Description
Detection lens
Fixing springs
LEDās for testing and
IR acknowledgement
IR sensor (detection) * The light measurement accuracy (Lux) is aīected
by the environment (furniture, ground, walls...).
If necessary, the level has to be adjusted by
potentiometer or programming tool.
Instances of lighting levels
Settings
Position of
potentiometer
Lux value
approximate*
Application
auto test
preset (ā 400 Lux)
1 200 Corridor
>1 ... 2 < > 200 ... 400 <
2 400 Offices
>2 ... On < > 400 ... 1000 <
On 1000 Offices
Potentiometers
1 2 and
Programming tool for settings
The installer programming tool EEK001
can be used to set the following features
if the potentiometer is set on āauto testā:
- Lux levels ( )
- Time ( )
- Absence / presence detection
- Power up behaviour
- Active / passive cell .
Override remote control
The remote control EEK002 allows the
switching ON or OFF of the light ( ).
The EEK002 allows the same functionality
as the wallswitch.
-+
M
Detection areas
h
x
y
2,5 m2,5 m
2,5 m
6 m
1 m
Overlap
Occupancy Sensors
standalone
EEK510B
Occupancy Sensors
with pre-wired lead
EEK513W: 3 m
Occupancy Sensors
with pre-wired lead
and klik.system plug
EEK513P: 3 m
EEK515P: 5 m
h 2,5 m 3 m 3,5 m
x 5 m 5 m 5 m
y 7 m 8 m 9 m
IR receiver (remote controls
& programming tools)
&
Ć©
The āyā values are given for lateral range.
The range may be reduced if walking
towards the sensor.
Brightness measurement sensor
(under the detection lens)
EEK510B, EEK513W
EEK51.P
6LE000505C
zPIR Occupancy Sensors
1 6LE000505C
Action Settings Potentiometers
Use Auto settings
(factory) or set by
the programming
tool to switch the
light automatically
for a deļ¬ned time.
Auto Settings
Put the Lux potentiometer on āauto testā.
The settings are predeļ¬ned:
Lux = 400,
time = 20 min.
q: test mode for 2 min.
Programming tool settings EEK001
(manual settings inhibited).
1
on
2
lux
auto
test
Automatically switch
on the light for a
deļ¬ned time.
Installer settings
auto
test
1 min
1 h
20 min
1
on
2
lux
Test and validate the
detection zone.
Test mode
Move the potentiometer 1 to āauto testā.
On this position, the programming tool
EEK001 can be used.
1
on
2
lux 1
on
2
lux
auto
test
auto
test
Technical characteristics
Electrical characteristics
Supply voltage 230V~ +10/-15% 50/60Hz
240V~ +/-6% 50/60Hz
Consumption with no load 2,4 VA / 270 mW
Upstream protection circuit breaker 16 A
Functional characteristics
Lighting output operating time 1 min. 1 h
Brightness level 5 1000 Lux
Recommended installation height 2,5 3,5 m
Detection range Ć 7 m
(installed product height: 2.5 m)
Fixing accessorie
Screws ( No 8), Protective cover
Products can be connected in parallel.
Hole size required 60 mm
Environment
Storage temperature -20 Ā°C +60 Ā°C
Class of insulation II
IK 03
Index of protection IP41
Fire resistance 650 Ā°C
Connection capacity (EEK510B)
0.5 mm2 to 1.5 mm2 ļ¬exible,
0.5 mm2 to 1.5 mm2 rigid
Operating altitude 2000m
Operating temperature :
Factory settings
Luminosity threshold 400 lux
Lighting time 20 min.
Mode Presence
Power Up OFF
Active cell (Luminosity Cell) ON
Functional modes
The detector has 2 diīerent modes.
- Presence detection (automatic).
- Absence detection (semi-automatic).
The power up and cell operation can be set for each
mode. A normally open retractive switch connected
to the product makes it possible to reverse the
lighting output state.
This state is maintained for the time period set
by the potentiometer or the programming tool 2
EEK001.
Presence detection (automatic mode)
In this mode the light is controlled by motion in the
detection area and ambient light levels.
If presence is detected whilst the light levels are
below the required Lux level, the sensor is activated
and keeps the light on whilst there is still occupancy
and for the time out period afterwards. Once the
sensor has deactivated the lights, it will require
a new occupancy whilst the ambient light levels
are below the required Lux levels to activate the
lights again. This mode can be changed via the IR
remote control EEK001 (default mode is presence
detection: automatic).
Absence detection (semi automatic mode)
The sensor needs to be activated by a normally
open retractive switch or a user remote control
input. Once the sensor is activated, it will hold the
lights on whilst there is still occupancy and for the
time out period afterwards. Once the sensor has
deactivated the lights, it will require another input
from the wallswitch or the programming tool to
switch the lights on.
Power Up
A parameter of the detector allows the choice of
state for the lighting after power up (mains return).
During warm up phase, the green LED blinks. In the
Power up ON state, the lighting will automatically be
energised when mains power is initially supplied or
returned to the sensor. In the Power up OFF state,
the lighting will not be energised and the sensor will
not operate during warm up period. This parameter
is modiļ¬ed using the installer programming tool
EEK001.
POWER UP state:
ā¢ ON: the light is immediately switched on for 30 s
after power up. In case of detection, the light
(in automatic mode) remains on during the time
delay; otherwise the light is switched oī.
ā¢ OFF: the detector switches to the selected mode
after warm up.
Active / passive cell
Active cell
The photocell will inhibit the output from the sensor
if the ambient light level is suīcient.
If the sensor detects occupancy whilst the ambient
light level is below the required Lux level, the lights
will be activated. However if the ambient light level
increases to a value where it is above the required
Lux level during a certain time, the sensor will
detect it and switch oī the light.
Passive cell
The photocell will inhibit the output from the sensor
if at the time of detection the ambient light level is
suīcient. In case of detection, if the ambient light
level increases, the photocell will not turn oī the
light.
Product description
and operating principles
Occupancy sensors EEK are designed to detect
low level movements (e.g. person sitting at a desk).
Diīerent models are available:
- without lead: EEK510B for standalone and BESA
mounting
- with pre-wired lead (3 m): EEK513W to be
interfaced with the KLDS marshalling boxes
- with pre-wired lead (3 m or 5 m) and klik.system
plug to be interfaced with the KLMB marshalling
boxes: EEK513P, EEK515P.
Detection is by means of a pyroelectric sensor
located under the detection lens.
The occupancy sensor measures the brightness in
the room on a continuous basis and compares it to
the level preset on the potentiometer (or by means
of the programming tool EEK001).
Settings
The Lux threshold and time out period can be set
with the potentiometers or by using the installer
programming tool (EEK001).
Test Mode - Walk test
This mode makes it possible to validate the
detection area. To select this mode, set the
potentiometer 1 to the position āauto testā. The
green or red LED behind the lens is on for 2 seconds
after detection. The red LED indicates that the light
level measured is lower than current setting. If the
green LED is on, the light level measured is higher
than current setting.
There is a time out of 2 minutes which is reactivated
after each detection. The output is also switched
during 2 s. after each detection.
It is also possible to use the programming tool
EEK001 to set the detector in test mode.
This device must be installed by a suitably
qualiļ¬ed electrician according to the installa-
tionās standards.
Correct Disposal of This product
(Waste Electrical & Electronic
Equipment)
(Applicable in the European Union and other European
countries with separate collection systems).
This marking shown on the product or its literature indicates
that it hould not be disposed with other household wasted at
the end of its working life. To prevent possible harm to the envi-
ronment or human health from uncontrolled waste disposal,
please separate this from other types of wastes and recycle it
responsibly to promote the sustainable reuse of material re-
sources.
Household users should contact either the retailer where they
purchased this product, or their local government oīce, for
details of where and how they can take this item for environ-
mentally safe recycling.
Business users should contact their supplier and check the
terms and conditions of the purchase contract. This product
should not be mixed with other commercial wastes of disposal.
Usable throughout Europe
Ć„
and in Switzerland
Hager Controls hereby declares that the PIR Occupancy
Sensorsdevice complies with the essential requirements
and other relevant provisions of Directive 2014/53/EU.
The CE declaration is available on the:
www.hagergroup.com
16A
40Ā°C 45Ā°C
Temperature (CĀ°)
Amperes (A)
10A
2 6LE000505C
Mounting EEK510B
Surface mounting (with accessory EEK005)
1. Mount the BESA Box.
2. Screw the accessory on the BESA Box.
3. Remove the protective cover and the springs from the detector.
4. Wire the detector according to the recommended connection diagram.
5. Push and turn the detector to lock it into the accessory.
6. Open the slider to set the potentiometers according to the desired values.
Ceiling mounting
1. Cut out a 60 - 63 mm diameter hole using a hole saw.
2. Fix the detector by pushing both springs upward then insert them into the
hole.
3. Wire the detector according to the recommended connection diagram or
plug into the klik.system marshalling box.
4. Mount the protective cover over the terminals and screw the cable clamp.
5. Set potentiometers according to the desired values.
10 < t < 28 mm
Ceiling
t = thickness
Protective cover
Cable clamp
2
1
3 6LE000505C
Setting instructions
Product specificaties
Merk: | Hager |
Categorie: | Bewegingsmelders |
Model: | EEK513W |
Heb je hulp nodig?
Als je hulp nodig hebt met Hager EEK513W stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Bewegingsmelders Hager
1 Februari 2023
25 Januari 2023
Handleiding Bewegingsmelders
- Bewegingsmelders Bosch
- Bewegingsmelders Philips
- Bewegingsmelders Bticino
- Bewegingsmelders Honeywell
- Bewegingsmelders Alecto
- Bewegingsmelders Berker
- Bewegingsmelders Blaupunkt
- Bewegingsmelders Brennenstuhl
- Bewegingsmelders Devolo
- Bewegingsmelders Eminent
- Bewegingsmelders ESYLUX
- Bewegingsmelders Gira
- Bewegingsmelders Goobay
- Bewegingsmelders Hama
- Bewegingsmelders Hikvision
- Bewegingsmelders HQ
- Bewegingsmelders KlikaanKlikuit
- Bewegingsmelders Konig
- Bewegingsmelders Marmitek
- Bewegingsmelders Nedis
- Bewegingsmelders Niko
- Bewegingsmelders Perel
- Bewegingsmelders Renkforce
- Bewegingsmelders Schneider
- Bewegingsmelders Silvercrest
- Bewegingsmelders Smartwares
- Bewegingsmelders Steinel
- Bewegingsmelders Technaxx
- Bewegingsmelders Theben
- Bewegingsmelders TP Link
- Bewegingsmelders Velleman
- Bewegingsmelders Optex
- Bewegingsmelders Orbis
- Bewegingsmelders Arlo
- Bewegingsmelders DSC
- Bewegingsmelders Merten
- Bewegingsmelders Chacon
- Bewegingsmelders Vemer
- Bewegingsmelders Chamberlain
- Bewegingsmelders Black Box
- Bewegingsmelders Speed-Link
- Bewegingsmelders Busch-Jaeger
- Bewegingsmelders EVE
Nieuwste handleidingen voor Bewegingsmelders
7 Februari 2023
7 Februari 2023
7 Februari 2023
7 Februari 2023
7 Februari 2023
6 Februari 2023
6 Februari 2023
4 Februari 2023
4 Februari 2023
4 Februari 2023