Smart Home Panel Installation Manual
WARN ING
The EcoFlow Smart Home Panel must be installed by a licensed electrician, who should
be familiar with all electrical codes, electrical wiring practices and experience working
with home electrical systems. Any accident, damage or personal injury caused by
incorrect installation is the sole responsibility of the user.
CONTENTS
3. Product Details
2. Specifications
4. What's in the box
5. Installation SOP Checklist
1. Safety Instructions
3.1 External Features
3.2 Internal Features
3
4
1
2
6. Installation Steps
7. System Commissioning and App Setup
8. FAQ
6.1 Preparation
6.2 Installation
6.2.1 Installing the Relay Module
6.2.2 Mounting
6.2.3 Wiring
10
12
14
16
23
24
6
7
1
1. Open all connected upstream circuit breakers and make sure the Grid Power Indicators are off.
2. Turn off DELTA Pro(s) from the SHP and ensure the DELTA Pro Power Indicators are off.
3. The alarm will sound if the SHP is energized while the front cover is open. Please ensure that the unit is de-
energized and the alarm has stopped
The SHP MUST be completely de-energized before being serviced
Complete the following to de-energize the SHP
1. The product must be installed by a licensed electrician and verified by local AHJ (Authority Having
Jurisdiction, i.e., your city, town, county or state).
2. The SHP defaults to grid mode when not powered. For safety, do not access or disconnect any load circuits
when there is an internal fault. Power down those loads and contact a licensed electrician or EcoFlow
technical support.
3. This product is not intended to be used as a service disconnect. To completely de-energize the product, the
user MUST open the upstream breakers as well as physically unplug all DELTA Pros. Failure to do so may
present a shock hazard.
4. DO NOT unplug relay modules while SHP is energized, because unplugging the relay module while the SHP
is energized may cause damage to the relay modules and SHP.
5. Smart Home Panel by itself does not provide an AFCI (Arc Fault Circuit Interrupter) function. AFCI or GFCI
protection may be available with an external AFCI accessory. Consult EcoFlow support for AFCI or GFCI
solutions.
6. All upstream breakers feeding SHP should be non-GFCI/AFCI. GFCI and AFCI protection should be
downstream of the SHP using GFCI/AFCI breakers or outlets. Follow NEC or local electrical codes for AFCI
or GFCI installation. An additional accessory panel to aid with installation of AFCI circuits may be available
from EcoFlow.
7. Do not use the product near a heat source, such as a fire or furnace. Do not place flammable gases or liquids
(e.g. Gasoline) near the device.
8. If there is a loud noise in the relay module, there may be a ground fault downstream of the SHP. The user
should clear the fault and replace the relay module before resetting the SHP for normal use.
9. Do not use the SHP if the Short-Circuit Current Rating (SCCR) at the electrical service entrance is above
10kA.
10. Do not install or operate the product outdoors or in damp/wet conditions.
11. Do not install or operate the product in extreme temperatures.
12. Do not use the product if it is damaged or appears to be damaged.
13. Do not connect the relay channels to circuit breakers higher than their current rating. Doing so can result in
damage to the relay modules.
14. The split-phase mode should be used for multi-wire circuits (MWBC, circuits sharing a balanced neutral),
and the circuits split across the two phases appropriately.
15. Adhere to all local and national safety regulations for installation and use.
16. If an overcurrent fault (breaker tripped) occurs, the corresponding relay module must be replaced to ensure
safe operation in the future.
17. This product is designed for residential use only.
18. Upstream circuit breakers protect the SHP only in grid mode. Only use circuit breakers with a fault current
interruption capability of 10kA or greater, 4ms or 5kA, 8ms.
19. The maximum total current for all input circuits under the grid mode is 160A.
1. Safety Instructions


Product specificaties

Merk: EcoFlow
Categorie: Niet gecategoriseerd
Model: Smart

Heb je hulp nodig?

Als je hulp nodig hebt met EcoFlow Smart stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd EcoFlow

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd

Festo

Festo VPPI Handleiding

21 November 2024
Festo

Festo SFAB Handleiding

21 November 2024
Festo

Festo SFAH Handleiding

21 November 2024
Festo

Festo DRRD-12 Handleiding

21 November 2024
Festo

Festo SDE3 Handleiding

21 November 2024
Festo

Festo SFTE Handleiding

21 November 2024
Festo

Festo CRVZS-5 Handleiding

21 November 2024