UPS BATTERY MODULE
Manual
DN- 8 R 17010 ev.2
2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during
installation and maintenance of the Extended Battery Pack (EPB). Please read all
instructions before operating the equipment and save this manual for future
reference. Only qualified service personnel with knowledge of batteries and the
required precautions should perform servicing.
DANGER
Batteries present a risk of electrical shock or burn from high
short- circuit current.
The EBP LETHAL VOLTAGES and has its own energy source
(batteries) that will carry live voltage even when not
connected to a source of power. Batteries also pose a danger
due leakage of hazardous chemicals.
• Remove watches, rings, or other metal objects
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or other metal parts on top of batteries.
• Keep unauthorized personnel away from batteries.
Failure to follow these instructions will result in death or
serious injury.
DANGER
Batteries may explode when exposed to open flame.
• Keep sparks and flames away from the batteries.
• Never dispose of batteries in a fire.
• Proper disposal of batteries is required.
• Refer to local codes for disposal requirements.
Failure to follow these instructions will result in death or
serious injury
3
WARNING
To reduce the risk of fire or electric shock:
• Install or service the EBP in a temperature and humidity
controlled, indoor environment, free of conductive
contaminants.
• Ambient temperature must not exceed 40°C (104°F).
• Do not operate near water or excessive humidity
(90% maximum).
• Over current protection and disconnect switch must be
provided by others.
• Install the EBP so that all wiring is inaccessible to users.
• The maximum number of EBP(s) per UPS is four.
• Failure to follow these instructions may result in death
or serious injury
Technical Notice
If the EBP requires any type of transportation, consult with the transport
company and take the recommended precautions. Always disconnect batteries
prior to transportation.
If the EBP must be stored, protect it from excessive humidity and heat.
The EBP should be mounted in an environment where the temperature is within
the required specs. Temperature is a major factor in determining battery life and
capacity. In a normal installation, the battery temperature is maintained
between 15°C and 25°C. Keep batteries away from heat sources.
Typical battery performance data are quoted for an operating temperature
between 20°C and 25°C. Operating it above this range will reduce the battery life
while operation below this range will reduce the battery capacity.
An unused battery should be recharged every 6 months. Temporarily connect
the EBP to AC supply and activate it for the time required for recharging the
batteries


Product specificaties

Merk: Digitus
Categorie: Server
Model: DN-170108
Kleur van het product: Zwart
Gewicht: 65000 g
Breedte: 443 mm
Diepte: 680 mm
Hoogte: 131 mm
Gewicht verpakking: 68200 g
Breedte verpakking: 585 mm
Diepte verpakking: 730 mm
Materiaal behuizing: Metaal
Vormfactor: Rackmontage/toren
Land van herkomst: China
Code UK-handelstarief: 85044085
Accu/Batterij voltage: 120 V
Ondersteund aantal accu's/batterijen: 20
Aantal: 1
Rack-montage: Ja
Rackcapaciteit: 2U
Bedrijfstemperatuur (T-T): 20 - 25 °C
Relatieve vochtigheid in bedrijf (V-V): 0 - 90 procent
Verpakkingsvolume: 119574 cm³
UPS-topologie: Dubbele conversie (online)
Hot-swap batterij: Ja