Technical data Technische data Dati tecnici
Data in compliance with EN 50470-1, EN 50470-3, IEC 62053-21 and
IECī¢62053-23
Gegevens conform EN 50470-1, EN 50470-3, IEC 62053-21 en
IECī¢62053-23
Dati conformi alle norme EN 50470-1, EN 50470-3, IEC 62053-21 e
IECī¢62053-23
General characteristics Algemene karakteristieken Caratteristiche generali
Housing DIN 43880 Behuizing DIN 43880 Involucro DIN 43880 DIN 6 0
Mounting EN 60715 Montage EN 60715 Montaggio EN 60715 35 mmDIN rail
Depth Diepte ProfonditĆ 60mm
Weight Gewicht Peso 700g
Operating features Bedieningsfuncties FunzionalitĆ operative
Connection to single-phase network - number of wires Verbinding naar eenfasig netwerk - aantal draden Connessione alla rete monofase - numero di ī°li -2 (L1)
to three-phase network - number of wires naar driefasen netwerk - aantal draden alla rete trifase - numero di ī°li -4
Storage of energy values and
conī°guration
Internal ī±ash non volatile memory Opslag van energiewaarden en
conī°g
Intern ī±ash niet-vluchtig geheugen Memorizzazione dei valori di
energia e conī°gurazione
Memoria interna non volatile -c
Tariff for active and reactive energy Tarief voor reĆ«le en reactieve energie Tariffa per energia attiva e reattiva T1 ā¦ T2 230V - T1 ā¦ T8 Modbus-
Approval (according to EN 50470-1, EN 50470-3) Goedkeuring (volgens EN 50470-1, EN 50470-3) Omologazione (secondo EN 50470-1, EN 50470-3)
Reference Voltage (Un) phase / neutral Referentiespanning fase /nul Tensione di riferimento fase / neutro 230(Un) (Un) VAC
phase / phase fase / fase fase / fase 400VAC
Reference Current Referentie stroom Corrente di riferimento 5(Iref) (Iref) (Iref) A
Minimum Current Minimumstroom Corrente minima 0.25(Imin) (Imin) (Imin) A
Maximum Current Maximale stroom Corrente massima 125(Imax) (Imax) (Imax) A
Starting Current Startstroom Corrente di avviamento 0.020(Ist) (Ist) (Ist) A
Reference Frequency Referentie frequentie Frequenza di riferimento 50(fn) (fn) (fn) Hz
Number of phases / number of wires Aantal fasen / aantal draden 3 / 4Numero di fasi / numero di ī°li -
Certiī°ed Measures Gecertiī°ceerde maatregelen Misure certiī°cate kWh kWh kWh
Accuracy Nauwkeurigheid Precisione
- Active Energies (accord. to EN 50470-3) - Reƫle energie (conform EN 50470-3) - Energia attiva (secondo EN 50470-3) classe B / 1
- Active Powers (accord. to IEC 62053-21 and IEC 61557-12) - Reƫel vermogen (conform IEC 62053-21 en IEC 61557-12) - Potenza attiva (secondo IEC 62053-21 e IEC 61557-12)
- Reactive Energies (accord. to IEC 62053-23) - Reactive Energieƫn (conform IEC 62053-23) - Energia reattiva (secondo IEC 62053-23) classe 2
- Reactive Powers (accord. to IEC 62053-21) - Reactief vermogen (conform IEC 62053-21) - Potenza reattiva (secondo IEC 62053-21)
Supply Voltage and Power Consumption Voedingsspanning en Energieverbruik Tensione di alimentazione e potenza assorbita
Operating Supply Voltage range Intervallo tensione di alimentazione 92 ā¦ 276 / 160 ā¦ 480Bedrī³fsspanningbereik V
Maximum Power Consumption (Voltage circuit) Maximaal energieverbruik (Spanningscircuit) Potenza massima assorbita (circuito voltmetrico) VA / W ā¤2 / 0.6
Maximum VA burden (Current circuit) @ Maximale VA last (stroom circuit) @ Massimo assorbimento VA (circuito amperometrico) @ Imax Imax Imax VA ā¤0.7
Voltage Input Waveform Meetspanningsvorm Forma d'onda tensione di ingresso AC-
Voltage impedance Impedantie spanningsingang Impedenza circuito voltmetrico 1MĪ©
Current impedance Impedantie stroomingang Impedenza circuito amperometrico mĪ© ā¤20
Overload capability Overbelastingscapaciteit CapacitĆ di sovraccarico
Voltage continuous phase / neutral Spanning doorlopend fase /nul Tensione continuo fase / neutro 276VAC
temporary (1 s) phase / neutral fase /nul temporaneo (1 s) fase / neutro 300tī³delī³k (1 s) VAC
continuous phase / phase doorlopend fase / fase continuo fase / fase 480VAC
temporary (1 s) phase / phase fase / fase temporaneo (1 s) fase / fase 800tī³delī³k (1 s) VAC
Current continuous Stroom doorlopend Corrente continuo 125A
temporary (10 ms) temporaneo (10 ms) 3750tī³delī³k (10 ms) A
Measuring Features Meetfuncties Funzioni di misura
Voltage range phase / neutral Spanningsbereik fase /nul Intervallo di tensione fase / neutro 92 ā¦ 276VAC
phase / phase fase / fase fase / fase 160 ā¦ 480VAC
Current range Stroombereik Intervallo di corrente 0.020 ā¦ 125A
Frequency range Frequentiebereik Intervallo di frequenza 45 ā¦ 65Hz
Measured Quantities Gemeten hoeveelheden QuantitĆ misurate V, A, kWh, kvarh, PF, Hz, kW, kvar-
Display features Display functies Caratteristiche del display
Display type LCD with backlight Display type LCD met achtergrondverlichting Tipo di
visualizzazione
LCD retroilluminato -7.2 +3.2
Active Energy 7 digits + 2 decimal digits ReĆ«le Energie Energia attiva 7 cifre + 2 cifre decimali 0.01 ā¦ 9999999.997 cī³fers + 2 decimalen kWh
Reactive Energy 7 digits + 2 decimal digits Reactieve energie Energia reattiva 7 cifre + 2 cifre decimali 0.01 ā¦ 9999999.997 cī³fers + 2 decimalen kvarh
Voltage 3 digits + 1 decimal digit Spanning Tensione 3 cifre + 1 cifra decimale 92.0 ā¦ 276.03 cī³fers + 1 decimaal V
Current 2 digits + 2 decimal digits / 3+1 / 4+0 Stroom Corrente 2 cifre + 2 cifre decimali / 3+1 / 4+0 0.00 ā¦ 125.002 cī³fers + 2 decimalen / 3+1 / 4+0 A
Power factor 1 digit + 3 decimal digits with sign + capac./induc. indic. Powerfactor Fattore di potenza 1 cifra + 3 cifre decimali con segno + indic. capac. / 1 cī³fer + 3 decimalen + capaciteit./induc. indic.
indutt. --1.000 ā¦ 1.000
Frequency 2 digits + 2 decimal digits Frequentie Frequenza 2 cifre + 2 cifre decimali 45.00 ā¦ 65.002 cī³fers + 2 decimalen Hz
Active Power 2 digits + 2 decimal digits ReĆ«el vermogen Potenza attiva 2 cifre + 2 cifre decimali 0.00 ā¦ 34.502 cī³fers + 2 decimalen kW
Reactive Power 2 digits + 2 decimal digits Reactief vermogen Potenza reattiva 2 cifre + 2 cifre decimali 0.00 ā¦ 34.502 cī³fers + 2 decimalen kvar
Apparent Power 2 digits + 2 decimal digits Schī³nbaar
vermogen
2 cī³fers + 2 decimalen Potenza Apparente 2 cifre + 2 cifre decimali kVA 0.00 ā¦ 34.50
Running Tariff 1 digit Actueel tarief Tariffa in funzione 1 cifra T1 ā¦ T2 230V - T1 ā¦ T8 Modbus1 cī³fer -
Display refresh period Toon verversingsperiode Frequenza di aggiornamento del display 1s
Optical metrological LED Optische metrologische LED LED metrologico ottico
Front mounted red LED (meter constant) proportional to active imp/
exp Energy
Aan voorzī³de gemonteerde rode LED (meter
constant)
evenredig met actieve imp /
exp Energie
LED rosso frontale (costante del contatore) proporzionale all'energia imp /
exp. Attiva
p/kWh 1000
Safety Veiligheid Sicurezza
Overvoltage category Overspanningscategorie Categoria di sovratensione 3-
Protective class Beschermingsklasse Classe di protezione IIclasse
AC voltage test (EN 50470-3, 7.2) AC spanningstest (EN 50470-3, 7.2) Test di tensione AC (EN 50470-3, 7.2) 4kV
Degree of pollution Vervuilingsgraad Grado di inquinamento 2-
Operational voltage Nominale spanning Tensione di funzionamento 300V
Impulse voltage test Impulsspanningstest Test di tensione ad impulso 6(Uimp) (Uimp) (Uimp) 1.2/50 Ī¼s-kV
Housing material ī±ame resistance Resistenza alla ī°amma del materiale dell'involucroUL 94 Behuizing materiaal vlamwerendheid UL 94 UL 94 classe V0
Safety-sealing between upper and lower housing part Veiligheidsafdichting tussen bovenste en onderste behuizing Sigillo di sicurezza tra la parte superiore e quella inferiore dell'involucro -c
IR Connectable Communication Modules IR-koppelbare communicatiemodules Moduli di comunicazione IR collegabili
For communication modules Voor communicatiemodules Per moduli di comunicazione -c
Embedded Modbus communication GeĆÆntegreerde communicatie Modbus Comunicazione incorporata Modbus
Physical interface RS-485 - 3 wires / 2 x RJ-45 Fysieke interface RS-485 - 3 draden / 2 x RJ-45 Interfaccia ī°sica RS-485 - 3 ī°li / 2 x RJ-45 --, +, 0
Baud rate adjustable Baudrate Instelbaar VelocitĆ Baud regolabile 1200 ā¦ 38400bps
Parity adjustable: Odd, Even, None Pariteit Instelbaar: Oneven, even, geen ParitĆ regolabile: Dispari, Pari, Nessuno -c
Stop Bit adjustable Stop Bit Instelbaar Stop Bit regolabile -1, 2
Address adjustable Adres Instelbaar Indirizzo regolabile -1 ā¦ 247
Isolation class SELV Isolatieklasse SELV Classe di isolamento SELV -c
Tariff Tarief Tariffa
Tariff 1 Tarief 1 Tariffa 1 -c
Tariff 2 Tarief 2 Tariffa 2 230 Ā±20%VAC
Input impedance Ingangsimpedantie Impedenza di ingresso 224kĪ©
Environmental conditions Milieuomstandigheden Condizioni ambientali
Storage temperature range Opslagtemperatuur Temperatura di stoccaggio -25 ā¦ +70Ā°C
Operating temperature range Temperatura di funzionamento -25 ā¦ +55Bedrī³fstemperatuur Ā°C
Mechanical environment Mechanische omgeving Ambiente meccanico M1-
Electromagnetic environment Elektromagnetische omgeving Ambiente elettromagnetico -E2
Installation indoor only Installatie alleen binnen Installazione solo all'interno -c
Altitude (max.) Hoogte (max.) Altitudine (max.) mā¤2000
Humidity yearly average, without condensation Vochtigheid UmiditĆ media annuale, senza condensajaarlī³ks gemiddelde, zonder condensatie -ā¤75%
on 30 days per year, without condensation op 30 dagen per jaar, zonder condensatie su 30 giorni all'anno, senza condensa -ā¤95%
IP rating in built-in condition (front part) IP rating in ingebouwde conditie (voorkant) Grado di protezione IP in condizione di incasso (parte frontale) IP51(*)-
terminal block klemblok morsettiera IP20-
(*) For use in accordance with the MID Directive, the energy meter must be installed in a
distribution board/enclosure for modular products with a minimum protection rating IP30
The IP51 ratings apply to the meter parts exposed in front of (outside of) the cover of the
enclosure.
(*) Voor gebruik in overeenstemming met de MID-richtlīn moet de energiemeter
worden gemonteerd in een verdeelkast voor modulaire producten met een minimale
beschermingsklasse IP30. De IP51 is van toepassing op het gedeelte van de behuizing van
de energiemeter dat door de afdekplaat heen naar buiten steekt..
(*) Per l'utilizzo in conformitĆ alla direttiva MID, il contatore di energia deve essere installato
in un quadro di distribuzione per apparecchi modulari con grado di protezione minimo
IP30. Il grado di protezione IP51 ĆØ relativo a parti del contatore esterne al quadro (frontale
dell'apparecchio).
z
i
y
Sealable terminal cover Dimension
Verzegelbare
schroefklemafdekkap Afmetingen
Coprimorsetto sigillabile Dimensione
Wiring diagram
Cable stripping length and terminal screw torque
Aansluitschema
Kabelstriplengte en aandraaimomenten van de
aansluitklemmen
Schema di collegamento
Lunghezza di sguainatura del cavo e coppia della
vite del morsetto
MID certified
MID gecertiīceerd
Certiīcato MID
MID safety sealing
MID-verzegeling
Sigillo di sicurezza MID
6LE005394Ad
1 Hager Electro S.A.S., Boulevard dāEurope, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 6LE005394AdOCOM 136679
ECA310D
OK
1s
1s
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
By powering. Software
version and checksum
Active Energy Imported
Tariff 1 with Partial
register
Active Energy Exported
Tariff 1 with Partial
register
Active Energy Imported
Tariff 2 with Partial
register
Active Energy Exported
Tariff 2 with Partial
register
Reactive Energy
Imported Tariff 1
Reactive Energy
Exported Tariff 1
Reactive Energy
Imported Tariff 2
Reactive Energy
Exported Tariff 2
After 2 seconds it goes
back to the Main Page
Active Power
(L1, L2, L3)
Reactive Power
(L1, L2, L3)
Apparent Power
(L1, L2, L3)
Voltage
(L1-N, L2-N, L3-N)
Current
(L1, L2, L3)
Neutral current
Power factor
L1
Power factor
L2
Power factor
L3
Frequency
Modbus Address:
1 ... 247
Baud Rate:
1200-2400-4800-9600
19200-38400
Parity:
none-even-odd
Stop Bit:
1-2
Unidirectional
Bidirectional
Tariffs conīguration:
1T
2T input 230 V
8T input Modbus
Meter type
Main page is depending on current power direction
indication with the corresponding global and
partial energy register display.
Active energy exported
Reactive energy
imported
Reactive energy
exported
Tariff related Energies
Partial Register Reset
Measures reading
Conīguration
Serial number
Software version and
checksum
Display test
The cabling sequence (L1-L2-L3) is wrong. L1, L2 and L3
icons blink. Invert the voltage wires of 2 phases (phase 1 <ī¢>
phase 2 or phase 2 <ī¢> phase 3). Otherwise, by pressing the
"OK" button for at least 5 seconds, the message disappears
until the next restart.
Diagnostic message
Active energy imported
Three phase energy meter,
direct connection 125 A
with MID declaration of conformity
and Modbus RTU communication / agardio system
MID certiī°cation concerns active energy only.
User instructions
EU declaration of conformity:
http://hgr.io/r/eca310d
Power factor
Convention according to IEC 62053-23
Safety instructions
This device must be installed only by a professional electrician ī°tter
according to local applicable installation standards. Do not plug in
or unplug this product when the power supplying is ON. Its use is
only permitted within the limits shown and stated in the installation
instructions. The device and the equipement connected can be
destroyed by loads exceeding the values stated.
Operating principle
This 4 quadrants Modbus RTU meter measures the active and reactive
energy used in an electrical installation. This device can manage 2
tariffs by 230 VAC digital input and up to 8 controlled via communication.
Only the total active energy register can be used for billing purposes
according to measuring instrument directive (MID).
- Active Energy Class B (according to EN 50470)
- Active Power Class 1 (according to IEC 62053-21 and IEC 61557-12)
- Reactive Energy Class 2 (according to IEC 60253-23)
- Reactive Power Class 2 (according to IEC 62053-21).
This device has a backlighted LCD and 3 push-button keys to read
Energies, V, I, PF, F, P, Q and to conī°gure some parameters. The design
and manufacture of this meter comply with Standard EN 50470-3
requirements.
Product presentation
LCD display:
Energy for all tariffs
Tariff
Reactive power
inductive/capacitive
Phase indicator
Main Energy Register, not resettable
Partial Energy Register, resettable
Units
Energy import (consumption )
Energy export (production )
Communication activity status
Energy meter has received a
message with the correct address
and with the correct checksum,
but the meter has answered with
an Exception Message in case of
Modbus:
- illegal function
- illegal data address
- illegal data value
Commands
OK button: is used to conī°rm a modiī°cation of a
parameter (or of a digit of a numerical parameter) or to
answer to a question
SCROLL button: is used to scroll Menu pages or to
modify the whole value or a digit of a parameter
ESCAPE button: is used to escape to main menu from
anywhere or to skip back to the previous digit of the
value under modiī°cation
Optical metrological LED
Note:
If no button is pushed for at least 20 seconds the display goes back to the
Main Page and the backlight is switched off again.
Symbols
One phase
Three phases
Protected by double insulation (Class II)
Backstop: Reversal preventing device
Modbus RTU Communication
Recommendations:
Use HTGxxxH reference cables specially developed as accessories by
Hager.
Important:
It is essential to connect a resistance (reference HTG467H) of 120 Ohms
at the 2 ends of the connection.
agardio system:
The plug-in and services for ECA310D are directly integrated in agardio
manager HTG41xH.
Error condition:
When partial energy blinks, reset partial energy (maximum partial energy
register). When the display shows the message or ERROR N02 ERROR
N03, the meter has got a malfunction and must be replaced.
z
QS
P
- +
+
-
II I
III IV
kvar
kW
kvar
kW
PF PF ā¤0 ā„0
6LE005394Ad
2 Hager Electro S.A.S., Boulevard dāEurope, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 6LE005394AdOCOM 136679
ECA310D
OK
1s
1s
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Via voeding.
Softwareversie en check
som
Reƫle energie
geĆÆmporteerd Tarief 1
met gedeeltelī”k register
Reƫle energie
geƫxporteerd Tarief 1
met gedeeltelī”k register
Reƫle energie
geĆÆmporteerd Tarief 2
met gedeeltelī”k register
Reƫle energie
geƫxporteerd Tarief 2
met gedeeltelī”k register
Reactieve energie
geĆÆmporteerd Tarief 1
Reactieve energie
geƫxporteerd Tarief 1
Reactieve energie
geĆÆmporteerd Tarief 2
Reactieve energie
geƫxporteerd Tarief 2
Na 2 seconden gaat
het terug naar de
hoofdpagina
Reƫel vermogen
(L1, L2, L3)
Reactief vermogen
(L1, L2, L3)
Schī”nbaar
vermogen
(L1, L2, L3)
Spanning
(L1-N, L2-N, L3-N)
Stroom
(L1, L2, L3)
Nulgeleider stroom
Powerfactor
L1
Powerfactor
L2
Powerfactor
L3
Frequentie
Modbus-adres:
1 ... 247
Baudrate:
1200-2400-4800-9600
19200-38400
Pariteit:
geen-even-oneven
Stop Bit:
1-2
Unidirectionele
Bidirectionele
Tarieven conīguratie:
1T
2T ingang 230 V
8T ingang Modbus
Meter type
Hoofdpagina is afhankelī”k van de huidige aanduiding
van de stroomrichting met het bī”behorende
algemeen en gedeeltelī”ke energieregisterscherm.
Reƫle energie
geƫxporteerd
Reactieve energie
geĆÆmporteerd
Reactieve energie
geƫxporteerd
Tariefgerelateerde
energieƫn
Gedeeltelī”k register
resetten
Meetwaarden
Conīguratie
Serienummer
Softwareversie en
check som
Displaytest
De bekabelingsvolgorde (L1-L2-L3) is verkeerd.
Pictogrammen L1, L2 en L3 knipperen. Keer de
spanningsdraden van 2 fasen om (fase 1 <ī¢> fase 2 of fase
2 <ī¢> fase 3). Anders verdwī”nt het bericht door gedurende
ten minste 5 seconden op de knop "OK" te drukken tot de
volgende herstart.
Diagnostisch bericht
Reƫle energie
geĆÆmporteerd
Driefase energiemeter,
directe stroommeting 125 A
met MID-verklaring van overeenstemming
en Modbus RTU communicatie / agardio-systeem
MID certiī°cering heeft alleen betrekking op werkelī³ke energie.
Gebruikersinstructies
EU-conformiteitsverklaring:
http://hgr.io/r/eca310d
Powerfactor
Conventie volgens IEC 62053-23
Veiligheidsinstructies
Dit apparaat mag alleen worden geĆÆnstalleerd door een professionele
installateur in overeenstemming met de geldende installatienormen.
Sluit dit product niet aan of koppel het niet los bī³ ingeschakelde
spanning. Het gebruik ervan is alleen toegestaan binnen de aangegeven
grenzen en vermeld in de installatie-instructies. Het apparaat en het
aangesloten apparaat kunnen worden beschadigd door belastingen die
de vermelde waarden overschrī³den.
Werkingsprincipe
Deze 4-kwadranten Modbus RTU-meter meet de reƫle en reactieve
energie die wordt gebruikt in een elektrische installatie. Dit apparaat
kan 2 tarieven beheren via de binaire 230 VAC tarief ingang en 8
tarieven via de digitale communicatie interface. Alleen het totale actieve
energieregister kan voor factureringsdoeleinden worden gebruikt
volgens de meetinstrumentrichtlī³n (MID).
- Reƫle energieklasse B (volgens EN 50470)
- Reƫle vermogensklasse 1 (volgens IEC 62053-21 en IEC 61557-12)
- Reactieve energieklasse 2 (volgens IEC 60253-23)
- Reactieve vermogensklasse 2 (volgens IEC 62053-21).
Dit apparaat heeft een LCD-achtergrondverlichting en 3 druktoetsen om
de meetwaarden, V, I, PF, F, P, Q te lezen en om enkele parameters te
conī°gureren. Het ontwerp en de fabricage van deze meter voldoen aan
de vereisten van norm EN 50470-3.
Productpresentatie
LCD scherm:
Energie voor alle
tarieven
Tarief
Reactief vermogen
inductief/capacitief
Fase-indicator
Hoofdenergieregister, niet opnieuw
instelbaar
Gedeeltelī³k energieregister,
opnieuw instelbaar
Eenheden
Energie-import (consumptie )
Energie-export (productie )
Status van communicatieactiviteit
Energiemeter een bericht heeft
ontvangen met het juiste adres
en de juiste controlesom, maar de
meter heeft beantwoord met een
uitzonderingsbericht in het geval
van Modbus:
- illegale functie
- illegaal gegevensadres
- illegale gegevenswaarde
Commando's
OK-knop: wordt gebruikt om een wī³ziging van een
parameter (of een cī³fer van een numerieke parameter) te
bevestigen of om een vraag te beantwoorden
SCROLL-knop: wordt gebruikt om door menupagina's
te bladeren of om de hele waarde of een cī³fer van een
parameter te wī³zigen
ESCAPE-knop: wordt gebruikt om naar het hoofdmenu
terug te gaan of om naar het vorige cī³fer van de
gewī³zigde waarde terug te gaan
Optische metrologische LED
Opmerking:
Als er ten minste 20 seconden lang op geen enkele knop wordt
gedrukt, keert het display terug naar de hoofdpagina en wordt de
achtergrondverlichting weer uitgeschakeld.
Symbolen
Een fase
Drie fasen
Beschermd door dubbele isolatie (klasse II)
Backstop: apparaat om achteruitrī³den te voorkomen
Modbus RTU communicatie
Aanbevelingen:
Gebruik HTGxxxH-referentiekabels die speciaal zī³n ontwikkeld als
accessoires door Hager.
Belangrī”k:
Het is noodzakelī³k om een weerstand (referentie HTG467H) van 120
Ohm aan te sluiten op beide uiteinden van de datacommunicatiekabel.
agardio-systeem:
De plug-in en services voor ECA310D zī³n direct geĆÆntegreerd in Agardio
Manager HTG41xH.
Foutconditie:
In de situatie dat het woord Partial op het diplay knippert, dan heeft de
āpartialā teller de maximale waarde overschreden. In dit geval moet je
de āpartialā teller resetten.
In de situatie dat de foutmeldingen of op het ERROR N02 ERROR N03
display verschī³nen dan is er een defect in de meter. In deze situatie
moet de meter worden vervangen.
i
QS
P
- +
+
-
II I
III IV
kvar
kW
kvar
kW
PF PF ā¤0 ā„0
6LE005394Ad
3 Hager Electro S.A.S., Boulevard dāEurope, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 6LE005394AdOCOM 136679
Product specificaties
Merk: | Hager |
Categorie: | Elektriciteit meiter |
Model: | ECA310D |
Kleur van het product: | Wit |
Breedte: | 107 mm |
Diepte: | 60 mm |
Hoogte: | 92 mm |
Soort: | Elektronisch |
Internationale veiligheidscode (IP): | IP20 |
Certificering: | Midden |
Ingangsspanning: | 92/480 V |
Eenheid van de maatregel: | A, kWh |
Temperatuur bij opslag: | -25 - 70 Ā°C |
Meetfuncties: | Power current, Power factor, Power frequency, Voltage |
Bedrijfstemperatuur (T-T): | -25 - 55 Ā°C |
Aantal fases: | 3 |
Stroom (max.): | 125 A |
Aantal modules: | 6 |
Heb je hulp nodig?
Als je hulp nodig hebt met Hager ECA310D stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding Elektriciteit meiter Hager
8 April 2023
4 Maart 2023
14 Januari 2023
28 November 2022
24 November 2022
Handleiding Elektriciteit meiter
- Elektriciteit meiter ABB
- Elektriciteit meiter Apc
- Elektriciteit meiter Brennenstuhl
- Elektriciteit meiter Gembird
- Elektriciteit meiter Greenlee
- Elektriciteit meiter HQ
- Elektriciteit meiter Kathrein
- Elektriciteit meiter Plugwise
- Elektriciteit meiter Schneider
- Elektriciteit meiter Becken