Calorex DH 15 Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Calorex DH 15 (2 pagina's) in de categorie Ontvochtiger. Deze handleiding was nuttig voor 11 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/2
SD462450 ISSUE 5
Installation instructions
MODELS DH 15AX - DH TTW 15AX
Heal & safety warnings
INSTALLATION - MODEL DH 15AX - DH TTW 15AX
1. Remove machine from packaging and locate fixing bracket.
2. Locate bracket on wall in required position. Drill hole Ø6.0mm (no.10)
by 60mm deep as shown at ‘A’. Insert wall plug and screw bracket in
place.
3. Set bracket level wi spirit level as shown, drill rough and fix it at ‘B’
wi wall plug and screw.
4. Ensure bracket still level, tighten screws ‘A’ and ‘B’, finally drill andfix
as above at position(s) ‘C’ & ‘D’.
5. Check all screws are tight.
6. Remove machine cover, retaining all fixings.
7. Li dehumidifier on to wall bracket and mark fixing holes.
8. Drill holes and fit wall plugs as stage 2.
9. Fit dehumidifier to wall.
10. The electrical supply to e unit must be sized according to e data
on e serial number label paying special attention to I.E.E. regulations
latest edition regarding e special conditions governing electrical
supply to machines in potentially damp areas.
11. The electrical supply should be connected to e terminal block
mounted on e bracket supporting e compressor. Brown/red to
‘live’, blue/black to neutral and ear to e stud provided.
12. Whilst not mandatory, e Danerm Group recommend at an
R.C.C.B. is always fitted or at e supply is to local electricity auority
recommendations, and at all ducting is bonded in accordance wi
ese regulations.
13. The supply to e machine should incorporate fuses or motor
rated circuit breakers (Type C) to specified rating, H.R.C. fuses are
recommended. An isolator must be fitted wiin clear view and not
more an 2 metres away. The isolator must have a minimum 3mm air
gap in e off position.
14. Locate pipe from drip tray and run it away to waste.
A short leng of 10mm pipe is provided which should be led into a
fixed waste pipe.
15. Set Humidistat to, “drier”, point on knob provided.
Please leave e instructions for e user.
A
C
B
D
As e Heat Pump contains electrical and rotational equipment, it is recommended at ONLY competent persons carry out any work on is type of
machine (see warranty).
ISOLATE ELECTRICALLY BEFORE ENTERING MACHINE OR REMOVING PANELS.
This appliance is not intended for use by persons (including children) wi reduced physical,sensory or mental capabilities, or lack of experience and
knowledge, unless ey have been given supervision or instruction concerning use of e appliance by a person responsible for eir safety. Children
should be supervised to ensure at ey do not play wi e appliance.
The Calorex TTW units are designed for installation in a heated room, adjacent to e pool room.
MACHINE OPERATION
MAINTENANCE
a. Ensure air inlet/outlets are kept clear and clean.
b. Wipe clean wi damp clo.
TTW MACHINES
Fit grilles, supplied wi e Heat Pump, in position required. Self-
adhesive base supplied wi e unit to be fitted to e grill frame
as shown in e diagram below. Filters to be fitted to grille. Isolate
machine electrically before entering machine or removing panels.
MACHINE NOT RUNNING AT ALL
CHECK THE FOLLOWING:
1. Is supply switched on.
2. Is supply fuse healy.
3. Check air inlet and outlet for obstructions.
4. If, aer carrying out e above and waiting 1 hour, e machine does
not start, phone for service.
MACHINE FAN ONLY RUNNING
5. Check air inlet and outlet for obstructions, if aer 30 mins e machine
has not restarted phone for service.
WATER LEAKING FROM BASE OF UNIT
6. Check connection from machine to drain for blockages and
clear accordingly. Check fall is adequate.
7. Check at machine is level bo vertically and horizontally.
The user check list should be carried out before initiating a service
call.
Do not attempt to interfere wi any internal control settings as ese
have been factory calibrated and sealed.
If in doubt or if advice is required, contact e Danerm group UK
Service Department. by calling (01621) 856611 (option 4) or
email service.department@danerm.com.
SD462450 ISSUE 5
OPTIONAL HUMIDISTAT (IF FITTED)
MACHINE NOT RUNNING AT ALL.
a. Turn humidistat knob fully clockwise.
b. Check air inlet and outlet for obstructions, if aer 30
mins e machine has not restarted phone for service.
Note: The Reply Paid Warranty Registration Card must be returned to
ensure e correct warranty is given. If you do not find a Registration
Card wi your machine please contact Danerm Group UK Service
Department giving your name address and serial number of your
machine. A card will en be sent to you for completion.
GAS CHARGE
The dehumidifier incorporates a hermetically sealed refrigeration circuit
containing less an 6kg of refrigerant. R407c Global warming potential
(GWP) 1774.
825
387 181
18138 38
26826
VIEW WITH COVER SHOWN IN SECTION
AND COMPONENTS REMOVED
320
363
SELF-ADHESIVE
BASE
FILTER
207mm (WIDE) x 290 (HIGH) APERTURE
IN WALL FOR GRILLE
DZUS FASTENER
DIMENSIONS FOR TTW15AX DUCTING


Product specificaties

Merk: Calorex
Categorie: Ontvochtiger
Model: DH 15

Heb je hulp nodig?

Als je hulp nodig hebt met Calorex DH 15 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Ontvochtiger Calorex

Handleiding Ontvochtiger

Nieuwste handleidingen voor Ontvochtiger