Overview
The ioLogik R1200 comes with 2 RS-485 serial ports, which can be
used in one of two ways:
1. For backup or asset monitoring, or
2. As an RS-485 repeater.
The ioLogik R1200 has the industry’s first all- -one design and in
provides Automatic Field Configuration via USB. No technical
background is needed, and maintenance is easy since users can
upload a device’s configuration settings and firmware via USB,
without needing to take a PC to the field site.
Model Selection:
ioLogik
DI
DIO
Relay
AI
AO
R1210
16
R1212
8
8
R1214
6
6
R1240
8
R1241
4
Package Checklist
1 ioLogik R1200 series remote I/O product
Documentation and software CD
Quick installation guide (printed)
Specifications
System
2 x -485-2W: Data+, Data-, GND RS
(5-contact terminal block)
8 KV ESD, 1 KV surge, 3 KV EFT
Modbus/RTU
24 VDC nominal, 12 to 48 VDC
I/O cable max. 14 AWG
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
under 200 g
Standard Models: -10 to 75°C (14 to
167°F)
Wide Temperature Models: -40 to 85°C
(-40 to 185°F)
-40 to 85°C (-40 to 185°F)
Ambient Relative
Humidity
5 to 95% (non-condensing)
Altitude
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to
function properly at higher altitudes.
Standards and
Certifications
UL 508, CE, FCC Class A
Warranty Period
5 years (excluding ioLogik R1214*)
Details
See www.moxa.com/warranty
*Because of the limited lifetime of power relay, products that use
this component are covered by a 2-year warranty.
Communication Parameters (Initial mode)
Parity
None, Even, Odd (default = None)
Data Bits
8
Stop Bits
1 2 (default = 1),
Flow Control
None, XON/XOFF (default = None)
Baudrate
1200 to 921.6 kbps (default = 9600)
Digital Input
Sensor Type
NPN, PNP, and Dry contact
I/O Mode
DI or Event Counter
Dry Contact
On: short to GND
Off: open
Wet Contact
(DI to COM)
On: 10 to 30 VDC
Off: 0 to 3 VDC
Isolation
3K VDC or 2K Vrms
Counter/Frequency
2.5 kHz, power off storage
Digital Output
I/O Mode
DO or Pulse Output
Pulse Wave
Width/Frequency
0.1 ms / 5 kHz
Over-voltage
Protection
45 VDC
Over-current Protection
2.6 A (4 channels @650 mA)
Over-temperature
Shutdown
175°C (typical), 150°C (min.)
Current Rating
200 mA per channel
Isolation
3K VDC or 2K Vrms
Relay Output
Type
Form A (N.O.) relay outputs, 5A
Contact Rating
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110
VAC
Inductance Load
2 A
Resistance Load
5 A
Breakdown Voltage
500 VAC
Relay On/Off Time
1500 ms (Max.)
Initial Insulation
Resistance
1G min. @ 500 VDC
Expected Life
100,000 times (Typical)
Initial Contact
Resistance
30 milli-ohms (Max.)
Pulse Output
0.3 Hz at rated load
Analog Input
Type
Differential input
Resolution
16 bits
I/O Mode
Voltage / Current
Input Range
0 to 10 VDC, 4 to 20 mA
Accuracy
± 0.1% FSR @ 25°C
± 0.3% FSR @ -10 and 60°C
± 0.5% FSR @ -40 and 75°C
Sampling Rate (all
channels)
12 samples/sec
Input Impedance
10M ohms (minimum)
Built-in Resistor for
Current Input
120 ohms
Analog Output
Resolution
12 bits
Output Range
0 to 10 VDC, 4 to 20 mA
Voltage Output
10 mA (Max.)
Accuracy
± 0.1% FSR @ 25°C
± 0.3% FSR @ -40 and 75°C
Load Resistor
• Internal power: 400 ohms
• External 24V power: 1000 ohms
Installation
Power and Networking
Connect the +12 to +48 VDC power line to the ioLogik R1200’s
terminal block terminal; connect the ground from the power V+
supply to the V- terminal. Connect the ground pin ( ) if earth
ground is available.
NOTE
For safety reasons, the wires attached to the power should
be at least 2 mm (12 gauge) in diameter.
4 5 6
www.moxa.com/support
The Americas:
- -528-6777 (toll-free: 1-888- - +1 714 669 2872)
Europe:
+49- -3 70 03 99-0 89
Asia-Pacific:
+886-2-8919- 1230
China:
+86- -5258-9955 (toll-free: 800- -5036) 21 820
5 Moxa Inc. All Rights Reserved 201 ,
Switch Settings
The R1200 series provides Dual/Rep and Run/Initial switch
setting to set up the communication mode. s
Duel (Default)
Dual RS-485 mode
Rep
Repeater mode
Run
User define communication parameters
Initial (Default)
Initial RS-485 communication parameters
Jumper Settings
The models with DIO or AI channels require configuring the
jumpers inside the enclosure. Remove the screw located on the
back panel and open the cover to configure the jumpers.
DIO mode configuration is
shown to the right (default: DO
Mode).
Analog mode configuration is
shown to the right (default:
Voltage Mode).
Mounting
The ioLogik R1200 is designed with a vertical form factor, and can
be used with both DIN-Rail and wall mounting applications. When
mounting on a rail, release the bottom mounting kit, install the
ioLogik on the rail, and then restore the bottom mounting kit to fix
the ioLogik to the rail. When using wall mounting, release both the
upper and bottom DIN-Rail kits.
LED Indicators
Type
LED Color
LED Action
PWR
Green
On:
Power On
Off:
Power Off
RDY
Green/
Red
Green:
System Ready
Green
Blinking:
Located
Red:
System Boot-up Error
Red
Blinking:
Firmware upgrade / USB upgrade
Green/Red
Blinking:
Safe Mode
Off:
System NOT Ready
P1
Green/
Amber
Green:
Tx
Amber:
Rx
Blinking:
Data Transmitting
Off:
Disconnected
P2
Green/
Amber
Green:
Tx
Amber:
Rx
Blinking:
Data Transmitting
Off:
Disconnected
I/O Wiring
Digital Input/Output (Sink Type)
Analog Input
Relay Output (Form A)
System Configuration
ioSearch Utility
ioSearch is a search utility that helps users locate an ioLogik R1200
on the local network. The utility can be found in the Document and
Software CD Software ioSearch; the latest version can be  
downloaded from Moxa website. ’s
Load Factory Default Settings
There are three ways to restore the ioLogik R1200 to the factory
default settings.
1. Hold the RESET button for 5 seconds.
2. Right click the specified ioLogik in the ioSearch utility and
select Reset to Default “ .”
3. Select Load Factory Default from the web console. “ ”
Modbus Address Table
Please refer to the user s manual for details of the ioLogik’ ’s
Modbus address.
NOTE
A “load” in a circuit schematic is a component or portion of
the circuit that consumes electric power. For the diagrams
shown in this document, “load” refers to the devices or
systems connected to the remote I/O unit.


Product specificaties

Merk: Moxa
Categorie: Niet gecategoriseerd
Model: ioLogik R1212-T
Stroom: 0.187 A
Soort serieële aansluiting: RS-485
Relatieve luchtvochtigheid: 5 - 95 procent
Aantal kanalen: 8 kanalen
Afmetingen (B x D x H): 27.8 x 124 x 84 mm
Signaal directie: Invoer/uitvoer
Input voltage bereik: 12 - 48 V

Heb je hulp nodig?

Als je hulp nodig hebt met Moxa ioLogik R1212-T stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Moxa

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd