CyberPower CPS5000PRO Handleiding

CyberPower Airco CPS5000PRO

Lees hieronder de 📖 handleiding in het Nederlandse voor CyberPower CPS5000PRO (20 pagina's) in de categorie Airco. Deze handleiding was nuttig voor 9 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/20
Users Manual
CPS3500PIE/CPS3500P RO
CPS5000PIE/CPS5000PRO
K01-0000137-04
EN
CyberPower Systems, Inc.
Website: www.cpsww.com
CPS &CPS5000 Series 3500
Copyright © 2014 CyberPower Systems, Inc.
1
SAFETY AND EMC INSTRUCTIONS
Safety and EMC instruction
This manual contains important safety instructions. Please read and follow all instructions carefully during
installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or
operate your Emergency Power System (EPS).
CAUTION! To prevent the risk of re or electric shock, install in a temperature and humidity
controlled indoor area free of conductive contaminants. (Please see specications for acceptable
temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover.
CAUTION! EPS must be connected to an AC power outlet with circuit breaker protection. Do not
plug into an outlet that is not grounded. If you need to de-energize this equipment, turn o and unplug the
unit.
CAUTION! To avoid electrical shock, turn o the unit and unplug it from the AC power source before
servicing EPS, replacing the external battery or installing equipment.
CAUTION! To reduce the risk of re, only connect the EPS to a circuit with 40 amperes
( ) maximum branch circuit
CPS3500PIE/CPS3500PRO & CPS5000PIE/CPS5000PRO Series
over-current protection in accordance with the CE requirement.
CPS3500PIE Series include CPS3500PIE CPS3500PIE- CPS3500PIE-UK and other versions. FR
CPS3500P Series include CPS3500PRO ROCPS3500P -RO FRCPS3500P -UK and other versions. RO
CPS5000PIE Series include CPS5000PIE CPS5000PIE- CPS5000PIE-UK and other versions. FR
CPS5000P Series include CPS5000PRO ROCPS5000P -RO FRCPS5000P -UK and other versions. RO
CAUTION! The building wiring socket outlet (shockproof socket outlet) must be easily accessible
and close to the EPS.
CAUTION! Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
equipment) to connect the EPS to the building wiring socket outlet (shockproof socket outlet).
CAUTION! Please use only VDE-tested, CE-marked power cables to connect the loads to the EPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of the EPS
and the connected equipment does not exceed 3.5mA.
CAUTION! This is permanently connected equipment and only qualied maintenance personnel
may carry out installations.
CAUTION! Do not disconnect the mains cable on the EPS or the building wiring socket outlet
(shockproof socket outlet) during operations since this would remove the protective ground of the EPS
and of all connected loads.
CAUTION! THE EPS shall be connected to the emergency switching device.
CPS &CPS5000 Series 3500
Copyright © 20 CyberPower Systems, Inc.14
2
DO NOT USE FOR MEDICAL SUPPORT EQUIPMENT!OR LIFE
DO NOT use in any circumstance that would aect operation or safety of any life support equipment or
with any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of re or electric shock,
do not use with or near an aquarium. Condensation from the aquarium can cause the unit to short out.
DO NOT USE WITH LASER PRINTERS! The power demands of these devices will
overload and possibly damage the unit.
DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT
SUNLIGHT OR NEAR HEAT!
DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS HOUSING! S
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO
EPS OUTPUT SOCKETS.
SAFETY:
EN62040-1- 1
EMI:
Conducted Emission: IEC/EN 62040-2 Category C2
Radiated Emission: IEC/EN 62040-2 Category C2 ……
Harmonic Current: IEC/EN61000-3-2
Voltage Fluctuations and Flicker: IEC/EN61000-3-3
EMS:
IEC/EN61000-4-2(ESD)
IEC/EN61000-4-3(RS)
IEC/EN61000-4-4(EFT)
IEC/EN61000-4-5(lightning surge)
IEC/EN61000-4-6(CS)
IEC/EN61000-4-8(Magnetic)
IEC/EN61000-2-2 (Immunity to low frequency signals)


Product specificaties

Merk: CyberPower
Categorie: Airco
Model: CPS5000PRO
Kleur van het product: Geel
Gewicht: 45000 g
Breedte: 330 mm
Diepte: 260 mm
Hoogte: 440 mm
Gebruikershandleiding: Ja
LED-indicatoren: Stroom
Type verpakking: Doos
Vormfactor: Tower
Accu/Batterij voltage: 12 V
Ondersteund aantal accu's/batterijen: 20
Certificering: CE
Geluidsalarm(en): Ja
Responstijd: 10 ms
Meegeleverde software: PowerPanel Business
Uitgangsvermogen: 3500 W
Batterij capaciteit: 200 Ah
Stroomspanning bescherming: Over voltage, Overcharge, Overheating, Overload, Reverse polarity
Frequentie: 45/65 Hz
Web-gebaseerd management: Ja
Auto-herstart: Ja
Beheerprotocollen: SNMP/HTTP
Batterijtechnologie: Sealed Lead Acid (VRLA)
Type beeldscherm: LCD
Aantal AC uitgangen: 3 AC-uitgang(en)
Stopcontacttypes: Terminal, Type F
Output power capacity: 5 kVA
Ingang operation voltage (min): 140 V
Ingang operation voltage (max): 300 V
Uitgang operation voltage (min): 220 V
Uitgang operation voltage (max): 220 V
UPS-topologie: Dubbele conversie (online)
Hot-swap batterij: Ja
Output frequentie: 50/60 Hz
Hoorbare alarmstanden: Fault, Low battery alarm, Overload alarm, Battery replacement
Emergency Power Off (EPO): Ja
Aantal output fases: 1
Spanningsbeveiliging: Ja
Golfvorm: Sinus
Uitgangsfrequentieregeling: 50/60 Hz
Automatische uitgangsspanningaanpassing: Ja
Automatic Voltage Regulation (AVR): Ja
Automatische batterij test: Ja
Laadstroom: 45 A
Aantal type F-uitgangen: 2
Type invoerbescherming vereist: 3-polige stroomonderbreker
Bypass: Ja

Heb je hulp nodig?

Als je hulp nodig hebt met CyberPower CPS5000PRO stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Airco CyberPower

Handleiding Airco

Nieuwste handleidingen voor Airco