Lenovo RT5kVA Handleiding
Lees hieronder de 📖 handleiding in het Nederlandse voor Lenovo RT5kVA (16 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 50 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/16
RT5kVA and RT6kVA 3U Rack or Tower
Uninterruptible Power Supplies
Product Guide
The RT5kVA and RT6kVA 3U Rack or Tower Uninterruptible Power Supply (UPS) offerings provide
extended power protection with increased efficiency and simplified power management to safeguard high-
availability of System x® and ThinkServer® server environments. With efficiency ratings of up to 98%,
these compact 3U rack or tower designs can help reduce energy usage without compromising
performance or reliability. The 3U Rack or Tower UPS units can be installed in a data center rack cabinet o
can be used as tower UPS units in office and distributed IT environments where extended power
protection is required.
The 3U Rack UPS unit (RT5kVA or RT6kVA) with the Extended Battery Module is shown in Figure 1.
Figure 1. RT5kVA or RT6kVA 3U Rack UPS unit (top) with Extended Battery Module (bottom)
Did you know?
3U Rack or Tower UPS units feature Advanced Battery Management (ABM) technology that uses a unique
three-stage charging technique that significantly extends battery service life and optimizes recharge time,
compared to traditional charging methods.
3U Rack or Tower UPS units can enhance system availability with individual receptacle groups or load
segments that can be programmed and controlled, which allows mission-critical devices to be prioritized
during shutdown to preserve battery run time if there is a prolonged power outage.
3U Rack or Tower UPS units come standard with UPS Manager software that integrates seamlessly with
the major virtualization platforms, which enables you to view and manage your entire power system from
your current dashboard. It also triggers live migration during power outages and avoids data loss by
gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.
RT5kVA and RT6kVA 3U Rack or Tower Uninterruptible Power Supplies 1
Check for Updates
Ordering information
Table 1 shows the part numbers and feature codes for the 3U Rack or Tower UPS models and options.
Table 1. Ordering part numbers and feature codes
Description Part number Feature code
UPS units
RT5kVA 3U Rack or Tower UPS (200-240VAC) 55945KX A540 (5594-RU6)
RT6kVA 3U Rack or Tower UPS (200-240VAC) 55946KX A541 (5594-RU6)
Extended Battery Modules
5kVA/6kVA 3U Rack or Tower Extended Battery Module 55946BX A542
Options
Environmental Monitoring Probe 46M4113 6146
The UPS models are shipped standard with the Network Management Card (NMC) installed, and they
include the following items:
An accessory kit that contains the following items:
Rack-mount kit
Rack installation instructions
Tower kit
Serial cable: 3.7 m (12 ft)
USB cable
Remote On/Off (ROO) and Remote Power Off (RPO) connector
A documentation kit that contains the following items:
Warranty flyer
Important Notices Manual
Documentation CD
Software CD, which contains UPS Manager power management software
The Extended Battery Modules (EBMs) are shipped with the following items:
An accessory kit that contains the following items:
Rack-mount kit
Tower kit
EBM power cable
EBM detection cable
A documentation kit that contains the following items:
Warranty flyer
Important Notices Manual
Documentation CD
The RT5kVA and RT6kVA 3U Rack or Tower UPS models do not ship with line cords. Table 2 lists the
compatible line cords that are suitable for the RT5kVA 3U Rack or Tower UPS unit. The RT6kVA 3U Rack
or Tower UPS unit has a hardwired terminal block connector for AC input power.
Table 2. Line cords for the RT5kVA 3U Rack or Tower UPS unit
Description Part number Feature code
DPI 30A Cord (NEMA L6-30P) 40K9614 6500
DPI 32A Cord (IEC 309 P+N+G) 40K9612 6502
DPI PDU+ Australian/NZ 3112 Cord (32A) 40K9617 6505
DPI PDU+ Korean 8305 Line Cord (30A) 40K9618 6506
RT5kVA and RT6kVA 3U Rack or Tower Uninterruptible Power Supplies 2
All 3U Rack or Tower UPS models come standard with an NMC installed. The NMC provides convenient,
over-the-network UPS remote monitoring and management through a standard web browser or UPS
Power Manager software. Figure 2 shows the UPS NMC.
Figure 2. UPS Network Management Card
The NMC has the following features:
Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
Simultaneous shutdown of protected servers
Configuration of automatic email messages in response to UPS alarms and to transmit periodic
reports
Customizable actions, including automatic shutdown if there is an extended power failure with
standard UPS Power Protector software
Control of UPS on/off switching with a web browser
Adjustment and control of load segments through the HTML interface, including sequential starting
of the installation and optimization of backup time by shutting down non-priority systems
Automatic date and time adjustment through an NTP server
Dual stack IP v4/IP v6
Recording of events and measurements in the card log
Data and event logging in the nonvolatile memory
Card firmware update through the network
10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
Measurement of humidity and temperature with the optional Environmental Monitoring Probe (EMP)
An optional Environmental Monitoring Probe (EMP) (part number 46M4113) is used to report local
temperature and humidity values and make that information available to management tools. The EMP
connects to the UPS via the NMC. The EMP is shown in Figure 3.
Figure 3. Environmental Monitoring Probe
The EMP has the following features:
RT5kVA and RT6kVA 3U Rack or Tower Uninterruptible Power Supplies 3
Product specificaties
Merk: | Lenovo |
Categorie: | UPS |
Model: | RT5kVA |
Heb je hulp nodig?
Als je hulp nodig hebt met Lenovo RT5kVA stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS Lenovo
15 Mei 2023
3 Mei 2023
25 April 2023
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Apc
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Tripp Lite
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS CyberPower
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
2 December 2024
2 December 2024
2 December 2024
2 December 2024
18 November 2024
17 November 2024
17 November 2024
17 November 2024
16 November 2024
15 November 2024