Crestron CLXI-1DELV4 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Crestron CLXI-1DELV4 (6 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 30 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/6
CLTI- & CLXI-1DELV4
Crestron Electronics, Inc. Installation Guide – DOC. 6405A
15 Volvo Drive Rockleigh, NJ 07647 (20138 )15
Tel: 888.CRESTRON 03.08
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
Functional Summary
The Crestron 1-Feed, 4-Dimmer Electronic Low Voltage
Terminal Block and Module (CLTI-1DELV4 and
CLXI-1DELV4, respectively), are considered a single
entity and must be used together. They ship separately to
permit termination of the field wiring to the
CLTI-1DELV4 prior to installation of the
CLXI-1DELV4, as described in this guide. They can be
mounted in any Crestron Automation Enclosure (CAEN
or CAENIB-Series Enclosures). The terminal block is
designed to terminate the circuit feed (LINE and
NEUTRAL) and distribute the controlled circuit (LOAD)
to the fixture(s). The module connects to the terminal
block and performs dimming control of four electronic
low-voltage or incandescent loads. The maximum load is
10 amps for any controlled circuit, limited to 13 amps
total per module. The unit requires 230VAC 50 Hz, 1
phase input voltage. An oversize heat sink dissipates heat
efficiently. There are LEDs on the module to indicate
communication to a Cresnet network, input power to the
module, and output power to the load.
NOTE: When connecting to an Arc Fault Breaker, the
load should not exceed 1000 watts.
Installation
Terminal block and module must be mounted into a
Crestron Automation Enclosure by a licensed electrician,
in accordance with all national and local codes.
CAUTION: This equipment is for indoor use only and
needs to be air-cooled. Mount in a well-ventilated area.
The ambient temperature must be 0°C to 40°C (32°F to
104°F). The relative humidity must be 0% to 90% (non-
condensing).
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and
right sides) of double-wide enclosures. Modules are
installed along the right side of single-wide enclosures
and side-by-side in the center of double-wide enclosures.
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so
that they can be properly wired. Refer to the illustrations
shown in the next column when considering the location
of terminal blocks and modules within an enclosure.
NOTE: Modules and terminal blocks must be installed
into the lowest available spaces and continue toward the
top of the enclosure.
Terminal Block & Module Locations (Single-wide Enclosure)
GROUNDING
TERMINAL
BLOCK
TERMINAL
BLOCK
MODULE
(INSTALL INTO
LOWEST AVAILABLE
SPACES)
Terminal Block & Module Locations (Double-wide Enclosure)
TERMINAL BLOCK
(RIGHT)
GROUNDING TERMINAL BLOCKS
TERMINAL BLOCK
(LEFT)
MODULE
(INSTALL INTO
LOWEST AVAILABLE
SPACES)
Terminal Block & Module Crestron CLTI- & CLXI-1DELV4
2
Terminal Block & Module: CLTI- & CLXI-1DELV4 Installation Guide – DOC. 6405A
Terminal Block Installation and Field
Wiring
NOTE: To install a CLTIBN Circuit Breaker Terminal
Block, refer to the latest version of the CLTIBN
Installation Guide (Doc. 6561) which can be downloaded
from the Crestron website (www.crestron.com/manuals).
NOTE: Both left-side and right-side adhesive wiring
labels are provided. The left-side labels are used in both
single and double-wide enclosures. The right-side labels
are only used in double-wide enclosures.
1. Remove the backing from the left or right
adhesive wiring label.
2. Apply the adhesive label by aligning the holes in
the label with the appropriate holes on the
Crestron Automation Enclosure where the
terminal block is to be mounted. For information
on mounting locations, refer to the latest version
of the CAEN Installation Guide (Doc. 5940) or
the CAENIB Installation Guide (Doc. 6562). The
wiring label lies beneath the terminal block as
shown in the two wiring diagrams on this page.
3. Use the two supplied self-tapping pan Phillips
screws (8B x ¼ (6 mm) length) to secure the
terminal block to the Crestron Automation
Enclosure.
CAUTION: Bypass jumpers are provided to allow
testing and to protect the module during installation.
When properly secured by five screws, the bypass
jumper on the brown and red section of the terminal
block shorts the LINE in to DIM out so that the
circuit is energized. Do not remove this bypass
jumper until all feed and load wiring has been
completed, the circuit has been tested for electrical
faults, and the module has been installed. Refer to
“Module Installation” on next page.
Furthermore, the jumper on the blue section of the
terminal block ties the neutral in to the neutral outs.
This jumper should never be removed.
NOTE: Use copper conductors only – rated 75°C.
4. With the circuit breakers turned off, connect the
circuit feed (LINE and NEUTRAL) and
controlled circuit (LOAD) wires to the terminal
block per the markings provided on the wiring
label (as shown in the diagrams on this page).
Terminal blocks accept one 0.2 - 4 mm
2 wire.
Wires should be stripped to 12 mm. Tighten
terminal blocks to 1 Nm.
5. Grounding terminal blocks are available in the
cabinet for termination of ground wires. Tighten
2.5-6 mm2 wires to 4 Nm, 10 mm2 wires to 4.5
Nm, or 16 mm2 wires to 5.1 Nm.
6. Test the circuit for electrical faults by turning on
the circuit breakers, checking that the breakers
do not trip, and that power is delivered to the
proper loads.
NOTE: If installing in a CAENIB, complete the
installation with a CAENIB-BP Blank Plate. Refer to the
latest version of the CAENIB-BP Installation Guide (Doc.
6563) for details.
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Single-wide and Left Side Double-wide Enclosures)
TERMINAL
BLOCK
GROUNDING
TERMINAL
BLOCK
GND
LEFT SIDE
WIRING LABEL
TO
LOAD(S)
AREA FOR
MODULE
LOCATION
LABEL
(FROM 16 AMP OR SMALLER
CIRCUIT BREAKER)
NEUTRAL
LINE
BYPASS
JUMPER
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Right Side Double-wide Enclosures)
NEUTRAL
(FROM 16 AMP
OR SMALLER CIRCUIT
BREAKER)
TERMINAL
BLOCK
AREA FOR
MODULE
LOCATION
LABEL
RIGHT SIDE
WIRING LABEL
TO
LOAD(S)
GROUNDING
TERMINAL
BLOCK
LINE
BYPASS
JUMPER
GND
Crestron CLTI- & CLXI-1DELV4 Terminal Block & Module
Installation Guide – DOC. 6405A Terminal Block & Module: CLTI- & CLXI-1DELV4
3
Module Installation
CAUTION: Module contains electrostatic sensitive
devices (ESDs); unit must be handled from metal
chassisdo not touch PC board or components.
NOTE: Modules are to be installed after enclosure
has been completely wired. Refer to the terminal
block installation procedure on page 2 for details.
1. Use the four supplied self-tapping pan Phillips
screws (8B x ¼-inch (6 mm) length) to secure
the module to the enclosure.
2. As shown in the wiring diagrams (next column),
connect the wires from the module to the
terminal block. Each wire exits the module
directly in line with, and is the same color as, the
terminal to which it should be connected. Wires
are pre-stripped to 12 mm. Tighten to 1 Nm.
3. If the module is being installed above another
module within the enclosure, attach the supplied
module interconnect cable between the two
modules. The illustration below depicts the area
within a double-wide enclosure where the
corners of four modules meet.
NOTE: One wire on the module interconnect cable
may be a different color from the rest. The color has
no bearing on its orientation during installation.
Use Module Interconnect Cable to Wire Module to Module
MODULE
INTERCONNECT
CABLE ATTACHED
CONNECTION
NOT
MADE
4. Turn on the circuit breaker and verify that the
green PWR LED on the module lights, the
breaker does not trip, and power is delivered to
the loads.
5. Turn off the circuit breaker and remove the five-
position bypass jumper from the brown and red
section of the terminal block. The jumper on the
blue section of the terminal block remains
installed. Refer to the figures in the next column
for a close-up of the jumpers.
NOTE: Before the five-position bypass jumper,
shown in the illustration, is removed, the Crestron
Professional Automation Computer (PAC2), which
provides control to the system, should be properly
connected and contain a valid program to provide
control of the module.
Wiring Diagram of the Terminal Block to the Module
(Single-wide and Left Side Double-wide Enclosures)
BYPASS JUMPER ON BROWN AND
RED SECTION OF TERMINAL
BLOCK HAS BEEN REMOVED
AFTER LOOSENING ALL SCREWS.
JUMPER ON BLUE SECTION
REMAINS INSTALLED.
BLUE
BROWN
RED
ENLARGEMENT DETAIL:
BYPASS JUMPER REMOVED
JUMPER INSTALLED
Wiring Diagram of the Terminal Block to the Module
(Right Side Double-wide Enclosures)
BLUE
BROWN
RED
JUMPER INSTALLED
JUMPER ON BROWN AND
RED SECTION OF TERMINAL
BLOCK HAS BEEN REMOVED
AFTER LOOSENING ALL SCREWS.
JUMPER ON BLUE
SECTION REMAINS
INSTALLED.
ENLARGEMENT DETAIL:
BYPASS JUMPER REMOVED
6. Turn on the circuit breaker.


Product specificaties

Merk: Crestron
Categorie: Niet gecategoriseerd
Model: CLXI-1DELV4

Heb je hulp nodig?

Als je hulp nodig hebt met Crestron CLXI-1DELV4 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Crestron

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd