Apc 19061CL-3F-1E Handleiding
Lees hieronder de 📖 handleiding in het Nederlandse voor Apc 19061CL-3F-1E (2 pagina's) in de categorie UPS. Deze handleiding was nuttig voor 11 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld
Pagina 1/2
APC Back-UPS Pro®
1000/1050/1100/1400
User’s Manual
990-2012F Revision 7 12/03
Installation and Initial Start-Up
To obtain warranty coverage, please fill out and
return the warranty registration card now.
Inspection
Inspect the UPS upon receipt. Notify the carrier
and dealer if there is damage. The packaging is
recyclable; save it for reuse or dispose of it
properly.
Placement
Install the UPS in a protected area that is free of
excessive dust and has adequate air flow. Do
not operate the UPS where the temperature and
humidity is outside the specified limits.
Warning: Changes or modifications to this
unit not expressly approved by the party
responsible for compliance could void the
warranty.
Connect to Utility
Check the Site Wiring Fault Indicator
Location: Top right corner of UPS back panel.
Caution: If the site wiring fault indicator lights,
get a qualified electrician to correct the building
wiring.
Connect the Loads
Plug the loads into the output connectors on the
rear of the UPS. To use the UPS as a master
“On/Off” switch, make sure that all of the loads
are switched “On”.
Caution: Do not connect a laser
printer to the Battery Backup Outlets.
Battery Backup Outlets: These UPS outlets
provide battery power and surge protection to
equipment when utility voltage is outside
acceptable limits. Data sensitive equipment such
as a computer, monitor, or external drive are
connected to these outlets.
Connect Telephone / Network Surge
Suppression (Optional)
Connect a single line telephone or a 10Base-T/
100Base-Tx network cable into the RJ-45/RJ-11
telephone/network surge protection “IN” jack on
the back of the UPS. Connect from the “OUT”
jack with telephone cable (supplied) or network
cabling (not supplied) to a fax modem or network
port.
Connect Computer Interface
Port (Optional, BP1050/1100)
PowerChute® plus power management software
is included with this UPS. Connect the supplied
interface cable to the 9-pin computer interface
port on the back panel of the UPS. Connect to
the computer. See software documentation for
installation instructions.
Charge the battery
The UPS charges its battery whenever it
is connected to utility power. The battery will
charge fully during the first 4 hours of normal
operation. Do not expect full runtime during this
initial charge period.
Operating Instructions
Switch “On” — Switch “Off”
With the UPS plugged in, press and
release the On/Off/Test button to supply
power to the loads.
The UPS loads are immediately powered while
the UPS performs a self-test. Press and release
the button again to turn “Off” power to the loads.
It may be convenient to use the UPS as a
master “On/Off” switch for the protected
equipment.
The on-line LED illuminates when the
UPS is supplying utility power to the
battery backup loads.
Self-test
The UPS performs a self-test automatically when
turned “On”, and every two weeks thereafter (by
default). Automatic self-test eliminates the need
for periodic manual self-tests.
During the self-test, the UPS briefly operates the
loads on-battery. If the UPS passes the self-test,
it returns to on-line operation.
If the UPS fails the self-test it
immediately returns to on-line operation
and lights the replace battery LED.
The loads are not affected by a failed test.
Recharge the battery overnight and perform the
self-test again. If the replace battery LED is still
"On”, replace the battery using the Replacing
the Battery procedure.
On-Battery
During on-battery operation, the on-
battery LED illuminates and the UPS
sounds an audible alarm consisting of 4
beeps every 30 seconds. The alarm stops when
the UPS returns to on-line operation.
Low Battery
When the UPS is operating on-battery and the
energy reserve of the battery runs low, the UPS
beeps continuously until the UPS shuts down
from battery exhaustion or returns to on-line
operation.
Overload
When loads exceed the UPS capacity,
the overload LED illuminates and the
UPS emits a sustained tone. The alarm
remains “On” until the overload is removed.
Disconnect nonessential load equipment from
the battery backup outlets, to eliminate the
overload.
If the overload is severe, the input circuit breaker
may trip (the resettable center plunger of the
circuit breaker pops out), as well. Disconnect
nonessential load equipment from the UPS to
eliminate the overload and press the plunger
back in to restart the UPS.
If there is AC power and the circuit breaker does
not trip during overload, the loads are still
powered. If the circuit breaker trips or the UPS
attempts to transfer to battery, the loads’ power
will be shut “Off”. Turn the UPS “Off” then back
“On” to power the loads.
Replace Battery
If the battery fails a self-test, the UPS
emits short beeps for one minute and
the replace battery LED illuminates.
The UPS repeats the alarm every five hours.
Perform the self-test procedure to confirm
replace battery conditions. The alarm stops
when the battery passes the self-test.
Shutdown Mode
If there is no power, the host connected to the
computer interface port can command the UPS
to shut down. This is normally done to preserve
battery capacity after a controlled shutdown of
the protected system. In shutdown mode the
UPS stops supplying power to the load. The on-
line and overload LED indicators flash alternately
or, if the UPS has shutdown due to a low battery,
the UPS will beep once every 4 seconds for
approximately 16 seconds. When line power is
restored, the UPS will return to on-line operation.
Cold Start
Note: Cold start is not a normal operating
condition.
When the UPS is “Off” and there is no utility
power, it is possible to cold start the UPS to
power the loads from the UPS battery.
• Press and hold the On/Off/Test button
until the UPS begins beeping.
• Release the On/Off/Test button during the
beeping to start the UPS.
APC, Back-UPS Pro, and PowerChute are registered
trademarks of American Power Conversion Corp. All other
trademarks are the property of their respective owner.
Copyright © 2003
Storage
Storage conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully
charged. Before storing, charge the UPS for at least 4 hours.
Extended storage
At -15 to +30 °C (+5 to +86° F), charge the UPS battery every 6 months
At +30 to +45 °C (+86 to +113° F), charge the UPS battery every 3 months.
Replacing the Battery
This UPS has an easy to replace hot-swappable battery. Battery replacement is a safe
procedure, isolated from electrical hazards. You may leave the UPS and loads on for the
following procedure. See your dealer or call the number in this manual for information on
replacement battery kits.
Note: Once the battery is disconnected, the loads are not protected from power
outages.
1. Grasp the top of the front cover and tilt it out and down.
2. Unhook the bottom of the cover from the chassis and lift it upward to
expose the battery door. Be careful not to strain the ribbon cable. Do
not touch the exposed printed circuit board.
3. Fold the front cover on top of the UPS as shown.
4. Use a flat-blade screwdriver or a coin to remove the two battery door
screws and open the door.
5. Grasp the tab and gently pull the battery out of the UPS.
1
000-1100 VA
1
400 VA
6. Disconnect the battery leads.
• For the 1000/1050/1100 VA models, loosen the connectors by
gently wiggling them while pulling straight back from the battery
connector.
• For the 1400 VA model, pull the two gray couplers apart to
disconnect the battery.
7. Connect the battery leads to the new battery.
Note: Small sparks at the battery connectors are normal during
connection.
• For the 1000/1050/1100 VA models, connect the red wire to the
positive (+) terminal and the black wire to the negative (–) terminal.
• For the 1400 VA model, connect the gray battery coupler to the
UPS coupler.
8. Slide the battery into the UPS.
9. Close the battery door, replace the battery compartment screws, and
replace the front cover.
10. Dispose of the old battery properly at an appropriate recycling facility or
return it to the supplier in the packing material for the new battery. See
the new battery instructions for more information.
Warranty
Customers may return their defective unit to APC for replacement or repair during the standard
2-year warranty period. APC's standard procedure will be to replace the original unit with a
factory-reconditioned unit. Customers who must have the original unit back due to assigned
asset tags and set depreciation schedules must declare such a need at first contact with APC
Customer Service. APC will ship the replacement unit once the defective one has been received
by the repair department. The customer pays for the shipping to APC, APC covers ground
freight transportation costs back to the customer.
Service
If the UPS requires service, please do not return it to the dealer!
Follow these steps:
1. Use the Troubleshooting section of the Quick Reference Guide to eliminate common
problems.
2. Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common
UPS problem!
3. If the problem persists, call customer service or visit the APC Internet Website
(www.apc.com).
• Note the model number of the UPS, the serial number, and the date purchased. A
technician will ask you to describe the problem and try to solve it over the phone, if
possible. If this is not possible the technician will issue a Return Merchandise
Authorization Number (RMA#).
• If the UPS is under warranty, repairs are free. If not, there is a repair charge.
4. Pack the UPS in its original packaging. If the original packing is not available, ask customer
service about obtaining a new set.
• Pack the UPS properly to avoid damage in transit. Never use Styrofoam™ beads for
packaging. Damage sustained in transit is not covered under warranty.
• Include a letter with your name, RMA#, address, copy of the sales receipt, description of
the trouble, your daytime phone number, and a check (if necessary).
• Mark the RMA# on the outside of the package.
5. Return the UPS by insured, prepaid carrier to the address given to you by Customer
Service.
APC Contact Information
USA/Canada …………..
Mexico …………………..
Brazil …………………….
Worldwide ………………
1-800-800-4272
292-0253 / 292-0255
0800-12-72-21
1-401-789-5735
Internet …………………. http://www.apc.com
Technical Support ……. http://www.apc.com/support
Troubleshooting
Problem Possible Cause Solution
UPS will not turn “On”. On/Off/Test button not
pushed. Press the On/Off/Test
button to power the UPS
and the loads.
UPS input circuit breaker
tripped. Reduce the load on the
UPS by unplugging
equipment and reset the
circuit breaker by pressing
the plunger back in.
UPS will not turn “On” or
“Off”. Computer interface problem. Disconnect the computer
interface. If the UPS now
works normally, check the
interface cable and the
attached computer.
UPS operates on-battery
even though normal line
voltage is thought to exist.
UPS input circuit breaker
tripped. Reduce the load on the
UPS by unplugging
equipment and reset the
circuit breaker by pushing
the plunger back in.
UPS beeps occasionally. Normal UPS operation. None. The UPS is
protecting the load.
UPS does not provide
expected back up time. The UPS battery is weak due
to recent outage or is near
the end of its service life.
Charge the battery. The
UPS batteries require
recharging after an
extended outage. Batteries
age faster when put into
service often and when
operated at elevated
temperatures. If the battery
is near the end of its service
life, consider replacing the
battery even if the replace
battery indicator is not yet
lit.
On-line and overload
indicators are flashing
alternately.
The UPS was shutdown by
PowerChute® plus software. None. The UPS will restart
automatically when utility
power returns.
All indicators are flashing. Internal UPS fault. Do not attempt to use the
UPS. Turn the UPS “Off”
and have it serviced
immediately.
The UPS operates normally,
but the site wiring fault
indicator is lit.
Building wiring error such as
missing ground or hot to
neutral wire reversal.
Have a qualified electrician
correct the building wiring.
On-line and on-battery
indicators only are flashing Internal UPS fault. Do not attempt to use the
UPS. Turn the UPS “Off”
and have it serviced
immediately.
All indicators are “Off” and
the UPS is not operating. The UPS is shutdown and the
battery is discharged from an
extended power outage.
None. The UPS will return
to normal operation when
the power is restored and
the battery has a sufficient
charge.
The replace battery light is
illuminated. Weak batteries. Allow the batteries to
recharge for at least 4
hours. If the problem
persists after recharging,
replace the batteries.
Replacement batteries not
connected properly. Confirm the battery
connections.
The overload light is
illuminated or flashing The UPS is overloaded. Reduce the load on the
UPS by unplugging
equipment.
Specifications
1000 VA 1050 VA
1100 VA
1400 VA
Acceptable input voltage 0 - 160 VAC
Input voltage (on-line operation) 94-148 VAC
Output voltage 106-127 VAC
Input Over Current Protection Resettable circuit breaker
Frequency limits (on-line operation) 47 - 63 Hz (auto-sensing)
Transfer time 4 ms typical, blackout response time
Maximum load 1000 VA
670 W 1050 VA
670 W
1100 VA
670 W
1400 VA
950 W
On-battery output voltage 115 VAC
On-battery frequency 50 or 60 Hz, ±0.1 Hz; unless synchronized to utility
during brownout
On-battery waveshape Stepped sine-wave
Output Over Current Protection Over-current and short-circuit protected, latching
shutdown on overload
Battery type Spill proof, maintenance free, sealed lead-acid
Typical battery life 3 to 6 years, depending on number of discharge
cycles and ambient temperature
Typical recharge time 2 to 5 hours from total discharge
Operating temperature 0 to +40 C (+32 to +104° ° F)
Storage temperature -15 to +45 °C (+5 to +113° F)
Operating / storage relative humidity 0 to 95%, non-condensing
Operating elevation 0 to +3,000 m (0 to +10,000 ft)
Storage elevation 0 to +15,000 m (0 to +50,000 ft)
Audible noise at 1 m (3 ft) <45 dBA
Size (H x W x D) 21.6 x 17.0 x 43.9 cm
(8.5 x 6.7 x 17.3 in.)
Weight - net (shipping) 19.3 (21.1) kg
42.5 (46.5) lb. 19.3 (21.2) kg
42.5 (46.8) lb. 24.1 (25.9) kg
53.0 (57.0) lb.
Listing, Certifications and Unlisted
Components UL 1778, UL 497A, CSA 107.1, FCC part 15
EMI certification FCC/DOC Class B certified
Electromagnetic immunity IEC 801-4 level IV, 801-5 level III
Product specificaties
Merk: | Apc |
Categorie: | UPS |
Model: | 19061CL-3F-1E |
Kleur van het product: | Beige |
Gewicht: | 19360 g |
Snoerlengte: | 1.83 m |
Aantal Ethernet LAN (RJ-45)-poorten: | 1 |
Interface: | DB-9 RS-232 |
Geluidsalarm(en): | Ja |
Responstijd: | 1449 ms |
Uitgangsvermogen: | 670 W |
Temperatuur bij opslag: | -15 - 45 °C |
Frequentie: | 60 Hz |
Luchtvochtigheid bij opslag: | 0 - 95 procent |
Bedrijfstemperatuur, bereik: | 0 - 40 °F |
Afmetingen (B x D x H): | 170 x 439 x 216 mm |
Relatieve vochtigheid in bedrijf (V-V): | 0 - 95 procent |
Type batterij: | Lood-zuur |
Surge energy rating: | 320 J |
Nominale input voltage: | 120 V |
Output power capacity: | 1 kVA |
Netspanning, in bedrijf: | 120 V |
Vervangings-batterij cartridge: | RBC6 |
Heb je hulp nodig?
Als je hulp nodig hebt met Apc 19061CL-3F-1E stel dan hieronder een vraag en andere gebruikers zullen je antwoorden
Handleiding UPS Apc
16 November 2024
12 November 2024
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
12 Oktober 2024
Handleiding UPS
- UPS HP
- UPS IKEA
- UPS AEG
- UPS Siemens
- UPS Dell
- UPS Digitus
- UPS Eaton
- UPS Emerson
- UPS Furman
- UPS Gembird
- UPS Gys
- UPS Lenovo
- UPS LevelOne
- UPS Riello
- UPS Schneider
- UPS Voltcraft
- UPS Jung
- UPS Steren
- UPS Conceptronic
- UPS Tripp Lite
- UPS Approx
- UPS Block
- UPS LC-Power
- UPS Energenie
- UPS CyberPower
- UPS Adj
- UPS East
- UPS Equip
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Salicru
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nieuwste handleidingen voor UPS
18 November 2024
17 November 2024
17 November 2024
17 November 2024
15 November 2024
15 November 2024
14 November 2024
14 November 2024
7 November 2024
7 November 2024