Maintenance bypass switch module
FDC-BS10KMR
1. Introduction
Thank you for purchasing the Maintenance bypass switch from Forza. This module is used as an external maintenance bypass switch
to provide continuous power without shutting down the connected loads during UPS scheduled maintenance or battery replacement. It
is perfect to use in conjunction with 6K/10KVA UPS systems.
Important safety instructions
You must first read and closely follow all installation and operation instructions contained in this manual. Keep this guide in a safe place
for future reference.
2. Preliminary steps
Unpacking and inspection
Upon opening the box, make sure the following items are included:
• Maintenance bypass switch module (1)
• Signal control cable (1)
• Mounting bracket and M4 screw kit (1)
• User guide (1)
NOTE: Carefully inspect the unit before installation. Make sure that nothing inside the package is damaged or loose. Please keep the
original package in a safe place for future use.
3. Product overview
1. Input/ output terminal block (Refer to diagram 2 for details)
2. UPS input breaker on bypass
3. Two-position maintenance bypass switch
4. Output signal control slot
5. Output terminal (to load)
6. UPS output terminal
7. UPS input terminal
8. Utility input terminal
9. Grounding terminal
1 2 3 4
Diagram 1: Rear panel View
4.2. Installation and configuration
Important safety instructions
Installation and wiring must be performed by qualified personnel, and in accordance with the local electrical regulations and
codes. Also, you must observe the following guidelines:
1. Make sure the mains wire and breakers in the building are enough for the rated capacity of the UPS to avoid the hazards of electric
shock or fire.
Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS's maximum input current. Failure to do so may result in a broken or burned out receptacle.
2. For safety considerations, turn off the mains switch in the building before installation.
3. Turn off and shut down the connected UPS
4. Wiring sizes should be installed in accordance with the following table:
NOTE 1: The cable for 6K/6KL should be able to withstand currents of over 40A. It is recommended to use a 6 AWG or thicker wire for
safety and efficiency.
NOTE 2: The cable for 10K/10KL should be able to withstand currents of over 63A. It is recommended to use an 4 AWG or thicker wire
for safety and efficiency.
NOTE 3: The color selection of wires should be made according to the local electrical codes and regulations.
5. Remove the terminal block cover on the rear panel of the bypass switch module. Then connect the wires according to the terminal
block diagrams included in the section below.
4.3. Connection of the UPS to the external maintenance bypass switch module
1. Remove the terminal block cover on the rear panel of the bypass switch module.
2. Then connect the output terminals of the UPS to the UPS output terminals located on the bypass switch module.
3. Proceed to connect the utility input terminals of the UPS to the UPS input terminals on the bypass switch module.
4. Connect the signal slots of the UPS and the switch module using the supplied signal control cable.
5. Connect main utility line to utility input on the bypass switch module.
6. Finish by connecting the desired load to the bypass switch module output terminals (load).
UPS model
6K/6KL
10K/10KL
Wiring specification
6 AWG
4 AWG


Product specificaties

Merk: Forza
Categorie: Niet gecategoriseerd
Model: FDC-BS10KMR
Soort bediening: Draaiknop
Kleur van het product: Zwart
Gewicht: 4000 g
Breedte: 438 mm
Diepte: 210 mm
Hoogte: 86 mm
Materiaal behuizing: Staal
Stroom: 60 A
Montagewijze: Rekgemonteerd
Ingangsspanning: 120 - 250 V
Ondersteunde beveiligingsalgoritmen: SNMP
Temperatuur bij opslag: 0 - 40 °C
Frequentie: 50/60 Hz
Luchtvochtigheid bij opslag: 0 - 95 procent
Output current: 60 A
Spanning: 120 - 600 V
Rackcapaciteit: 2U
Bedrijfstemperatuur (T-T): 0 - 40 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 95 procent
Type product: Overbruggingsschakelaar
Aantal fases: 1
Output power capacity: 10 kVA
Laad-capaciteit: 10000 VA
Compatibele rackbreedte: 19 "
Maximum totaalstroomverbruik per fase: 63 A