CAENIB
Introduction
The Crestron CAENIB Series automation enclosures are
designed to house Crestron's CLXI-Series lighting control
modules with optional load- side circuit breakers and a
PAC2 or PAC2M control system. CAENIB enclosures are
available in an assortment of sizes, suitable for surface or
flush wall-mount installation. Each model has been
engineered to provide a clean and manageable installation
with abundant provisions for wire termination and
electrical knockouts.
NOTE: The PAC2 occupies two module spaces in a
double-wide enclosure and one module space in a
single- wide.
NOTE: Four keyholes are located within the enclosure
and should be used if surface mounting.
CAENIB Overall Dimensions (Front and Side Views)
W3
W4
W1
W2
H2
W3
H1 H3
D1W3 W5
W6
Functional Summary
Specifications
DIMENSIONS 7x2 7x1 4x2 4x1 2x1
H1
(mm (in))
1575
(62)
1575
(62)
987
(38 7/8)
987
(38 7/8)
596
(23 1/2)
H2
(mm (in))
68
(2 11/16)
68
(2 11/16)
68
(2 11/16)
53
(2 1/8)
53
(2 1/8)
H3
(mm (in))
1422
(56)
1422
(56)
835
(32 7/8)
863
(34)
473
(18 5/8)
W1
(mm (in))
673
(26 1/2)
390
(15 3/8)
673
(26 1/2)
390
(15 3/8)
390
(15 3/8)
W2
(mm (in))
647
(25 1/2)
365
(14 3/8)
647
(25 1/2)
365
(14 3/8)
365
(14 3/8)
W3
(mm (in))
63
(2 1/2)
44
(1 3/4)
63
(2 1/2)
44
(1 3/4)
44
(1 3/4)
W4
(mm (in))
520
(20 1/2)
276
(10 7/8)
520
(20 1/2)
276
(10 7/8)
276
(10 7/8)
W5
1
(mm (in))
520
(20 1/2)
250
(9 7/8)
520
(20 1/2)
250
(9 7/8)
250
(9 7/8)
W6
(mm (in))
63
(2 1/2)
69
(2 3/4)
63
(2 1/2)
69
(2 3/4)
69
(2 3/4)
D1
(mm (in))
104
(4 1/8)
104
(4 1/8)
104
(4 1/8)
104
(4 )1/8
104
(4 1/8)
Cover
Thickness
1
(1/16)
1
( )1/16
1
(1/16)
1
( )1/16
1
( )1/16
Cover Height
(mm (in))
1593
(62 3/4)
1593
(62 3/4)
1006
(39 5/8)
1006
(39 5/8)
615
(24 1/4)
Cover Width
(mm (in))
692
(27 1/4)
409
(16 1/8)
692
(27 1/4)
409
(16 )1/8
409
(16 1/8)
Included Cover
Plates2
6 3 4 2 1
Weight (empty)
3
(kg (lb))
29.5
(65)
19.5
(43)
20
(44)
13.2
(29)
8.6
(19)
Max. Weight
(filled) (kg (lb))
90.9
(200)
45.5
(100)
45.5
(100)
22
(55)
14.1
(31)
1. The lower keyholes are not symmetrically spaced within
single- wide enclosures.
2. Additional cover plates are available from Crestron.
3. Weight (empty) is the weight of an empty enclosure with a cover.
Houses Crestron lighting modules, terminal
blocks, professional automation computer, and
third-party products with or without Crestron
u mniversal ounting p lates
Flush or surface mounted installation
Ventilated cover for convection cooling of
modules
Conveniently located electrical knockouts for
both high voltage and Class 2 wiring
16- o gauge h t dipped galvanized steel
Crestron Electronics, Inc. Installation Guide – DOC. 6562A
15 Volvo Drive Rockleigh, NJ 07647 (2017317)
Tel: 888.CRESTRON 06.14
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
Automation Enclosures – International Versions, 230 V Crestron CAENIB
Regulatory Compliance Conformité Reglementaire
This product is Listed to applicable UL Standards Ce produit est homologselon les normes et les
and requirements by Underwriters Laboratories Inc. exigences UL applicables par Underwriters
Laboratories Inc.
As of the date of manufacture, the CAENIB Series has been tested and found to comply with specifications
for CE marking.
Federal Communications Commission (FCC) Compliance Statement
These devices comply with part 15 of the FCC Rules. Operation is subject to the following conditions:
(1) These devices may not cause harmful interference and (2) these devices must accept any interference
received, including interference that may cause undesired operation.
CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for
compliance could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna
Increase the separation between the equipment and receiver
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
Consult the dealer or an experienced radio/TV technician for help
Industry Canada (IC) Compliance Statement Industrie Canada (IC) Décl aration de conformité
CAN ICES-3(B)/NMB 3(B)-
2
Automation Enclosures – International Versions, 230 V: CAENIB Installation Guide DOC. 6562A
Crestron CAENIB Automation Enclosures – International Versions, 230 V
Installation
The enclosure must be mounted by a licensed electrician
in accordance with all national and local codes. Refer to
the table on page 1 for the weight of a fully loaded
enclosure.
When choosing components to place in the enclosure,
refer to the table on page 1 to ensure that the maximum
weight capacity is not exceeded. Each module’s product
page on the Crestron website lists the module’s weight.
CLTI and CLTIBN terminal blocks and CLXI modules
must be mounted using screw holes shown in the
“Mounting Detail ” diagrams. Note that the CLTIBN s
terminal blocks include circuit breakers with overload
protection. For applications where an RCCBO (Residual
Current Circuit Breaker with Overload) is needed, the
corresponding breaker provided must be replaced with the
RCCBO of choice. Note that the presence of an RCCBO
requires that the CLXI module be mounted in a different
location to allow for the added size of the new breaker.
For additional information, see the documentation that
ships with the CLTIBN.
CAUTION: These enclosures house equipment that
needs to be air-cooled. Therefore, mount in a
well-ventilated area. The ambient temperature range
should be 0 C to 40 F to 104° °C (32° °F). The relative
humidity should range from 10% to 90% (non-
condensing). Furthermore, allow adequate clearance in
front of the vented cover for servicing and ventilation.
NOTE: Install modules into the lowest available spaces
and continue toward the top of the enclosure.
NOTE: Enclosures are intended for indoor use only.
NOTE: When flush mounting, 16 mm (5/8 in) drywall is
preferred.
Wiring
CAUTION: All power feeds must be protected by
appropriate branch circuit breakers as required by national
and local code (supplied by others).
NOTE: Use copper conductors only – rated 60°C.
NOTE: All wiring must be installed in accordance with
all local and national electrical codes.
NOTE: Two snap bushings are supplied. If required,
insert into knockouts at the bottom of the enclosure to
prevent damage to low voltage wiring.
High voltage and Class 2 field wires must be kept
separate. Refer to the following illustrations showing
single-wide and double-wide wiring details. Areas for
high voltage wiring are shown along the top and side(s) of
the unit. The lower area is reserved for Class 2 wiring.
Tighten all CLTI Series terminal block - -and CLTIBN
screws and grounding terminal block screws to the torque
specified in the Torque Data table below.
CAUTION: Failure to properly tighten the screws may
result in poor electrical connection and overheating of the
terminals.
Torque Data
CLTI/CLTIBN
Terminal
Blocks
Grounding Terminal
Blocks
Wire Range
(mm2 (AWG))
0.34 – 6.0
(22 10)
2.5 – 6.0
(14 10)
10.0
(8)
16 –
25
(6 – 4)
Torque
(N- - m (lb in))
1.02
(9)
3.95
(35)
4.52
(40)
5.08
(45)
Key - Typical Products in a CAENIB Enclosure
Mounting Details - - Single Wide CAENIB
Mount CLTIBN
to these holes.
Mount CLXI
to these holes
when using CLTI
or CLTIBN.
Mount CLTI
to these holes.
Mount CLXI
to these holes
when using CLTIBN
with RCCBO.
Mount CLTI and CLTIBN terminal blocks
and CLXI modules to the holes shown above.
Installation Guide A DOC. 6562 Automation Enclosures – International Versions, 230 V: CAENIB
3


Product specificaties

Merk: Crestron
Categorie: Niet gecategoriseerd
Model: CAENIB-7X2

Heb je hulp nodig?

Als je hulp nodig hebt met Crestron CAENIB-7X2 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Crestron

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd