Intrusion Alarm Systems | B901 Door Controller
B901 Door Controller
www.boschsecurity.com
uDirect interface to compatible Wiegand card readers
uOn-board buzzer output and supervised on-board
points
uRequest to Exit and Request to Enter inputs that
can have a shunt only option
uFour door states: Locked, Unlocked, Secured, Fire
Unlock
uSDI2 support as well as SDI compatible
The B901 Access Control Interface Module is a fully
supervised, addressable SDI/SDI2 bus device that
allows access control integration for Bosch compatible
control panels. This module offers 14 programmable
levels of access authority. Authority for access is
controlled by the user level, the group of the user, the
time of day, the door state, and the area armed state.
Control each authority restriction through automatic
and manual functions.
A door that has been automatically released by the
control panel will require manually re-engaging to
return to normal.
In a combination Fire/Intrusion system, the B901
should not be used to lock doors used for emergency
egress unless these doors have a mechanical release
mechanism.
Functions
Reader input
Standard 5-wire Weigand interface.
+5 VDC or +12 VDC supplied to power readers.
Open collector output for reader LED.
Unsupervised inputs
Tamper. Supports normally open devices.
REX. Supports normally open devices. Request to Exit
(REX) on short.
RTE. Supports normally open devices. Request to
Enter (RTE) on short.
Supervised input
1 kΩ End-of-line resistor.
Use for door contact.
Door states
Four door states are controlled through the keypad,
RPS (Remote Programming Software), scheduled
events (SKEDs), and automatic programmable
functions in the door controller parameters:
Locked. The lock relay can be deactivated (door
allowed to open) with a valid credential or REX/RTE
input.
Unlocked. The Lock relay is held in the deactivated
state to allow access without the need of a
credential.
Secured. The lock relay is activated and no access is
allowed even with valid credential (overridden by Fire
Unlock).
Fire Unlock. The lock relay is held in the deactivated
state during a Fire Alarm. This allows free access to
and from the building during an emergency.
Two automatic functions link the door state to the
arming state of the area:
Auto Door. When the area is Off (disarmed), the door
state is switched to “Unlocked”.
Disarm on Open. With this function as "Yes," a user
with valid access rights activates the strike and turns
off (disarms) the system after the door is opened.
With this function as "No," the area turns off
(disarms) upon the strike activation.
Indicators
Heartbeat LED. Blue LED blinks on and off when
system is operational. A rapid three-blink sequence
indicates a system error.
Reader LED. Rapidly blinking LED indicates the Card
data is being received. When the LED is off, no card
data is being received.
Certifications and approvals
Region Regulatory compliance/quality marks
Australia RCM ACMA
Europe CE EMC, RoHS [B915, B920, B930, B430,
B208, B308, B901]
USA UL Underwriters Laboratories
UL UL 294 - Standard for Access Control
Units and Systems
UL UL 365 - Police Station Connected Bur-
glar Alarm Units
UL UL 609 - Standard for Local Burglar
Alarm Units and Systems
UL UL 864 - Standard for Control Units and
Accessories for Fire Alarm Systems
(10th edition)
UL UL 985 - Household Fire Warning Sys-
tem Units (6th edition)
UL UL 1023 - Household Burglar Alarm Sys-
tem Units
UL UL 1076 - Proprietary Burglar Alarm
Units and Systems
UL UL 1610 - Central Station Burglar Alarm
Units
CSFM California State Fire Marshal (see our
website)
FCC Part 15 Class B
Canada ULC Underwriters Laboratories of Canada
ULC CAN/ULC S303 - Local Burglar Alarm
Units and Systems
ULC CAN/ULC S304 - Standard for Signal Re-
ceiving Center and Premise Burglar
Alarm
ULC ULC-ORD C1023 - Household Burglar
Alarm System Units
ULC ULC-ORD C1076 - Proprietary Burglar
Alarm Units and Systems
IC ICES-003 - Information Technology
Equipment (ITE)
Installation/configuration notes
The B901 Access Control Interface Module is
individually programmed through the control panel.
The module is compatible with several credential
models and readers.
Notice
Not all products and features are available in all
regions. Consult your local Bosch representative
for availability details.
Compatibility
Bosch readers and
accessories
ARD-AYJ12 EM Prox Mullion
ARD-MINIPROX
ARD-PROX-PPL
ARD-SER90-WI
ARD-SER40-WI
ARD-SER10-WI
D8223 HID Prox Wall Mount
D8224 HID Prox Mullion
D8224‑SP Low‑profile card reader,
HIDprox
D8225 HID Prox Mini Mullion
D8229 PIN Reader
Bosch tokens and cards ACA-ATR13 EM Tokens
ACD-ATR11ISO EM Cards
ACD-ATR14CS EM Clamshell Cards
ACD-IC2K26-50 iClass Cards
ACT-IC2K26-10 iClass Tokens
D8236‑10 HID Prox Cards
D8236KF‑10 HID Prox Tokens
Parts included
Quan
tity
Component
1 B901
1 1 kΩ ½ watt end of line resistor
1 Innerconnect cable (included)
3 # 6x3/8 self-tapping screws
1 Literature pack
Technical specifications
Environmental considerations
Relative humidity 5% to 93% at +32°C (+90°F)
Temperature (operating) 0°C to +49°C (+32°F to +120°F)
Properties
Dimensions 2.9 in x 5.0 in x 0.6 in
(73.5 mm x 127 mm x 15.25 mm)
Power requirements
Current Standby:110 mA + reader current
Alarm: 110 mA + reader current
Output (alarm) Form C relay (COM, NC, NO) at 12/24
V @ 2.0 A
Voltage (input) 12 VDC nominal
2 | B901 Door Controller
Wiring
Terminal wire size 18 AWG to 22 AWG (1.02 mm to 0.65
mm)
SDI2/SDI wiring to B901 +
Reader with external power
supply
Maximum distance – wire size
(unshielded wire only): 1000 ft (305
m) – 22 AWG (0.65 mm), 2500 ft
(762 m) – 18 AWG (1.02 mm)
SDI2/SDI wiring to B901 +
Reader from control panel
175 ft (61 m) – 22 AWG (0.65 mm),
500 ft (152 m) – 18 AWG (1.02 mm)
Wiring distance from B901
to Reader
200 ft (61 m) – 22 AWG (0.65 mm),
500 ft (152 m) – 18 AWG (1.02 mm)
Reader dependant
Credentials
Compatible credential
formats
37 bit. HID H10304 (With Site Code)
37 bit. HID H10302 (No Site Code)
26 bit. HID H10301 EM-EM4200 (3-
byte or 5-byte)
Ordering information
B901 Door Controller
Fully supervised, addressable SDI2/SDI bus device
that allows access control integration for Bosch G and
B Series Control Panels.
Order number B901
3 | B901 Door Controller
Represented by:
Europe, Middle East, Africa: Germany: North America: Asia-Pacific:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
emea.securitysystems@bosch.com
emea.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5
85630 Grasbrunn
Germany
www.boschsecurity.com
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
onlinehelp@us.bosch.com
www.boschsecurity.us
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
© Bosch Security Systems 2020 | Data subject to change without notice
16673845259 | en, V29, 25. Jun 2020


Product specificaties

Merk: Bosch
Categorie: Toegangscontrolesysteem
Model: B901
Breedte: 735 mm
Diepte: 127 mm
Hoogte: 15.25 mm
AC-adapter, uitgangsspanning: 12 V
Bedrijfstemperatuur (T-T): 0 - 49 °C
Relatieve vochtigheid in bedrijf (V-V): 5 - 93 procent