For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 PN51F
Page 1 of 2
Pan-Punch 110 Punchdown System
Part Numbers: P110KB1004Y, P110KB1005Y, P110KB3004Y, P110KB3005Y, P110B1004R2Y,
P110B1005R2Y, P110B1004R4WJY, P110B1005R4WJY
CABLE REQUIREMENT: Terminates most 22-26 AWG solid or stranded
IWC wire with a 0.050" (1.27mm) max. o.d., either PVC or Plenum rated.
INSTALLATION
1. Use appropriate mounting hardware to install base on
desired surface as shown in Figure 1, 3/4" plywood is
recommended. (Tip: Panduit lettering should be upright).
2. Route cables through slots in the base as shown in Figures
1a (4-pair installation) or 1b (25-pair installation). The wire
strip color markings from left to right are white, red, blue,
yellow, and violet.
3. Insert each pair into position in wire strip slots while
maintaining the proper color sequence. Cable jacket end
should be within 1/2" from where cable pairs are inserted.
Cable pairs must remain twisted up to the point of
connection for Category 5e installation.
4. Inspect cable pair color placement prior to using a PDT110
single wire punchdown tool or PDT110M multi-pair
punchdown tool to seat and cut the pairs to length.
5. Position the connecting block over the wired base.
6. Secure the connecting block in place using the PDT110M
multi-pair punchdown tool. It is important to keep the tool
perpendicular to the base to ensure a good termination. Use
a combination of 3, 4, and 5-pair connecting blocks to
completely fill the wire strip, such as:
- Five 5-pair connecting blocks
- Five 4-pair connecting blocks and one 5-pair
connecting block
- Seven 3-pair connecting blocks and one 4-pair
connecting block
Figure 1a (4-pair installation)
Figure 1b (25-pair installation)
Figure 2b
Figure 2a
5 PAIR KIT
4 PAIR KIT
LOCATION
Mounting a system at the right height will make wiring changes The optimum heiand additions cost efficient. ght, from the
floor to the top of a 300 pair Pan-Punch base, is 68 inches. If the customer needs don’t exceed the wiring capacity of one
base of 100 pair, the optimum distance from the floor to the top of the system can be reduced to 43 inches. This height will
allow for expansion of 300 pair on top and 300 pair underneath.
4-pair cables are installed from the center out to the sides, in groups of
three. Three cables exit from the left and three exit from the right. Each
channel will contain 12 cables - 6 for upper strip and 6 for lower strip. Far
right slot will be unused.
For clarity, only first two cables are shown. Repeat for other side
WHITE RED BLUE YELLOW VIOLET
25 pair cable (for clarity, only 5 pairs shown) Tip colors marked in 5 pair increments
Notes:
1. Strip back outer jacket of 25-pair cable to edge of wiring block (up to
10 inches) and load one complete wire strip.
2. Follow tip color code sequence as indicated on wire strip.
P110CB
CONNECTING BLOCK
WIRE STRIP
P110B BASE
PDT110M
5-PAIR IMPACT TOOL


Product specificaties

Merk: Panduit
Categorie: Niet gecategoriseerd
Model: Pan-Punch 110
Kleur van het product: Ivoor
Breedte: 272.1 mm
Diepte: 85.9 mm
Hoogte: 87.5 mm
Duurzaamheidscertificaten: RoHS
Aantal poorten: 72

Heb je hulp nodig?

Als je hulp nodig hebt met Panduit Pan-Punch 110 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Panduit

Panduit

Panduit EC001 Handleiding

17 November 2024
Panduit

Panduit CDE3 Handleiding

17 November 2024
Panduit

Panduit MEHT187 Handleiding

17 November 2024
Panduit

Panduit FPONE2 Handleiding

13 November 2024
Panduit

Panduit FPONE3 Handleiding

13 November 2024
Panduit

Panduit FPONE1 Handleiding

13 November 2024
Panduit

Panduit FPONE4 Handleiding

13 November 2024
Panduit

Panduit AFR4EC Handleiding

18 Oktober 2024
Panduit

Panduit AFR4RA Handleiding

18 Oktober 2024

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd