Extron KNX 100G Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Extron KNX 100G (7 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 7 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/7
KNX 100G • Setup Guide
This setup guide covers the physical installation of the KNX 100G and KNXnet/IP tunneling from a PC to a KNX network during
conguration and commissioning.
The KNX 100G allows better integration of control with KNX building management systems (BMS). The product serves as a
gateway for control systems and ETS software to the KNX bus, and it is designed to be installed onto a DIN rail with a width of 1
unit (18 mm).
Power is supplied via the KNX bus; an external power supply is not necessary. The KNX bus can be accessed from any point on
the LAN. The IP address can be obtained by a DHCP server or by manual conguration. There are ve simultaneous connections
possible for access via KNXnet.
1
Figure 2. KNX 100G DIN Rail Installation
Installing Onto DIN Rail
1. Ensure the DIN rail is securely mounted onto the wall or furniture.
2. Place top rear against wall/furniture (Figure 2, 1).
3. Slide the unit down onto top of rail (Figure 2, 2).
4. Tilt the unit and snap onto the rail (Figure 2, 3).
Figure 1. KNX 100G Controls and Displays
DIN Rail
KNX 100G
Patent(s): www .extron.com/patents
33-2700-01 A
E
Prog. KNX
__.__.____
E
E
KNX 100G
KNX
Mode
IP
P/Esc
Conn
Up
Conn
Dn
e t
e t
KNX 100G
Place top rear against
wall/furniture.
Slide down the unit
onto top of rail.
Tilt the unit an
d
snap into rail.
1
2
3
KNX 100G
Pat ent(s): w ww.extron.com/pa tents
33-2700-01 A
E
KNX 100G
P
at ent(s):
www.ext ron.com/patents
33-2700-01 A
E
E
Prog. KNX
__.__.____
E
E
KNX 100G
KNX
Mode
IP
P/Esc
Conn
Up
Conn
Dn
est
e t
LAN
33-2558-01 B
www.e xtron.com/pat ents
Bottom View
I
A
B
E
G
H
C
D
F
A KNX Bus connector
B Programming Mode Button
C Programming Mode LED (Red)
D KNX LED (multicolor)
E Mode LED (multicolor)
F IP LED (multicolor)
G Button Connection Up
H Button Connection Down
I Ethernet/LAN Connector
Figure 3. KNX 100G Application Diagram
2
LED Status Indicators
C Programming Mode LED
LED STATUS Meaning
LED lights red Programming mode is active
LED Off Programming mode is not active
E Mode LED
LED STATUS Meaning
LED lights green Device is working in standard operation mode
LED lights red Programming mode is active
LED ashes green 1x...5x Programming mode is not active
Manual operation is active
The selected tunnel (1-5) is not used and free
LED ashes orange 1x...5x Programming mode is not active
Manual operation is active
The selected tunnel (1-5) is used and free
LED ashes red Programming mode is not active
Manual operation is not active
The device is not properly loaded for example after an interrupted download
F IP LED
LED STATUS Meaning
LED lights green The device has an active Ethernet link and valid IP settings.
LED lights red The device has an active Ethernet link and invalid IP settings or not yet received the IP settings by a
DHCP server.
LED ashes green IP telegram trafc
D KNX LED
LED STATUS Meaning
LED lights green KNX 100G successfully powered
LED ashes green Telegram trafc on the KNX bus
LED lights red shortly Communication failure on the KNX bus
est
est
KNX 100G
Patent(s): www.extron.com/patents
33-2700-01 A
E
Prog. KNX
__.__.____
E
KNX 100G
KNX
Mode
IP
P/Esc
Conn
Up
Conn
Dn
Ethernet
Twisted Pair
Cable
IPC P PRO
550
OV
ER
2
1
4
3
LIMIT
R
IR
1
2 3
4 5 6 7 8
Tx
Rx
T
x
Rx
RTS
CTS
COM
IR/S
ER
IAL
1
3
2
4
REL
AYS
FLE
X
I/
O
S
LIMI
T
OVE
R
eBU
S
SW
ITC HED
12 V DC
100 0
LINK
ACT
2
1
5
6
3
7
4
8
2
1
5 6
3
7
4
8
Light
Shutters
Dimmer
e
Thermostat
(Temperature)
Dimme
Volum
KNX 100G
IPCP Pro 550
IPCP
Pro 550
TLP Pro 725M
Net work
IPCP PRO 550
OVER
2
1
4
3
LIMIT
R
I
R
1
2
3
4 5 6
7
8
Tx
Rx
Tx
Rx
RTS
C
TS
COM
IR
/SE
R
IAL
1
3
2
4
REL
AYS
FLEXI/O
S
LIMIT
OV
ER
eBU
S
S
WITCH E D
12 V
DC
1000
LINK
A
CT
21
5 6
3
7
4
8
2
1
5 6
3
7
4
8
TLP Pro 725M
KNX
Bus
KNX 100G Network Installation
1. Using a certied KNX twisted pair cable, connect to the
KNX BUS located on the top of the device (see gure 3).
2. Connect an ethernet cable between the Ethernet port
located at the bottom of the KNX 100G and the local
network.
3. Congure the KNX 100G using ETS.
4. Congure your Extron Control System using the Extron
driver targeted at your congured KNX 100G.
NOTE: Engineering Tool Software (ETS) is an application
for designing, commissioning, and debugging KNX
installations. Click this to view and purchase ETS link
for your KNX setup. KNX system setup should be done
by a certied KNX professional.
3
KNX 100G Setup
1. Add KNX 100G Interface Within ETS
Within ETS, the KNX 100G interfaces can be selected and setup via “Bus Interfaces”.
NOTE: ETS can access congured KNX 100G interfaces without a database entry if the default settings are compatible with
the KNX installation. If the KNX 100G setup does not comply with installation conditions, it must be configured within an
ETS project. See Configure Interface Properties on page 4.
After connecting the KNX 100G to the LAN and the KNX bus, the device should automatically appear in ETS within the “Bus”
menu under “Discovered Interfaces”. By double clicking on the discovered interface, it will be selected as the current interface. On
the right side of the ETS window, all specic information and options of the connection appear (see gure 5).
2. Setup Individual Address for Tunneling
The device’s name and “Individual Address” can be changed within your ETS project. The KNX 100G has an individual address
which can be used to access the device.
The device supports up to ve connections for control. Each connection is associated with one of the ve individual addresses
in the device. The addresses can be assigned via ETS. Telegrams sent to the bus contain a sender address from one of the ve
additional addresses, and response telegrams can be transmitted to respective clients.
Additional individual addresses must be selected from the address range of the bus line in which the interface is installed and may
not be used by another device. The individual KNX 100G address and the addresses for additional tunneling connections can be
changed within the ETS project after the device has been added to the project.
Factory Default Settings
Setting Value
Individual Device Address
Number of congured KNXnet/IP tunneling
connection
Individual address of tunneling connection
IP address assignment: DHCP
Reset to Factory Device Settings
The following callouts reference Figure 1 on page 1.
1. Separate the KNX Bus connector A from the device.
2. Press and hold the Programming Mode button B.
3. Reconnect KNX Bus connector A of device.
4. Continue holding the Programming Mode button B for six seconds.
5. A short ashing of all LEDs (CDEF) visaulizes the successful reset of the device to factory default settings.
Figure 5. Changing Device Address in ETSFigure 4. New Connection in Bus Interfaces


Product specificaties

Merk: Extron
Categorie: Niet gecategoriseerd
Model: KNX 100G

Heb je hulp nodig?

Als je hulp nodig hebt met Extron KNX 100G stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Extron

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd