advertencia!
Cuando el sistema está en funcionamiento, el voltaje del plano trasero es peligroso.
Tenga cuidado cuando lo revise.
Attention
Lorsque le système est en fonctionnement, des tensions électriques circulent sur
le fond de panier. Prendre des précautions lors de la maintenance.
Warning!
Hazardous voltage or energy is present on the backplane when the system is
operating. Use caution when servicing.
경고!
이 장치에는 한 개 이상의 전원 공급 단자가 연결되어 있을 수 있습니다. 이 장치에
전원을 차단하기 위해서는 모든 연결 단자를 제거해야만 합니다.
Waarschuwing
Deze eenheid kan meer dan één stroomtoevoeraansluiting bevatten. Alle
aansluitingen dienen verwijderd te worden om het apparaat stroomloos te maken.
.        
     
4-16
SuperServer 2028R-C1R(T) User's Manual
Waarschuwing
De uiteindelijke verwijdering van dit product dient te geschieden in overeenstemming
met alle nationale wetten en reglementen.
プの警告
警告回転部品に注意運転中は回転部(羽根)に触れないシか
ン装置をた際、だ回転可能性 ンの
口部に指、バーびその他ののを近づけないで下
警告!
警告!危险的可移动性零件。请务必与转动的风扇叶片保持距离 您从机架移除
风扇装置,风扇可能仍在转动。小心不要将手指、螺丝起子和其他物品太靠近风扇
警告
危險的可移動性零件。請務必與轉動的風扇葉片保持距離。 當您從機架移除風扇裝
置,風扇可能仍在轉動。小心不要將手指、螺絲起子和其他物品太靠近風扇。
경고!
이 제품은 해당 국가의 관련 법규 및 규정에 따라 폐기되어야 합니다.
Hot Swap Fan Warning
Warning!
Hazardous moving parts. Keep away from moving fan blades. The fans might still
be turning when you remove the fan assembly from the chassis. Keep ngers,
screwdrivers, and other objects away from the openings in the fan assembly's
housing.
Attention
La mise au rebut ou le recyclage de ce produit sont généralement soumis à des
lois et/ou directives de respect de l'environnement. Renseignez-vous auprès de
l'organisme compétent.
רצומה קוליס
!הרהזא
.הנידמה יקוחו תויחנהל םאתהב תויהל בייח הז רצומ לש יפוס קוליס
           
4-19
Chapter 4: Warning Statements for AC Systems
¡Advertencia!
Cuando instale el producto, utilice la conexión provista o designada o procure
cables, Cables de alimentación y adaptadores de CA que cumplan con los códigos
locales y los requisitos de seguridad, incluyendo el tamaño adecuado del cable y el
enchufe. El uso de otros cables y adaptadores podría causar un mal funcionamiento
o un incendio. La Ley de Seguridad de Aparatos Eléctricos y de Materiales prohíbe
El uso de cables certicados por UL o CSA (que tienen el certicado UL / CSA en
el código) para cualquier otros dispositivos eléctricos que los productos designados
únicamente por Supermicro.Attention
Attention
Lors de l'installation du produit, utilisez les cables de connection fournis ou désig
ou achetez des cables, cables de puissance et adaptateurs respectant les normes
locales et les conditions de securite y compris les tailles de cables et les prises
electriques appropries. L'utilisation d'autres cables et adaptateurs peut provoquer
un dysfonctionnement ou un incendie. Appareils électroménagers et la Loi sur la
Sécurité Matériel interdit l'utilisation de bles certies- UL ou CSA (qui ont UL ou
CSA indiqué sur le code) pour tous les autres appareils électriques sauf les produits
désignés par Supermicro seulement.
ימאתמו םיילמשח םילבכ AC
הרהזא!
םימאתמו םיקפס ,םילבכב שמתשהל שי ,רצומה תא םיניקתמ רשאכ וא ושכרנ רשא AC
הנוכנ הדימ ללוכ ,תוימוקמה תוחיטבה תושירדל ומאתוה רשאונקתהה ךרוצל ומאתוה
רצק וא הלקתל םורגל לולע ,רחא גוסמ םאתמ וא לבכ לכב שומיש . עקתהו לבכה לש
שמתשהל רוסיא םייק ,תוחיטבה יקוחו למשחה ירישכמב שומישה יקוחל םאתהב .ילמשח
ב םיכמסומה םילבכב ב וא לש דוק םהילע עיפומ רשאכ- UL -CSA ( (UL/CSA רובע
י"ע םאתוה רשא רצומב קר אלא ,רחא ילמשח רצומ לכ Supermicro דבלב.
           
  .          
     .     
             UL CSA  (UL/CSA)
   Supermicro.
4-20
SuperServer 2028R-C1R(T) User's Manual
전원 이블 AC 어댑터
경고! 제품을 설치할 때 현지 코드 적절한 굵기의 코드와 플러그를 포함한 안전
요구 사항을 준수하여 제공되거나 지정된 연결 혹은 구매 케이블, 전원 케이블
AC 어댑터사용하십시오.
다른 케이블이나 댑터를 용하면 오작동이나 재가 발생할 있습니다. 전기
용품 전법은 UL 또는 CSA 인증 케이블 (코드에 UL / CSA가 표시된 케이블)
Supermicro가 지정한 제품 이외의 전기 장치에 사용하것을 금지합니다.
Stroomkabel en AC-Adapter
Waarschuwing! Bij het aansluiten van het Product uitsluitend gebruik maken van de
geleverde Kabels of een andere geschikte aan te schaffen Aansluitmethode, deze
moet altijd voldoen aan de lokale voorschriften en veiligheidsnormen, inclusief de
juiste kabeldikte en stekker. Het gebruik van niet geschikte Kabels en/of Adapters
kan een storing of brand veroorzaken. Wetgeving voor Elektrische apparatuur en
Materiaalveiligheid verbied het gebruik van UL of CSA -gecerticeerde Kabels (met
UL/CSA in de code) voor elke andere toepassing dan de door Supermicro hiervoor
beoogde Producten.
Chapter 5: Advanced Serverboard Setup
5-1
Chapter 5
Advanced Serverboard Setup
This chapter covers the steps required to install processors and heatsinks to the
X10DRH-C(T) serverboard, connect the data and power cables and install add-on
cards. All serverboard jumpers and connections are described and a layout and
quick reference chart are included in this chapter. Remember to close the chassis
completely when you have nished working on the serverboard to protect and cool
the system sufciently.
5-1 Handling the Serverboard
Static electrical discharge can damage electronic com ponents. To prevent damage
to printed circuit boards, it is important to handle them very carefully (see Chapter
4). Also note that the size and weight of the serverboard can cause it to bend if
handled improperly, which may result in damage. To prevent the serverboard from
bending, keep one hand under the center of the board to support it when handling.
The following measures are generally sufcient to protect your equipment from
static discharge.
Precautions
Use a grounded wrist strap designed to prevent static discharge.
Touch a grounded metal object before removing any board from its antistatic bag.
Handle a board by its edges only; do not touch its components, peripheral chips,
memory modules or gold contacts.
When handling chips or modules, avoid touching their pins.
Put the serverboard, add-on cards and peripherals back into their antistatic
bags when not in use.
Unpacking
The serverboard is shipped in antistatic packaging to avoid static damage. When
unpacking the board, make sure the person handling it is static protected.
5-2
S SUPER ERVER 2028R-C1R(T) User's Manual
5-2 Installing the Processor and Heatsink
Notes:
Always remove the power cord before adding, removing or changing a CPU.
When receiving a serverboard without a processor pre-installed, make sure that
the plastic CPU socket cap is in place and none of the socket pins are bent;
otherwise, contact your retailer immediately.
If you buy a CPU separately, use only an Intel-certied, multi-directional heatsink.
Avoid placing direct pressure to the top of the processor package.
Install the processor into the CPU socket before installing the heatsink.
Refer to the Supermicro web site for updates on CPU support.
Installing an LGA 2011 Processor
Release
the lever labeled "Open 1st"
Installing a CPU
1. There are two levers on the LGA 2011
socket. First press and release the
load lever labeled "Open 1st".
OPEN 1st
OPEN 1st
Release
the lever labeled "Close 1st"
2. Press the second load lever labeled
"Close 1st" to release the load plate
from its locked position.
Chapter 5: Advanced Serverboard Setup
5-3
3. Wit h the s ec ond leve r full y
retracted, gently push down on
the "Open 1st" lever to loosen the
load plate. Lift the load plate with
your ngers to open it completely.
4. Pop the plas tic c ap mar ked
"Warning" out of the load plate.
5. Holding the CPU carefully above
the socket, orient the CPU so
that all keys and edges will t the
socket.
OPEN 1st
IMPORTANT!
Caution: You can only install the CPU into the socket in one direction. Make sure
that the CPU is properly inserted into the socket before closing the load plate. If it
does not close properly, do not force it as it may damage your CPU. Instead, open
the load plate again and double-check that the CPU is aligned properly.
Open the load
plate.
6. Carefully lower the CPU straight
down into the socket. Do not
move the CPU horizontally, and
do not rub the pins of the socket.
This may damage the CPU or the
socket.
5-4
S SUPER ERVER 2028R-C1R(T) User's Manual
8. Make sure the locking mechanism
on the "Close 1st" lever catches the
lip of the load plate. Close and lock
the "Close 1st" lever.
Push down and lock
the
lever labeled "Open 1st"
OPEN 1st
OPEN 1st
Push down and lock the lever
labeled "Close 1st".
9. Close and lock the "Open 1st" lever.
Engage the lip
of the load plate
and locking
portion of the
lever."
7. With the "Close 1st" lever fully
retracted, gently close the load
plate.
Gently close
the load plate.
5-6
S SUPER ERVER 2028R-C1R(T) User's Manual
5-3 Connecting Cables
Now that the processors are installed, the next step is to connect the cables to the
serverboard. These include the data (ribbon) cables for the peripherals and control
panel and the power cables.
Connecting Data Cables
The cables used to transfer data from the peripheral devices have been carefully
routed in precongured systems to prevent them from blocking the ow of cooling
air that moves through the system from front to back. If you need to disconnect any
of these cables, you should take care to reroute them as they were originally after
reconnecting them and be aware of the pin 1 locations. If you are conguring the
system, keep the airow in mind when routing the cables.
Connecting Power Cables
The serverboard has a 24-pin primary power supply connector designated J24
for connection to the power supply. There are also two 8-pin power connectors,
JPWR1 and JPWR2. Connect the appropriate cable connectors from the power
supply. Connector pin denitions are explained later in the chapter.
Connecting the Control Panel
JF1 contains header pins for the front control panel connectors. All JF1 wires have
been bundled into single keyed ribbon cable to simplify their connection. The red
wire in the ribbon cable plugs into pin 1 of JF1. Connect the other end of the cable
to the Control Panel printed circuit board, located just behind the system status
LEDs in the chassis.
See the Connector Denitions section in this chapter for details and pin descriptions
of JF1.
Chapter 5: Advanced Serverboard Setup
5-7
5-4 I/O Ports
Figure 5-2 shows the I/O ports on the rear of the system.
Figure 5-2. Rear Panel I/O Ports
LAN Ports
The 2028R-C1R uses the X10DRH-C serverboard, and the LAN ports offer gigbit
speed. The 2028R-C1RT uses the X10DRH-CT, and the LAN ports provide
10GBase-T.
Rear I/O Ports
1. COM Port 1
2. USB Port 0 (USB 2.0)
3. USB Port 1 (USB 2.0)
4. Dedicated IPMI LAN
5. USB Port 4 (USB 3.0)
6. USB Port 5 (USB 3.0)
7. LAN Port 1
8. LAN Port 2
9 VGA Port
10 UID Button
1 987
6
5
4
3
2
10
5-8
S SUPER ERVER 2028R-C1R(T) User's Manual
5-5 Installing Memory
Note: Check the Supermicro web site for recommended memory modules.
CAUTION
Exercise extreme care when installing or removing DIMM modules
to prevent any possible damage.
Installing DIMMs
1. Insert the desired number of DIMMs into the memory slots, starting with slot
DIMMA1.
2. Push the release tabs outwards on both ends of the DIMM slot to unlock it.
3. Align the key on the DIMM module with the receptive point on the slot.
4. Use two thumbs together to press on both ends of the module straight down
into the slot until the module snaps into place.
5. Press the release tabs to the lock positions to secure the DIMM module into
the slot. See Figure 5-3.
Figure 5-3. Installing DIMM into Slot
Socket Key
Release Tab
Release Tab
Chapter 5: Advanced Serverboard Setup
5-9
Memory Support
The server features 16 DIMM slots that can support up to 2 TB of Load Reduced
(LRDIMM) ECC registered memory or up to 512 GB of registered (RDIMM) DDR4-
2400/2133/1866/1600 memory. For the latest memory updates, please refer to our
website at http://www.supermicro.com/products/motherboard.
Processor & Memory Module Population Conguration
For memory to work properly, follow the tables below for memory installation.
Processors and their Corresponding Memory Modules
CPU# Corresponding DIMM Modules
CPU 1 P1-
DIMMA1
P1-
DIMMB1
P1-
DIMMC1
P1-
DIMMD1
P1-
DIMMA2
P1-
DIMMB2
P1-
DIMMC2
P1-
DIMMD2
CPU2 P2-
DIMME1
P2-
DIMMF1
P2-
DIMMG1
P2-
DIMMH1
P2-
DIMME2
P2-
DIMM F2
P2-
DIMMG2
P2-
DIMMH2
Processor and Memory Module Population for Optimal Performance
Number of
CPUs+DIMMs
CPU and Memory Population Conguration Table
(For memory to work properly, please follow this table.)
1 CPU &
2 DIMMs
CPU1
P1-DIMMA1/P1-DIMMB1
1 CPU &
4 DIMMs
CPU1
P1-DIMMA1/P1-DIMMB1, P1-DIMMC1/P1-DIMMD1
1 CPU &
5~8 DIMMs
CPU1
P1-DIMMA1/P1-DIMMB1, P1-DIMMC1/P1-DIMMD1 + any pair of P1-DIMMA2/P1-
DIMMB2/P1-DIMMC2/P1-DIMMD2 slots
2 CPUs &
4 DIMMs
CPU1 + CPU2
P1-DIMMA1/P1-DIMMB1, P2-DIMME1/P2-DIMMF1
2 CPUs &
6 DIMMs
CPU1 + CPU2
P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1
2 CPUs &
8 DIMMs
CPU1 + CPU2
P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1/P2-
DIMMG1/P2-DIMMH1
2 CPUs &
9~16 DIMMs
CPU1/CPU2
P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1/P2-
DIMMG1/P2-DIMMH1 + any pair of P1, P2 DIMM slots
2 CPUs &
16 DIMMs
CPU1/CPU2
P1-DIMMA1/P1-DIMMB1/P1-DIMMC1/P1-DIMMD1, P2-DIMME1/P2-DIMMF1/
P2-DIMMG1/P2-DIMMH1,P1-DIMMA2/P1-DIMMB2/P1-DIMMC2/P1-DIMMD2, P2-
DIMME2/P2-DIMMF2/P2-DIMMG2/P2-DIMMH2
5-10
S SUPER ERVER 2028R-C1R(T) User's Manual
Caution: For the memory to work properly, install DIMMs of the same type and
speed. Mixing of DIMMs of different types or speeds is not allowed.
Populating DDR4 Memory Modules
Populating RDIMM/LRDIMM DDR4 Memory Modules
Type
Ranks
Per DIMM
and Data
Width
DIMM Capacity
(GB)
Speed (MT/s); Voltage (V); Slots per Channel (SPC) and
DIMMs per Channel (DPC)
2 Slots per Channel
1 DPC 2 DPC
E5-2600 V3 E5-2600 V4 E5-2600 V3 E5-2600 V4
4 GB 8 GB 1.2 V 1.2 V 1.2 V 1.2 V
RDIMM SRx4 8 GB 16 GB 2133 2400 1866 2133
RDIMM SRx8 4 GB 8 GB 2133 2400 1866 2133
RDIMM DRx8 8 GB 16 GB 2133 2400 1866 2133
RDIMM DRx4 16 GB 32 GB 2133 2400 1866 2133
LRDIMM QRx4 32 GB 64 GB 2133 2400 2133 2400
LRDIMM 3DS 8Rx4 64 GB 2133 2400 2133 2400128 GB


Product specificaties

Merk: Supermicro
Categorie: Server
Model: SuperServer 2028R-C1R
Kleur van het product: Zwart
Breedte: 437 mm
Diepte: 630 mm
Hoogte: 89 mm
LED-indicatoren: Ja
Processorfamilie: Intel
Ethernet LAN: Ja
Aantal USB 2.0-poorten: 4
VGA (D-Sub)poort(en): 1
Aantal Ethernet LAN (RJ-45)-poorten: 3
Netvoeding: 920 W
Duurzaamheidscertificaten: RoHS
Ethernet LAN, data-overdrachtsnelheden: 1000 Mbit/s
Temperatuur bij opslag: -40 - 70 °C
Aantal ventilatoren: 3 ventilator(en)
Processor socket: LGA 2011-v3
Systeembus: 9.6 GT/s
Maximum intern geheugen: 1000 GB
On-board graphics adapter model: Aspeed AST2400
Luchtvochtigheid bij opslag: 5 - 95 procent
Type behuizing: Rack (2U)
Overtollige fans ondersteuning: Ja
ECC: Ja
Ethernet interface type: Gigabit Ethernet
PCI Express x1 slots: 16
Koperen ethernetbekabelingstechnologie: 1000BASE-T, 100BASE-TX
Ondersteunde opslagstationinterfaces: Serial Attached SCSI (SAS)-3, Serial ATA III
Seriële poort(en): 4
LAN controller: Intel® I350
Soorten RAID: 0, 1,6, 10, 50, 60
Geheugenbus: 72 Bit
Aantal SATA III connectors: 8
Compatibele processors: Intel® Xeon®
Aantal ondersteunde processoren: 1
Intel® Xeon series: E5-2600
Maximum UDIMM geheugen: 32 GB
Aantal DIMM sloten: 16
Aantal storage drives ondersteund: 16
Opslagschijf afmetingen ondersteund: 2.5 "
Ondersteunde geheugen types: DDR4-SDRAM
Hot-swap HDD bays: Ja
AC-ingangsspanning: 100 - 240 V
AC-ingangsfrequentie: 50 - 60 Hz
Bedrijfstemperatuur (T-T): 10 - 35 °C
Relatieve vochtigheid in bedrijf (V-V): 8 - 90 procent
Code geharmoniseerd systeem (HS): 84714100
Ventilator diameter: 80 mm
DC output stroom (+ 12 V): 75 A
IPMI LAN (RJ-45) port: Ja
DC uitgangsstroom (+ 5 V): 4 A
Maximale cache: 45 MB