H.Koenig KOL6812 Handleiding
Lees hieronder de 📖 handleiding in het Nederlandse voor H.Koenig KOL6812 (148 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 150 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/148

Instruction manual
Manuel d'utilisation
Gebruachsanweisung
Gebruiksaanwijzing
Manual de Usuario
Manuale d’uso
KOL6812
PORTABLE AIR CONDITIONER
CLIMATISEUR MOBILE
MOBILE KLIMAANLAGE
DRAAGBARE AIRCONDITIONER
AIRE ACONDICIONADO
PORTATIL CONDIZIONATORE
PORTATILE


ENGLISH SAFETY INSTRUCTIONS
Thank you very much for selecting this new model of Portable Air Conditioner, please read this
Use and Care Manual carefully before installing and using this appliance. Please keep this Use
and Care Manual properly for future reference.
The refrigerant used in portable air conditioner is the environmentally friendly hydrocarbon
R290.This refrigerant is odorless, and compared to the alternative refrigerant, the R290 is an
ozone-free refrigerant.
Please read the instructions before use and repair.
The drawings provided in this manual may not be the same as the physical objects. Please
refer to the physical objects.
WARNING
lDo not use means to accelerate the defrosting process
or to clean, other than those recommended by the
manufacturer.
lThe appliance shall be stored in a room without
continuously operating ignition sources (for example:
open flames, an operating gas appliance or an operating
electric heater.)
lDo not pierce or burn.
lBe aware that refrigerants may not contain an odour.
lAppliance shall be installed, operated and stored in a
room with a floor area larger than12.5 m2.
lKeep any required ventilation openings clear of
obstruction.
lServicing shall be performed only as recommended by
the manufacturer.
lThe appliance shall be stored in a well-ventilated area
where the room size corresponds to the room area as
specified for operation.
lAny person who is involved with working on or breaking
into a refrigerant circuit should hold a current valid
certificate from an industry-accredited assessment

!
!
authority, which authorises their competence to handle
refrigerants safely in accordance with an industry
recognised assessment specification.
l Servicing shall only be performed as recommended by
the equipment manufacturer. Maintenance and repair
requiring the assistance of other skilled personnel shall
be carried out under the supervision of the person
competent in the use of flammable refrigerants.
l All working procedure that affects safety means shall
only be carried by competent persons.
l Be careful not to bump when moving to avoid leakage in
the refrigeration line.
Flammable material. Refer operators Read technical Read operators
manual manual manual
This appliance contains R290/Propane a flammable refrigerant
The maximum dosage of refrigerant is 260g.
NOTES:
l The air conditioning is only suitable for indoor use, and is
not suitable for other applications.
l Follow local grid interconnection rules while installing the
air conditioning and ensure that it is properly grounded. If
you have any question on electrical installation, follow the
instructions of the manufacturer, and if necessary, ask a
professional electrician to install it.
l Place the machine in a flat and dry place and keep a
distance of above 50cm between the machine and the
surrounding objects or walls.
lAfter the air conditioning is installed, ensure that the
power plug is intact and firmly plugged into the power
outlet, and place the power cord orderly to prevent
someone from being tripped or pulling out the plug.
lDo not put any object into the air inlet and outlet of the air
conditioning. Keep the air inlet and outlet free from
obstructions.
lWhen drainage pipes are installed, ensure that the
drainage pipes are properly connected, and are not
distorted or bended.
lWhile adjusting the upper and lower wind-guide strips of
the air outlet, pluck it with hands gently to avoid damaging
wind-guide strips.
lWhen moving the machine, make sure that it is in an
upright position.
lThe machine should stay away from gasoline, flammable
gas, stoves and other heat sources.
lDon't disassemble, overhaul and modify the machine
arbitrarily, otherwise it will cause a machine malfunction
or even bring harm to persons and properties. To avoid
danger, if a machine failure occurs, ask the manufacturer
or professionals to repair it.
lDo not install and use the air conditioning in the bathroom
or other humid environments.
lDo not pull the plug to turn off the machine.
lDo not place cups or other objects on the body to prevent
water or other liquids from spilling into the air
conditioning.
lDo not use insecticide sprays or other flammable
substances near the air conditioning.
lDo not wipe or wash the air conditioning with chemical
solvents such as gasoline and alcohol. When you need to
clean the air conditioning, you must disconnect the power
supply, and clean it with a half-wet soft cloth. If the
machine is really dirty, scrub with a mild detergent.
lThis device is not intended for use by persons with
reduced capacity on the physical, mental or sensory or
lack of experience and knowledge (including children),
unless they have had instructions to use the appliance by
a person responsible for their safety use of the appliance
and understand the hazards involved. Children should be
supervised to ensure they do not play with the device.
lDo not operate this appliance if it has a damaged cord or
plug, if it is not working properly or if it has been damaged
or dropped. If the supply cord is damaged, it must be
replaced by the manufacturer or its service agent or a
similarly qualified person in order to avoid a hazard.
lThe appliance shall be installed in accordance with
national wiring regulations.
lThe device must not be used if it has been dropped, it
obvious signs of damage are visible or if it has leaks.
TRANSPORTATION, MARKING AND STORAGE FOR UNITS
1. Transport of equipment containing flammable refrigerants
Compliance with the transport regulations
2. Marking of equipment using signs
Compliance with local regulations
3. Disposal of equipment using flammable refrigerants
Compliance with national regulations
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage to the
equipment inside the package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to be stored together will be determined
by local regulations.
The appliance shall be stored so as to prevent mechanical damage from occurring
Remark:
The best operating ambient temperature for cooling is 17-35 ° C.
Fuse Parameter: φ5.0x20mm 3.15A,250Vac.
Appliance is filled with flammable gas R290, and the maximum charge of refrigerant is 260g.
GWP value of R290refrigerant is 3.
Any repairs you need, contact the nearest authorized Service Centre and strictly follow
manufacturer’s instruction only.

FEATURES AND IDENTIFICATION OF PARTS
1. Features
lNew appearance with compact design, more luxury and upscale.
lOutlet louver swing automatically and wind direction up to consumer needs.
lBeautiful and simple appearance, humanized design for remote control storage, which can be
placed in storage bracket at the back of the unit body.
lSimple operation, LED digital display control panel and high-end LCD remote control.
lWinding pillar and universal socket can protect power cord better.
l24-hour Timer function, unique on/off reminding music.
l3-minute re-start delay protection to compressor and other multiple protection functions.
lUnique exhaust hose and fasteners, convenient installation.
2. Identification of Parts
1. Control panel
2. Horizontal louver
3. Remote control receiving window
4. Top panel
5. Front shell
6. Universal wheels
7. Handle
8. Back shell
9. Winding pillar
10. Chassis
11. Upper filter assembly
12. Drain cover and stopper
13. Lower filter assembly
14. Remote control
15. Round connector and exhaust hose
16. Adapter of exhaust hose
17. Window kits

OPERATIONS AND SETTINGS
1. Control Panel
This section explains proper mobile air conditioner operation.
2. Control Panel Operation
A. Power button: Press the power button, the power indicator lights up in green; when the power
is on, press the power button, the power indicator light is off (or red).
B. Mode button: Touch this key to switch and select unit working mode you want, all modes turn
as COOL – DEHUM – FAN , the indicator will light up accordingly.
C. Fan button: Press this button to change fan speed to High, Medium or Low.
D. Up button: Press the up key to adjust the set temperature or timing up.
E. Down button: Press the down key to adjust the set temperature or timing up.
F. Timer button: Press the timer button to set the timing, query timing, and cancel the timing.
G. "Up" + "Down" button: Press this group of composite keys at the same time to switch the display
temperature (Fahrenheit / Celsius).
H. "Timer" + "Up" button: Press this group of composite keys at the same time to select sleep
mode.
I. “Timer” + “Fan” button: Press this group of composite buttons at the same time to turn the
swing function on or off.
3. Remote Control Operation
Up and down button
Fan speed button
!
Timer button
!
Sleep button
LCD display window
Power button
Mode button
Auto-swing button
Auto-clean button

1) Power: Press this button to start the unit when it is energized or stop the unit when it is in
operation.
2) Mode: Press this button to select operation mode.
3) : Press this button to increase room temperature and timer setting.
4) : Press this button to decrease room temperature and timer setting.
5) Fan: Press this button to select fan speed in sequence: Low → Medium → High.
6) Auto-Swing: Press this button to turn on or turn off auto-swing function.
7) Sleep: Press this button to select or cancel sleep mode (only effective under coolingoperation or
energy conversation modes).
8) Timer: press this button to set AUTO-ON and AUTO-OFF time. Time can be adjusted between
0.5-24 hours. It jumps by 0.5 hour interval within 5 hours, and 1 hour interval over 5 hours, set
time will flash 5 times on screen then confirm the setting.
Before using your remote, install the AAA batteries into remote control.
1) Press and glide the battery cover on the back of the remote control, then you can remove the
cover.
2) Insert two new alkaline AAA batteries into the battery compartment, being sure to note the proper
polarity.
Reattach the battery cover, making sure the locking tab clicks into place.
Notes:
lUse alkaline batteries only. Do not use rechargeable batteries.
lWhen replace batteries, always replace both batteries with new batteries, do not mix old and
new batteries.
lIf the air conditioner will not be used for an extended period of time, remove the batteries from
the remote control.
4. Remote Control Storage
1) Insert remote controller into built-in compartment in left side of unit, and push it gently for
closure.
2) Press the lower part of built-in compartment gently to open it and take out remote controller.
Note: In order to avoid losing the remote control, please put the remote control inside of the
storage place when you not use it.
Be sure to note proper
polarity of batteries

WARNING
If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water, do not use the
remote control if the batteries have any leakage.
If you eat the liquid from the batteries, brush your teeth
and see doctor. The chemicals in batteries could cause
burns or other health hazards.
HANDLING AND TRANSPORTATION
1. Handle and move the unit
1) Hold handles on side panels to move the unit in upright position.
Note:
lMake the unit in the upright position whatever handling or moving it.
lDrain the water in the unit completely to prevent water leakage and wet the floor or carpet before
handling or moving the unit.
lTake out the remote control from the storage area and keep it.
Remote!control!
storage!area!

INSTALLATION & ADJUSTMENT
1. Installation
Notes:
lKeep this mobile air-conditioner in upright position at least 2 hours before first installation.
lThis air-conditioner may be moved indoor conveniently; keep the unit in upright position while
moving it. The air-conditioner shall be placed at flat surface.
lDo not install or operate this air-conditioner in bathroom or other wet environments.
1) Installation of exhaust hose assembly and its adapter.
A. Take out the exhaust hose and its connector and adapter, to remove the plastic bag.
B. Extend one end of exhaust hose, screw the end without slot of round connector onto it with
anticlockwise direction at least 3 laps.
C. Extend another end of exhaust hose, screw the adapter onto it with anticlockwise direction at
least 3 laps.
Note: Screw round connector and adapter into right position, at least 3 laps, to keep good
connection of exhaust hose assembly.
2) Installation of window seal-plate
A. Make the window half open, put the seal-plate into window, either in vertical or horizontal
position.
B. Extend seal plate parts and adjust it to the length of window, keep both ends to meet window
edge, fix it with screws then.
Note:
lKeep two ends of window seal-plate to meet the window edges well, to assure seal effect.
lTurn the screw in good position.

3) Installation of the unit
A. Move the unit with the exhaust hose assembly installed in front of window and keep the unit at
least 50cm away from the walls or other objects.
B. Install the rectangle end of exhaust hose assembly into the corresponding rectangle hole in
window seal-plate assembly, fix it with screw and close the window.
Note:
lSlide the adapter downwards and assure adapter installed in good position.
lAssure the slant panel direction to match seal-plate direction.
lExhaust hose cannot be bent or with flexure higher than 45°, in order to keep good ventilation
of exhaust hose.
Important notes:
The exhaust hose is 280mm-1500mm long and this length is determined based on the
specification of the air-conditioner (s). Do not use prolonged the hose or replace it with other
different hoses as this may affect the functions of the air-conditioner. The exhaust hose must
be smooth or it may lead air-conditioner overheat and damage.

DRAINAGE INSTRUCTION
1. Manual drainage:
1) Once the unit shuts down upon water-full, turn off the unit and then unplug.
2) Put the tray below the water outlet at the back of the unit.
3) Screw off the drain cover, unplug the water stopper for water flow into the tray.
4) Plug in stopper and screw the drain cover tightly onto water outlet after drainage.
Notes:
lProtect the drain cover and water stopper properly.
lMove the unit carefully to avoid the leakage it is necessary.
lTilt the unit slightly backwards when draining.
lBlock the drain hole as soon as possible before the tray is full if it cannot hold all water in the
unit to prevent the water leakage and wet the floor or carpet.
lWater stopper and drain cover must be tightly installed, to avoid new condensate to wet the floor
or carpet when the unit re-starts working.
2. Continuous drainage
1) Screw off the drain-cover & unplug the water stopper.
2) Connect drain-hole with φ13mm drain hose, as deep as possible to avoid leakage.
3) Pull the drain hose to bathroom or outdoor.
Notes:
lDrain hose must be installed when there’s no water in the tray.
lIt is suggested that not to use continuous drainage when unit is in COOL mode, to ensure enough
water recycle in the unit to enhance the system cooling effects.
lPut the drain hose in an inaccessible place, not higher than drainage hole and keep drain hose
straight without any flexure.
lKeep the drain cover and its stopper properly when continuous drainage is adopted.
lDrain pipe needs to be purchased separately
Drain Cover
MULTIPLE PROTECTION FUNCTIONS
1. Anti-frozen protection function
Under COOL mode, when the compressor continuously runs over 10 minutes, if tube
temperature is ≦2℃/36℉ for 20 seconds, the anti-frozen protection function will be on, E4 will
be shown on LCD display, compressor and water wheel motor will stop working, but upper fan
remains running; If tube temperature≧8℃/46℉, the unit will stop anti-frozen protection and
recover to the original working condition. Compressor will re-start working with 3 minutes delay
for protection.
2. Water-full safety alarm and shut –off protection function
When the water volume exceeds its alarm level in chassis, warning sounds automatically and
water-full icon is lighting in LCD display, you need to drain the condensate and re-start the
unit.(For more information about how to drain, refer to the “Drainage Instruction” please). If the
unit is not shut down manually, the unit will recover to the original operating status automatically
once the water is fully drained. Or connect the power to re-start the unit again.
3. Delay protection function of compressor
This unit offers restart protection to compressor. Except that the compressor may start
immediately when the unit is energized first time, there is 3-minute delay re-start protection after
compressor is shut down.
MAINTENANCE AND SERVICE
Note: Be sure to turn off the unit and pull out the plug
before maintain or send to service center.
1. Surface cleaning
1) Clean the unit surface with wet soft cloth and do not use
chemical solvents such as alcohol and gasoline to avoid
any damage to unit.
2) Clean the dirty air outlet or louvers with wet soft cloth and
detergent.
3) Any chemical solvent is prohibited to use for unit cleaning
or put such things near the unit for a long time.
4) Any thinner, alcohol-glazer or other similar solvents is
prohibited for unit cleaning.
2. Filter cleaning
Clean the filter once every two weeks, or it would
influence the unit function if filter clogged with dust.
1) How to clean filter

A. Grip the filter handle and pull it out gently in correct
direction.
B. Clean the dirty particles in filter by cleaner if it is
necessary.
C. Immerse and wash the filter gently into warm water (about
40℃) mixed with neutral cleaner, and then rinse and dry
them thoroughly in the shade.
Notes:
lPull out the filter gently.
lRemoval of filter at back panel is at priority then for the
filter at side panel, to avoid any twist or damage to filter.
lDo not squash the mesh.
lDo not hit the mesh with sharp objects or brush.
3. Installation of the filter
Aim the end of the filter toward slot then push filter
gently into slot.
Notes:
lBe sure to install the filter to side panel then for the filter
to back panel.
lInstall the filter with opposite direction of removal.
lInstall the filter into place gently to avoid any damage to
filter.
4. End of Season Storage
1) Screw off the drain cover and pull out the stopper to drain
condensate water completely. (Note: the tilt angle of the
unit must be≦30).
2) Keep unit running in fan mode for half day to dry inside of
unit completely to prevent from going moldy.
3) Turn off the unit, pull out plug then wrap the power cord
around the wire-winding pillar, insert the plug into the
universal fixing hole at the back panel of the unit, install
the water stopper and drain cover.
4) Remove the heat exhaust hose assembly, clean and keep
it properly.
Notes:
lHold the exhaust hose assembly with both hands when
removal.
lPush the fasteners aside on exhaust air outlet using your
thumbs, then pull out exhaust hose assembly.
5) Pack the air-conditioner properly with soft plastic bag and
put it in dry place with appropriate dust-proof measures,
and keep the unit away from children.
6) Take out the batteries from the remote control and keep
it properly.
Note:
Assure the unit is stored in a dry place. All accessories of
the unit shall be protected together properly.
!
2) Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable
gas or vapor being present while the work is being performed.
3) General work area
All maintenance staff and others working in the local area shall be instructed on the nature of
work being carried out. Work in confined spaces shall be avoided. The area around the
workspace shall be sectioned off. Ensure that the conditions within the area have been made
safe by control of flammable material.
4) Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to
ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking,
adequately sealed or intrinsically safe.
5) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
6) No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any
pipe work that contains or has contained flammable refrigerant shall use any sources of ignition
in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources,
including cigarette smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which flammable refrigerant can possibly be released
to the surrounding space. Prior to work taking place, the area around the equipment is to be
surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed.
7) Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period that
the work is carried out. The ventilation should safely disperse any released refrigerant and
preferably expel it externally into the atmosphere.
8) Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification. At all times the manufacturer’s maintenance and service guidelines shall
be followed. If in doubt consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
a. The charge size is in accordance with the room size within which the refrigerant containing parts
are installed.
b. The ventilation machinery and outlets are operating adequately and are not obstructed.
c. If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the
presence of refrigerant.
d. Marking to the equipment continues to be visible and legible. Markings and signs that are illegible
shall be corrected.
e. Refrigeration pipe or components are installed in a position where they are unlikely to be
effects of aging or continual vibration from sources such as compressors or fans.
5. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall
not be used.
6. Leak detection methods
The following leak detection methods are deemed acceptable for systems containing
flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may
not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is
suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the
LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate
percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode
the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system
both before and during the brazing process.
7. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, it is important that best practice is followed
since flammability is a consideration. The following procedure shall be adhered to:
1) Remove refrigerant.
2) Purge the circuit with inert gas.
3) Evacuate.
4) Purge again with inert gas.
5) Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall
be “flushed” with OFN to render the unit safe. This process may need to be repeated several
times. Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to
fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down
to a vacuum. This process shall be repeated until no refrigerant is within the system. When the
final OFN charge is used, the system shall be vented down to atmospheric pressure to enable
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are
to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources
and there is ventilation available.
8. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
1) Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant
contained in them.
2) Cylinders shall be kept upright.
3) Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
4) Label the system when charging is complete (if not already).
5) Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak
tested on completion of charging but prior to commissioning. A follow up leak test shall be
carried out prior to leaving the site.
9. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with
the equipment and all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that
electrical power is available before the task is commenced.
1) Become familiar with the equipment and its operation.
2) Isolate system electrically.
3) Before attempting the procedure ensure that:
a) Mechanical handling equipment is available, if required, for handling refrigerant cylinders.
b) All personal protective equipment is available and being used correctly.
c) The recovery process is supervised at all times by a competent person.
d) Recovery equipment and cylinders conform to the appropriate standards.
4) Pump down refrigerant system, if possible.
5) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
6) Make sure that cylinder is situated on the scales before recovery takes place.
7) Start the recovery machine and operate in accordance with manufacturer's instructions.
8) Do not overfill cylinders. (No more than 80 % volume liquid charge).
9) Do not exceed the maximum working pressure of the cylinder, even temporarily.
10) When the cylinders have been filled correctly and the process completed, make sure that the
cylinders and the equipment are removed from site promptly and all isolation valves on the
equipment are closed off.
11) Recovered refrigerant shall not be charged into another refrigeration system unless it has been
cleaned and checked.
10. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment
stating the equipment contains flammable refrigerant.
11. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total
system charge is available. All cylinders to be used are designated for the recovered refrigerant
and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders
shall be complete with pressure relief valve and associated shut-off valves in good working
order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in good working order.
Hoses shall be complete with leak-free disconnect couplings and in good condition. Before
using the recovery machine, check that it is in satisfactory working order, has been properly
maintained and that any associated electrical components are sealed to prevent ignition in the
event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to
an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The evacuation process shall be carried out prior to returning the compressor to the
suppliers. Only electric heating to the compressor body shall be employed to accelerate this
process. When oil is drained from a system, it shall be carried out safely.

Appendix
Schematic diagram of the air-conditioner
For specific technical parameters of the model, refer to rating label on the product.
ENVIRONMENT
CAUTION:
Do not dispose of this product as it has with other household products. There is a separation of this
waste product into communities, you will need to inform your local authorities about the places where
you can return this product. In fact, electrical and electronic products contain hazardous substances
that have harmful effects on the environment or human health and should be recycled. The symbol
here indicates that electrical and electronic equipment should be chosen carefully, a wheeled waste container
is marked with a cross.
Adeva SAS / H.Koenig Europe - 8 rue Marc Seguin - 77290 Mitry Mory - France
www.hkoenig.com - sav@hkoenig.com - contact@hkoenig.com - Tél: +33 1 64 67 00 01
Evaporator
Condenser
Compressor
Capillary

lL'entretien doit être effectué conformément aux
recommandations du fabricant de l'équipement.
L'entretien et la réparation nécessitant l'assistance
d'autres personnes qualifiées doivent être effectués sous
la supervision d’une personne compétente en matière
d'utilisation des réfrigérants inflammables.
lToute procédure de travail affectant la sécurité ne doit
être effectuée que par des personnes compétentes.
lVeillez à ne pas cogner l’appareil lorsque vous vous
déplacez pour éviter toute fuite du circuit de
réfrigération.
matières inflammables voir mode d’emploi lire le manuel lire le mode d’emploi
technique
Cet appareil contient le réfrigérant R290 à base de propane inflammable
La charge maximale de réfrigérant est de 260 g.
Remarque :
lLe climatiseur ne convient que pour une utilisation à
l’intérieur et ne convient pas pour d’autres usages..
lRespectez les règles de branchement au réseau local lors
de l’installation du climatiseur et assurez-vous qu’il soit
correctement mis à la terre. Si vous avez des doutes
concernant l’installation électrique, suivez les
instructions du fabricant et, si nécessaire, demandez à un
électricien professionnel de l’installer.
lPlacez l’appareil sur une surface plane et sèche et
maintenez une distance supérieure à 50 cm entre la
machine et les objets ou les murs environnants.
lUne fois l’appareil installé, assurez-vous que la fiche du
lCet appareil n'est pas destiné à être utilisé par des
personnes présentant des capacités réduites sur le plan
physique, mental ou sensoriel ou bien manquant
d'expérience ou de connaissance, (y compris les enfants),
sauf si elles ont eu des instructions concernant l'utilisation
de l'appareil par une personne responsable de leur
sécurité et qu’elle en comprennent les risques. Les
enfants doivent être surveillés pour s'assurer qu'ils ne
jouent pas avec l'appareil.
lN’utilisez pas l’appareil si son câble d’alimentation ou sa
prise est endommagée, s’il ne fonctionne pas
correctement, s’il a été abimé ou s’il est tombé. Si le câble
d’alimentation est endommagé, il doit être remplacé par
le fabricant ou son agent ou encore par une personne
qualifiée afin d’éviter tout risque.
lL'appareil doit être installé conformément aux
réglementations d’installation électrique en vigueur.
lL’appareil ne doit pas être utilisé s’il a chuté, s’il y a des
signes visibles de dommages ou en cas de fuite

2. Identification des pièces
1. Panneau de commande
2. Grille d'aération horizontale
3. Emplacement de la télécommande
4. Partie supérieure
5. Partie avant
6. Roues universelles
7. Poignée
8. Partie arrière
9. Enrouleur
10. Réservoir
11. Filtre supérieur
12. Couvercle de vidange et bouchon
13. Filtre inférieur
14. Commande à distance
15. Raccord rond et tuyau de sortie
16. Adaptateur du tuyau de sortie
17. Kits de fenêtre

1) Power : appuyez sur ce bouton pour démarrer l'appareil lorsqu'il est éteint ou pour l'arrêter
lorsqu'il est en fonctionnement
2) Mode : appuyez sur ce bouton pour sélectionner le mode de fonctionnement.
3) appuyez sur ce bouton pour régler/augmenter la température
4) appuyez sur ce bouton pour régler/diminuer la température
5) Ventilateur : appuyez sur ce bouton pour régler la vitesse du ventilateur selon l’ordre : Low →
Medium → High
6) Auto-Swing : appuyez sur ce bouton pour allumer ou éteindre la fonction d’oscillation.
7) Veille : appuyez sur ce bouton pour sélectionner ou annuler le mode veille (uniquement en mode
de refroidissement ou d’économie d’énergie)
8) Timer : appuyez sur ce bouton pour définir le démarrage et l'arrêt automatiques de la minuterie.
Le temps peut être réglé entre 0,5 et 24 heures. Il progresse par intervalle de 30 mn pour les 5
premières heures et par intervalle d’une heure après 5 heures. L’heure programmée clignotera
5 fois à l’écran, puis confirmera le réglage.
Avant d’utiliser votre télécommande, installez les piles AAA dans la télécommande.
1) Appuyez sur le couvercle du compartiment de la batterie situé à l’arrière de la télécommande
et faites-le glisser pour pouvoir le retirer.
2) Insérez deux nouvelles piles alcalines AAA dans le compartiment des piles, en veillant à
respecter la bonne polarité. Replacez le couvercle des piles en vous assurant que la languette
de blocage se met en place.
Remarque :
lUtilisez des piles alcalines uniquement. Ne pas utiliser de piles rechargeables.
lLors du remplacement des piles, changez toujours les deux piles par des piles neuves, ne
mélangez pas piles neuves et usées.
lSi le climatiseur n'est pas utilisé pendant une période de temps prolongée, retirez les piles de la
télécommande.
Assurez-vous de
respecter la bonne
polarité des piles.
Product specificaties
Merk: | H.Koenig |
Categorie: | Airco |
Model: | KOL6812 |
Kleur van het product: | Wit |
Timer: | Ja |
Gewicht: | - g |
Breedte: | - mm |
Diepte: | - mm |
Hoogte: | - mm |
Geluidsniveau: | - dB |
Soort: | Mobiele airconditioner uit één stuk |
Aantal snelheden: | 3 |
Type timer: | Digitaal |
Air conditioner functies: | Cooling,Dehumidifying,Fan |
Jaarlijks energieverbruik (koelen): | - kWu |
Energie-efficiëntieklasse (koeling): | A |
Op afstand bedienbaar: | Ja |
Koelcapaciteit in watt (opgegeven): | - W |
Energieverbruik per uur (koeling): | - kWu |
Energieverbruik per uur (verwarming): | - kWu |
Koelcapaciteit (max): | 12000 BTU/h |
Koel capaciteit in watt (max): | 3500 W |
Verwarmingscapaciteit in watt (max): | - W |
Verwarmingscapaciteit in watt (opgegeven): | - W |
Afstandsbediening inbegrepen: | Ja |
Timerduur (maximum): | 24 uur |
Comfort-slaapstand: | Ja |
Heb je hulp nodig?
Als je hulp nodig hebt met H.Koenig KOL6812 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Airco H.Koenig

7 Januari 2023
Handleiding Airco
- Airco Electrolux
- Airco Bosch
- Airco Candy
- Airco Samsung
- Airco Delonghi
- Airco Panasonic
- Airco LG
- Airco AEG
- Airco Bauknecht
- Airco BEKO
- Airco Daewoo
- Airco Grundig
- Airco Honeywell
- Airco Inventum
- Airco Karcher
- Airco Medion
- Airco Remeha
- Airco Siemens
- Airco Toshiba
- Airco Unold
- Airco Vaillant
- Airco Whirlpool
- Airco Zanussi
- Airco Zibro
- Airco Adler
- Airco Airwell
- Airco Akai
- Airco Amana
- Airco Amcor
- Airco Apc
- Airco Arcelik
- Airco Argo
- Airco Balay
- Airco Bartscher
- Airco Bavaria
- Airco Be Cool
- Airco Bestron
- Airco Blaupunkt
- Airco Blumfeldt
- Airco Bodin
- Airco Bomann
- Airco Brandt
- Airco D-Let
- Airco Daikin
- Airco Daitsu
- Airco Defy
- Airco Dimplex
- Airco Dometic
- Airco Domo
- Airco Duracraft
- Airco Duux
- Airco Easy Home
- Airco Eco-De
- Airco Eden
- Airco Edgestar
- Airco Edy
- Airco Einhell
- Airco Emerio
- Airco Emerson
- Airco Eurom
- Airco Everglades
- Airco Evolar
- Airco Exquisit
- Airco Fairland
- Airco Ferroli
- Airco Finlux
- Airco Firstline
- Airco Fral
- Airco Frigidaire
- Airco Frilec
- Airco Fronius
- Airco Fuave
- Airco Fuji Electric
- Airco Fujitsu
- Airco G3 Ferrari
- Airco GE
- Airco General Electric
- Airco GlobalTronics
- Airco Gorenje
- Airco Gree
- Airco Gutfels
- Airco Haier
- Airco Hisense
- Airco Hitachi
- Airco Holland Electro
- Airco Home Electric
- Airco Hotpoint
- Airco Hotpoint-Ariston
- Airco HQ
- Airco Hyundai
- Airco Iceberg
- Airco Innoliving
- Airco Insignia
- Airco Itho
- Airco Kalorik
- Airco Kelvinator
- Airco Kenmore
- Airco Klarstein
- Airco Koenic
- Airco Kogan
- Airco Korona
- Airco Lanaform
- Airco Lavorwash
- Airco Livington
- Airco Livoo
- Airco Logik
- Airco Magnavox
- Airco Maiko
- Airco Manta
- Airco Master
- Airco Maxicool
- Airco Meaco
- Airco Meireles
- Airco Melissa
- Airco Mesko
- Airco Mestic
- Airco Midea
- Airco Mistral
- Airco Mitsubishi
- Airco Moa
- Airco MPM
- Airco MundoClima
- Airco Nabo
- Airco Nedis
- Airco Philco
- Airco Prem-i-air
- Airco Primo
- Airco Princess
- Airco Profile
- Airco Progress
- Airco Proklima
- Airco Proline
- Airco Protector
- Airco Qlima
- Airco RCA
- Airco REMKO
- Airco Rotel
- Airco Rowenta
- Airco Royal Sovereign
- Airco Russell Hobbs
- Airco Sanyo
- Airco Sauber
- Airco Saunier Duval
- Airco Sencor
- Airco Sencys
- Airco Sharp
- Airco Sigma
- Airco SMC
- Airco Sonnenkonig
- Airco SPT
- Airco Starlyf
- Airco Stirling
- Airco Suntec
- Airco Tarrington House
- Airco Taurus
- Airco TCL
- Airco Team
- Airco Technisat
- Airco Teco
- Airco Tectro
- Airco Telefunken
- Airco Termozeta
- Airco Theben
- Airco Thomson
- Airco Tomado
- Airco Tosot
- Airco Toyotomi
- Airco Trilec
- Airco Tristar
- Airco Tronix
- Airco Trotec
- Airco Truma
- Airco Ufesa
- Airco Vestel
- Airco Vivax
- Airco Waeco
- Airco Westinghouse
- Airco White Knight
- Airco Whynter
- Airco Woods
- Airco Zelmer
- Airco Jocca
- Airco Jocel
- Airco Just Fire
- Airco OK
- Airco Olimpia Splendid
- Airco OneConcept
- Airco Oregon Scientific
- Airco Ozito
- Airco Becken
- Airco Black And Decker
- Airco Camry
- Airco Clatronic
- Airco Concept
- Airco ECG
- Airco Elba
- Airco Essentiel B
- Airco Guzzanti
- Airco Heinner
- Airco Khind
- Airco Orbegozo
- Airco Profilo
- Airco Trisa
- Airco Vox
- Airco Wilfa
- Airco Anslut
- Airco Kunft
- Airco Soler And Palau
- Airco Conrad
- Airco Ansonic
- Airco Aspes
- Airco Comfee
- Airco Corberó
- Airco Danby
- Airco Equator
- Airco Esatto
- Airco IFB
- Airco Infiniton
- Airco Koldfront
- Airco Listo
- Airco Orima
- Airco Svan
- Airco Ardes
- Airco Eldom
- Airco Premium
- Airco Teesa
- Airco Alpatec
- Airco ElectriQ
- Airco Heylo
- Airco HTW
- Airco Prime3
- Airco Avidsen
- Airco SereneLife
- Airco DCG
- Airco Kubo
- Airco Malmbergs
- Airco Challenge
- Airco Calor
- Airco Riffel
- Airco Broan
- Airco RIDGID
- Airco KDK
- Airco Bimar
- Airco Climadiff
- Airco Tripp Lite
- Airco Igenix
- Airco Mabe
- Airco Equation
- Airco Godrej
- Airco Milectric
- Airco Orava
- Airco Simplicity
- Airco Cecotec
- Airco Baxi
- Airco Thermex
- Airco Keystone
- Airco Sanus
- Airco Carrier
- Airco Furrion
- Airco Rinnai
- Airco Sheffield
- Airco Carson
- Airco Artrom
- Airco Carrefour Home
- Airco Céliera
- Airco Commercial Cool
- Airco Coolix
- Airco Hokkaido
- Airco Kibernetik
- Airco Norpole
- Airco Senville
- Airco SHE
- Airco CyberPower
- Airco Perfect Aire
- Airco Ausclimate
- Airco Be Quiet!
- Airco Ariston Thermo
- Airco Element
- Airco Dantherm
- Airco Noveen
- Airco Argoclima
- Airco Heller
- Airco DEXP
- Airco Chigo
- Airco Elgin
- Airco Evapolar
- Airco EcoFlow
- Airco Liebert
- Airco Avalon Bay
- Airco NewAir
- Airco Braemar
- Airco ActronAir
- Airco Klimaire
- Airco General
- Airco Consul
- Airco SEEGER
- Airco LERAN
- Airco Friedrich
- Airco Aerian
- Airco Polocool
- Airco Convair
- Airco Companion
- Airco Volteno
- Airco Arcoaire
- Airco AFINTEK
- Airco Brivis
- Airco MRCOOL
- Airco B-Air
- Airco Monzana
- Airco Kaden
- Airco Geist
- Airco GoldAir
- Airco Sôlt
- Airco Avallon
- Airco Ravanson
- Airco Create
- Airco Columbia Vac
- Airco TURBRO
- Airco BISWIND
- Airco House & Luft
- Airco Daizuki
- Airco Bonaire
- Airco Evapcool
- Airco Vostok
- Airco American Comfort
- Airco Ocean Breeze
- Airco Quirky
- Airco Krone
- Airco KwiKool
- Airco Big Ass Fans
- Airco Arctic King
- Airco Omega Altise
- Airco Climachill
- Airco Heat Controller
- Airco Luma Comfort
- Airco AireMax
- Airco Kaco
- Airco Middle Atlantic
- Airco Goodwe
- Airco Swegon
- Airco InAlto
- Airco JHS
- Airco FREONIC
- Airco ARCTIC WIND
- Airco Electroline
- Airco BLUEPALM
- Airco KuulAire
- Airco Cool-Space
- Airco BOSFOR
- Airco Aconatic
- Airco VänEE
- Airco Mayer
- Airco Yamazen
- Airco Corona
- Airco Symphony
- Airco Soler & Palau
- Airco Universal Blue
Nieuwste handleidingen voor Airco

31 Maart 2025

30 Maart 2025

30 Maart 2025

29 Maart 2025

29 Maart 2025

29 Maart 2025

29 Maart 2025

29 Maart 2025

29 Maart 2025

29 Maart 2025