Installation instructions
DH75/DH110 RANGE
Installation model DH75/110
1. Remove machine from packaging and set on a level surface.
Check at machine is level bo vertically and horizontally.
2. Remove covers as shown in FIG.1 relative to machine type
installed.
3. The Electrical supply to unit must be sized according to e
data on e serial number label, paying close attention to
I.E.E regulations latest edition regarding e special conditions
governing electrical supply to machines in potentially damp
areas (DH75/110 are IP45).
4. The electrical supply should be connected to e terminals
on e Printed Circuit Board in e electrical box found in
e top corner of e machine, see Fig1 & Fig4. Wires to be
connected as follows: brown/red to live, blue/black - to neutral,
and green/yellow to ear.The fan mode switch can be set
to cycle fan when Hygrostat senses demand but should be
set to continuous to promote good air circulation and reduce
condensation.
Note that on models fitted with LPHW and or remote hygrostat
the fans will start automatically whenever there is an air heating
or dehumidification demand. During defrost the fans will stop. (Fan
cycle not recommended for TTW machines with humidistat only).
Set Fan Speed switch to “High” for maximum duty, “Low” for minimum sound.
5. Locate drain, 15mm compression fitting, on side of unit and run
it away to waste as preferred. A single hole is provided in e
side of e unit. The drain is factory fitted to is hole. (In TTW
machines ere is an alternate position - see drawings).
Models wi LPHW fitted
6. Connect water circuit piping to e 22mm stubs provided on
e side of e machine as per diagram.
7. It is recommended at isolation valves are fitted to enable
isolation ofe machine in e event of service.
The Circulating Pump must be sized to take into account
e design flow rate of e machine plus e water system
resistance. (Flow Rate 9.6 l/min Pressure Drop 2.8 m/hd).
Please leave ese instructions for e user.
Fig 1
Standard &
TTW machine
Standard
machine Mains in
terminals on
printed circuit
board
Grille
Fixing screws (3)
Outer cover
Rremove panel
(4 screws)
Mains in
Condensate
drain
LPHW in
LPHW out
Port B
LPHW out
Port AB
LPHW in
Port A to LPHW fin
block
Fig 2
LPHW SCHEMATIC
Boiler
Radiator
(If fitted)
Flow
balance
valve
Flow meter
3 way motorised vslve
LPHW connections
located in cabinet
(Diverting)
Pump
Fig 3
DH75/110
Radaitor
(If fitted)
HEALTH & SAFETY WARNING
As e Heat Pump contains electrical and rotational equipment, it is recommended at ONLY competent persons carry out any work on is type of
machine (see guarantee). Isolate electrically before entering machine or removing panels.
This appliance is not intended for use by persons (including children) wi reduced physical,sensory or mental capabilities, or lack of experience and
knowledge, unless ey have been given supervision or instruction concerning use of e appliance by a person responsible for eir safety.
Children should be supervised to ensure at ey do not play wi e appliance
ISOLATE ELECTRICALLY BEFORE ENTERING MACHINE OR REMOVING PANELS.
The Calorex TTW units are designed for installation in a heated room, adjacent to e poolroom.
SD405450 issue 15
Connections for remote 12V air ermostat, optional
hygrostat, and Rremote on/off.
8. If e Remote Hygrostat or combined stat is fitted, ensure at
e dial on e internal humidistat is set to minimum 20% -
Fully anti-clockwise. Connect remote Hygrostat to terminals on
Printed Circuit Board as shown in Fig 4.
USER CHECK LIST
OPERATION
A normal hygrostat setting (50-60%) is marked on e console.
Min air temp 5°C.
Note : The fan stops during defrost.
The fan will start automatically, as required, on machines fitted wi LPHW
and/or remote Hygrostat.
Operating
a. Ensure air inlets/outlets and filters are kept clear and clean.
b. Wipe clean wi damp clo or cleaning fluid suitable for painted
surfaces.
c. Note. The Reply Paid Warranty Registration Card must be returned to
ensure e correct warranty is given. If you do not find a Registration Card
wi your machine, please contact Calorex Service Department giving your
name, address and serial number of your machine, a card will en be sent
to you.
Filter cleaning
The filter can be washed in warm, soapy water, rinsed and shaken dry before
replacement. Frequency of cleaning depends on user alough no more an
two mons should elapse between cleaning. The dehumidifier must not be
run wiout a filter fitted.
Machine not running at all.
Check e following.
1. Is supply switched on?
2. Is supply fuse healy?
3. Turn Hygrostat knob fully anti-clockwise.
4. Check air inlet and outlet for obstructions and at filter is not
blocked.
5. Check at HP and LP switch are reset.
6. If, aer carrying out e above and waiting 30 mins, e machine
does not start, telephone for service.
Machine fan only running (No LPHW demand)?
7. Turn Hygrostat knob fully anti-clockwise.
8. Check air inlet and outlet for obstructions and at filter is not
blocked.
9. Check at HP and LP switch are reset, if aer 30 mins e
machine has not restarted, telephone for service.
Water leaking from e base of e unit
9. Check connection from machine to drain for blockages and clear
accordingly. Check fall is adequate.
10. Check at machine is level bo vertically and horizontally.
The user check list should be carried out before initiating a service call. Do
not attempt to interfere wi any internal control settings as ese have been
factory calibrated and sealed.
If in doubt or if advice is required, contact Calorex Service Department.
Telephone (01621) 856611 (option 4) or
email service.department@danerm.com.
Fig 4
All terminals are on e
printed circuit board
Remote
ermostat
Remote
on/off
switch
LPHW
THM
STAT
H
STAT
REMOTE
Fused mains
electrical supply
ON/
OFF
Zero volt
LPHW boiler
demand signal
L1 L2 L3 N E
Remote
combined stat
REMOTE
THM
STAT
H
STAT
Remove link when
remote switch or
remote humidistat
fitted
Remove link when
remote combined
stat is fitted
Remote
humidistat
Machine dimensions
800* 800*
1500*
1500
800*
RECOMMENDED TO PREVENT RECIRCULATION
1520
796
385
69 (DRAIN 15mm)
402
(LPHW IN 22 DIA)
502
(LPHW OUT 22 DIA)
675
(MAINS IN PG16)
30
AIR
AIR
988 138
342260
350
780
1167
888
980
1474
62
AIR SAMPLE TUBES
DO NOT OBSTRUCT
AIR
AIR
30 DRAIN TTW ONLY
STANDARD MACHINE WITH COVER
FILTER
THROUGH THE WALL MODEL
SERVICE REQUIREMENTS
VIEW FROM POOL HALL
*DIMENSIONS MARKED THUS ARE RECOMMENDED FOR SERVICE ACCESS
STANDARD MACHINE WITH COVER THROUGH THE WALL MODEL
MACHINE AND DUCT MUST BE
SEALED TO WALL & ALL CAVITIES
BRIDGED TO PREVENT RECIRCULATION