ZUMMESH-PART
ZÅ«mâ„¢ Wireless Partition Sensor
Installation Guide
Description
The Crestron® Zūm wireless partition sensor (ZUMMESH-PART) is used to facilitate
seamless control between two ZÅ«m spaces.
Powered with 24 VDC, the ZUMMESH-PART conveniently receives power from a
ZUMMESH-SIM or any Crestron 24 VDC power supply (both not supplied).
ZÅ«m Overview
A ZÅ«m space is an area, such as a board room or conference room, that is equipped
with ZÅ«m mesh devices such as dimmers, switches, keypads, and motion sensors.
ZÅ«m mesh devices create a wireless mesh network that facilitates seamless
communication between devices without using an independent wireless gateway.
Centralized control and monitoring is enabled by adding a ZUMMESH-NETBRIDGE
to the space and integrating a ZUMNET-GATEWAY and ZUM-FLOOR-HUB to the
Crestron control system (all not included).
NOTE: The ZUMMESH-NETBRIDGE requires a compatible J-box device (not
included) to provide power.
Install the ZUMMESH-PART
NOTE:
• Install and use this product in accordance with appropriate electrical
codes and regulations.
• Sensors must be mounted on a vibration-free surface.
Determine the Mounting Location
Position the ZUMMESH-PART about 2 ft (0.6 m) away from the partition. If
necessary, the ZUMMESH-PART can be mounted up to 4 ft (1.2 m) from the
partition. The lens on the ZUMMESH-PART must face the partition so that when
the partition is opened, the sensor sees the unobstructed room.
2 ft (0.6 m)
Partition
Mount the ZUMMESH-PART in a 1-gang electrical box:
1. Turn off the system power.
2. Connect the 2-pin terminal block to the 24 and G port on the ZUMMESH-PART.
When making connections, use 14 to 26 AWG wire, strip the ends of the wires
7/16 in (11 mm) (avoid nicking the conductors), and tighten the connector to
5 in-lb (0.5 to 0.6 Nm).
3. Secure the ZUMMESH-PART to the 1-gang box using the included screws. The
sensors must face towards the partition.
4. Attach a decorator style faceplate (not included).
5. Turn the system power on.
Standard 1-gang
electrical box
Ceiling
Mounting
screws (2)
Faceplate
(Not included)
ZUMMESH-PART
Mount the ZUMMESH-PART on a flat surface:
1. Turn off the system power.
2. Remove the two screws from the back of the ZUMMESH-PART and then
remove the bracket. Retain the screws.
3. Install the flat bracket to the back of the ZUMMESH-PART using the screws
removed in step 2.
4. Connect the 2-pin terminal block to the 24 and G port on the ZUMMESH-PART.
When making connections, use 14 to 26 AWG wire, strip the ends of the wires
7/16 in (11 mm) (avoid nicking the conductors), and tighten the connector to
5 in-lb (0.5 to 0.6 Nm).
5. Secure the ZUMMESH-PART to the ceiling using screws that are appropriate
for the mounting surface. The sensors must face towards the partition.
6. Attach a decorator style faceplate (not supplied).
7. Turn the system power on.
Ceiling
Mounting
screws (2)
Faceplate
(Not included)
ZUMMESH-PAR
Adjust the ZUMMESH-PART Sensitivity
The ZUMMESH-PART operates by emitting an IR pulse and then measuring the
reflected IR signal. The measurement of the reflected IR signal and the sensitivity
level determines if the partition is closed or open.
The ZUMMESH-PART has high, medium (default), and low sensitivity levels.
• High: Use when the partition is not being detected due to distance or partition
material.
• Medium (default): Sufficient for most installations.
• Low: Use when the partition is falsely detected due to reflectance from other
objects such as the ceiling, light fixtures, etc.
View and Adjust the Sensitivity Level:
The + and – buttons are used to view and adjust the sensitivity of the
ZUMMESH-PART. The + button increases the sensitivity and the - button decreases
the sensitivity.
To view and change the sensitivity level:
1. Press and hold the + or - button until the PART LED blinks.
• 1 blink: Sensitivity is low
• 2 blinks: Sensitivity is medium
• 3 blinks: Sensitivity is high
2. Continue holding the + button to increase the sensitivity or the - button to
decrease the sensitivity. Release the button when the desired sensitivity setting
is achieved.
3. Open and close the partition to verify the sensitivity level. The green PART LED
lights when the partition is closed. It takes several seconds for the
ZUMMESH-PART to determine that the partition is closed.
LED Functionality
PART LED:
• Lights green when the partition is closed.
• Is off when the partition is open.
NOTE: When the partition is opened or closed, there is a small delay for the
PART LED to change.
RM A LED:
• Lights solid red to indicate that the ZUMMESH-PART has not joined Room A.
• Once joined to Room A, the LED lights momentarily when a message is received
from a device in Room A.
RM B LED:
• Lights solid red to indicate that the ZUMMESH-PART has not joined Room B.
• Once joined to Room B, the LED lights momentarily when a message is received
from a device in Room B.
Add the ZUMMESH-PART to Existing ZÅ«m Spaces
NOTE:
• Scene 1 should be similar for both spaces. Occupancy sensors will recall
scene 1 for both spaces, so you want them both to recall the similar light
values. To set Scene 1, refer to the Zum Light Control System Setup Guide
(Doc. 7957) at www.crestron.com/manuals.
• The ZUMMESH-PART occupies one motion sensor slot in each room. Up
to seven additional motion sensors may be added in each room. When
the partition is opened, all motion sensors operate in unison to determine
occupancy and vacancy.
• Do not mix occupancy and vacancy sensors within the combined rooms.
Both rooms must use either occupancy or vacancy sensors.
Add the ZUMMESH-PART to Room A and then Room B by placing the ZÅ«m spaces
in Joining mode. The ZUMMESH-PART is added using button press sequences
on the ZÅ«m devices in the space. When performing the button press sequences,
remember the following:
• Perform consecutive button presses at a rate of one press per second.
• Transition between button press combinations on the same device within
1 second.
• When moving between devices, begin the next button press sequence before
the 4 minute timeout period expires.
Add the ZUMMESH-PART Using an AC powered Keypad, Dimmer, or Switch
1. Place Room A into Joining mode. Room A is the space where the
ZUMMESH-PART is mounted.
a. Press and hold both the top and bottom buttons until the LED lights.
b. Press the top button once.
c. Press the bottom button once. The LEDs on all devices in the space (except
battery powered devices) flash slowly to indicate that the devices are part
of the space and that the space is in Joining mode.
Press and hold until LED lights
Press and hold until LED lights
then then
Press 1x
Press 1x
2. Add the ZUMMESH-PART to Room A.
a. Press the + button 3 times. The RM A LED will flash with each button press
and then turn off.
b. Press and hold the + button until the RM A LED on the ZUMMESH-PART
lights. The ZUMMESH-PART is added to Room A.
Press and hold until LED lightsPress 3x then
3. Press any button on an AC-powered device that is part of the Room A ZÅ«m
space to exit Joining mode.
4. Place Room B into Joining mode as described in step 1 above.
5. Add the ZUMMESH-PART to Room B.
a. Press the - button 3 times. The RM B LED will flash with each button press
and then turn off.
b. Press and hold the - button until the RM B LED on the ZUMMESH-PART
lights. The ZUMMESH-PART is added to Room B.
Press and hold until LED lightsPress 3x then
6. Press any button on an AC-powered device that is part of the Room B ZÅ«m
space to exit Joining mode.
Add the ZUMMESH-PART using a J-box device:
1. Place Room A into Joining mode. Room A is the space where the
ZUMMESH-PART is mounted.
a. button 2 times.Press the SETUP
b. Press the TEST button once. The LEDs on all devices in the space (except
battery powered devices) flash slowly to indicate that the devices are part
of the space and that the space is in Joining mode.
T EST
SET UP
TEST
SETUP
TEST
SETUP
Press SETUP 2x
Press TEST 1x
then
2. Add the ZUMMESH-PART to Room A.
a. Press the + button 3 times. The RM A LED will flash with each button press
and then turn off.
b. Press and hold the + button until the LED on the ZUMMESH-PART lights.
The ZUMMESH-PART is added to Room A.
Press and hold until LED lightsPress 3x then
3. Press any button on an AC-powered device that is part of the Room A ZÅ«m
space to exit Joining mode.
4. Place Room B into Joining mode as described in step 1 above.
5. Add the ZUMMESH-PART to Room B.
a. Press the - button 3 times. The RM B LED will flash with each button press
and then turn off.
b. Press and hold the - button until the RM B LED on the ZUMMESH-PART
lights. The ZUMMESH-PART is added to Room B.
Press and hold until LED lightsPress 3x then
6. Press any button on an AC-powered device that is part of the Room B ZÅ«m
space to exit Joining mode.
Add the ZUMMESH-PART using an AV Bridge:
1. Place Room A into Joining mode. Room A is the space where the
ZUMMESH-PART is mounted.
a. Press and hold the button for 2 seconds. The LEDs on all devices in SETUP
the space (except battery powered devices) flash slowly to indicate that the
devices are part of the space and that the space is in Joining mode.
Press and hold until LED lights
2. Add the ZUMMESH-PART to Room A.
a. Press the + button 3 times. The RM A LED will flash with each button press
and then turn off.
b. Press and hold the + button until the LED on the ZUMMESH-PART lights. The
ZUMMESH-PART is added to Room A.
Press and hold until LED lightsPress 3x then
3. Press any button on an AC-powered device that is part of the Room A ZÅ«m
space to exit Joining mode.
4. Place Room B into Joining mode as described in step 1 above.
5. Add the ZUMMESH-PART to Room B.
a. Press the - button 3 times. The RM B LED will flash with each button press
and then turn off.
b. Press and hold the - button until the RM B LED on the ZUMMESH-PART
lights. The ZUMMESH-PART is added to Room B.
Press and hold until LED lightsPress 3x then
6. Press any button on an AC-powered device that is part of the Room B ZÅ«m
space to exit Joining mode.
Test the Functionality of the ZUMMESH-PART
Once joined to Room A and Room B, the RM A and RM B LEDs should be off.
Verify Communications:
• Tap the + button. If the lights in Room A toggle, the ZUMMESH-PART is
communicating with Room A.
• Tap the - button to toggle the lights in Room B. If the lights in Room B toggle,
the ZUMMESH-PART is communicating with Room B.
Test the Functionality:
• Open the partition wall and verify that the green PART LED turns off. Recall
scenes from the keypads in Room A and Room B. The lights in both rooms
should react in unison.
• Close the partition wall and verify that the green PART LED turns on. Recall
scenes from the keypad in Room A and the lights in Room A should be
controlled. Recall scenes from the keypad in Room B and the lights in Room B
should be controlled.
Factory Reset
Perform a factory reset when the device is removed from the network or to remove
the configuration settings. The device must also be factory reset if the device is being
moved to a different system.
NOTE: New-in-box devices do not need to be factory reset before joining a system.
To factory reset the ZUMMESH-PART, press and hold + and - buttons for 10 seconds
until the PART LED lights.
Press and hold and until
+ -
the PART LED lights
Specifications
SPECIFICATION DETAILS
Sensing
Method of Detection
Light Source
IR Sensitivity
Sensing Distance
Diffuse Reflective
Pulse modulated infrared LED
Adjustable
4 ft (122 cm)
Power Requirements
Current Consumption 20 mA @ 24 VDC
Environmental
Temperature -13° to 121 °F (-25° to 55 °C)
Housing
Construction
Mounting
Plastic
Surface mount; 1-gang mountable in a 3-1/2 inch
deep electrical box, fits decorator-style faceplate
Weight 3.32 oz (94 g)
Additional Resources
Visit the product page on the Crestron website
(www.crestron.com) for additional information and the latest
firmware updates. Use a QR reader application on your mobile
device to scan the QR image.
As of the date of manufacture, the product has been tested and found to comply with
specifications for CE marking.
Federal Communications Commission (FCC) Compliance Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following
conditions:(1) This device may not cause harmful interference and (2) this device must accept
any interference received, including interference that may cause undesired operation.
CAUTION: Changes or modifications not expressly approved by the manufacturer responsible
for compliance could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Industry Canada (IC) Compliance Statement
CAN ICES-3(B)/NMB-3(B).
The product warranty can be found at www.crestron.com/warranty.
The specific patents that cover Crestron products are listed at www.crestron.com/legal/patents.
Certain Crestron products contain open source software. For specific information, please visit
www.crestron.com/opensource.
Crestron, the Crestron logo, and ZÅ«m are either trademarks or registered trademarks of
Crestron Electronics, Inc. in the United States and/or other countries. Other trademarks,
registered trademarks, and trade names may be used in this document to refer to either the
entities claiming the marks and names or their products. Crestron disclaims any proprietary
interest in the marks and names of others. Crestron is not responsible for errors in typography
or photography.
This document was written by the Technical Publications department at Crestron.
©2018 Crestron Electronics, Inc.
Crestron Electronics, Inc. Installation Guide - DOC. 8278A
15 Volvo Drive, Rockleigh, NJ 07647 (2051219)
Tel: 888.CRESTRON 09.18
Fax: 201.767.7576 Specications subject to
www.crestron.com change without notice.


Product specificaties

Merk: Crestron
Categorie: Niet gecategoriseerd
Model: ZUMMESH-PART
Breedte: 106 mm
Hoogte: 57 mm
Aantal per verpakking: 1 stuk(s)
Lengte: 34 mm
Bedrijfstemperatuur (T-T): 0 - 45 °C

Heb je hulp nodig?

Als je hulp nodig hebt met Crestron ZUMMESH-PART stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Crestron

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd