Air King EVLD Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor Air King EVLD (16 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 43 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/16
www.airkinglimited.com6727916 Rev. H 12/21 1 of 16
IMPORTANT INSTRUCTIONS -
OPERATING MANUAL
SAVE THESE INSTRUCTIONS
Exhaust Fan with Light
EVLD Series
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN
THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should
always be followed to reduce the risk of fire, electric shock and
injury to person, including the following:
WARNING: TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK AND INJURY TO
PERSON, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer.If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service
panel and lock the service disconnecting means to prevent power
from being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
WARNING: TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK AND INJURY TO
PERSON, OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-related construction.
b) Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent
back drafting. Follow the heating equipment manufacturers guideline
and safety standards such as those published by the National Fire
Protection Association (NFPA) and the American Society for Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE), and the local
code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
d) Ducted fans must always be vented to the outdoors.
e) If this unit is to be installed over a tub or shower, it must be marked
as appropriate for the application and be connected to a GFCI (Ground
Fault Circuit Interrupter) – protected branch circuit.
f) Do not install in a ceiling with thermal insulation value greater than
R40.
g) This unit must be grounded.
h) To avoid motor bearing damage and noisy and/or unbalanced impellers,
keep drywall spray, construction dust, etc. off power unit.
i) Read all instructions before installing or using exhaust fan.
j) Suitable for use with electronic speed control device.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE
OUTSIDE OF THE BUILDING HAS A STRONG EFFECT
ON THE AIR FLOW, NOISE AND ENERGY USE OF THE FAN. USE
THE SHORTEST, STRAIGHTEST DUCT ROUTING POSSIBLE FOR
BEST PERFORMANCE, AND AVOID INSTALLING THE FAN WITH
SMALLER DUCTS THAN RECOMMENDED. INSULATION AROUND
THE DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD
GROWTH. FANS INSTALLED WITH EXISTING DUCTS MAY NOT
ACHIEVE THEIR RATED AIRFLOW.
www.airkinglimited.com6727916 Rev. H 12/21 2 of 16
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
SECTION 1
Preparing the Exhaust Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the
exhaust fan you should have:
1 - Grill
1 - Damper Assembly (attached)
4 - Mounting Rails
1 - Mounting Flange
1 - LED Lamp
1 - Instruction/Safety Sheet
2. Choose the location for your fan. To ensure the best air and sound performance, it is
recommended that the length of ducting and the number of elbows be kept to a minimum,
the radius of each elbow be as large as possible for the installation, and that insulated hard
ducting be used. Larger duct sizes will reduce noise and airflow restrictions. This fan will
require at least 10 of clearance in the ceiling or wall, and will mount through drywall up
to 3/4 thick.
3. No additional vibration deadening materials are needed for this fan.
SECTION 2
New Construction
NOTE: If the mounting flange is installed on the fan housing, remove the two screws that connect
the ceiling mounting flange to the housing and set aside (Figure 17).
1. Install the rails into the mounting channel on the housing. Center the mounting channel in
the slots on the housing, then from inside the housing tighten the mounting channel nuts so
the channel is securely in place. Position the housing next to the joist. Line up housing so
that it will be flush with the finished ceiling. Secure the ends of the rails with screws or nails
(not included) to the joists and slide the housing into the final position (Figure 1).
SECTION 3
Existing Construction
NOTE: If the mounting flange is installed on the fan housing, remove the two screws that connect
the ceiling mounting flange to the housing and set aside (Figure 17).
1. Set housing in position between the joist and trace an outline onto the ceiling material
(Figure 2). Set housing aside and cut opening, being careful not to cut or damage any
electrical or other hidden utilities. Install the rails into the mounting channel on the
housing. Center the mounting channel in the slots on the housing, then from inside the
housing tighten the mounting channel nuts so the channel is securely in place. Position
the housing in the previously cut hole so that it is flush with the finished ceiling. Secure
the ends of the rails to the joists (Figure 1).
SECTION 4
Ducting
NOTE: 6" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL
BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for best
performance, and avoid installing the fan with smaller ducts than recommended. Insulation
around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing
ducts may not achieve their rated air flow.
1. Connect the ducting to the fan’s duct collar Secure in place using tape or screw (Figure 3).
clamp. Always duct the fan to the outside through a wall or roof cap. It is recommended
that low restriction termination fittings be used.
2. Ensure duct joints and exterior penetrations are sealed with caulk or other similar
material to create an air-tight path to minimize building heat loss or gain and to reduce
the potential for condensation. Place/wrap insulation around duct and/or fan to in order to
minimize possible condensation buildup within the duct, as well as building heat loss or
gain (Figure 4).
SECTION 5
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL
ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL
WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of the
fan’s blower assembly. If you choose to wire the unit from the inside, you will need to remove the
blower assembly and internal wiring compartment. Both methods are equally effective.
1a. External Wire Compartment: Remove the wire compartment cover screw and place cover
in a secure place (Figure 5).
Ducting
Duct
Collar
Figure 3
Figure 2
Joist
Housing
Joist
Mounting Rails
Figure 1
Figure 4
Insulation*
(place around and
over Fan Housing
Fan Housing
Power Cable*
Seal gaps
around Housing
Round
Duct*
Seal duct joints
with tape
Round
Elbows*
Wall Cap*
Roof Cap*
(with built-in
damper)
Keep duct
runs short
*Purchase separately
or
www.airkinglimited.com6727916 Rev. H 12/21 3 of 16
1b. Internal Wire Compartment: If the motor is already installed in the housing, remove the
two screws holding the blower assembly in place. Lift up on the assembly and slide it out
of the tabs on the housing . Remove the wire compartment cover screw and (Figure 6)
place the cover in a secure place (Figure 7).
NOTE: If the fan motor plug is connected to the fan housing receptacle, unplug so the blower
assembly can be completely removed.
Standard Models
2. Continuous Ventilation: Secure the electrical wires to the housing with an approved
electrical connector. For two speed fans wired for continuous ventilation, connect the White
wires of the fan to the White (Neutral) wire from the power source. Connect the ground wire
from the house to the green wire from the fan housing. Connect the Black wire of the fan
to the Black wire (Hot) from the power source. Using a properly grounded standard duplex
toggle switch (such as Leviton 5224-2W, not included) connect the Black wire from the
supply to one side of the top and bottom switch. Connect the Red wire (light) from the fan
housing to the other side of the top switch. Using a second properly grounded standard
duplex toggle switch, connect the Hot Yellow wire from the fan to the input of the switch.
Connect the second Yellow wire from the fan to the output side of the switch. Closing the
switch will change from normal to high speed (Figure 8).
NOTE: There may be more than one white fan wire that will need to be connected to the
white wire from the supply.
NOTE: The yellow wire may contain a wire crimp nut which will have to be cut off and the
wire stripped.
Motion Sensing Models
3. Secure the electrical wires to the housing with an approved electrical connector. For two
speed fans wired for continuous ventilation, connect the White wires of the fan to the White
(Neutral) wire from the power source. Connect the ground wire from the house to the green
wire from the fan housing. Connect the Black wire of the fan to the Black wire (Hot) from
the power source. The fan will operate on low speed continuously and boost to high speed
when motion is detected. Using a properly grounded standard duplex toggle switch (such
as Leviton 5224-2W, not included) connect the black wire from the supply to one side of
the top and bottom switch. Connect the red wire (light) from the fan housing to the other
side of the top switch. A manual override switch (not included) can be used to provide a
manual fan Off function (Figure 9).
NOTE: There may be more than one white fan wire that will need to be connected to the
white wire from the supply.
Humidity Sensing Models
4. Secure the electrical wires to the housing with an approved electrical connector. For two
speed fans wired for continuous ventilation, connect the White wires of the fan to the
White (Neutral) wire from the power source. Connect the ground wire from the house to
the Green wire from the fan housing. Connect the Black wire of the fan to the Black wire
(Hot) from the power source. The fan will operate on low speed continuously and boost
to high upon a rise in humidity. Using a properly grounded switch, connect 1 yellow wire
to each side of the switch. Closing the switch will change from normal to high speed.
Using a properly grounded standard duplex toggle switch (such as Leviton 5224-2W, not
included) connect the Black wire from the supply to one side of the top and bottom
switch. Connect the Red wire (light) from the fan housing to the other side of the top
switch. A manual override switch (not included) can be used to provide a manual fan Off
function (Figure 10).
NOTE: The yellow wire may contain a wire crimp nut which will have to be cut off and the
wire stripped.
Humidity and Motion Sensing Models
5. Secure the electrical wires to the housing with an approved electrical connector. For two
speed fans wired for continuous ventilation, connect the White wires of the fan to the White
(Neutral) wire from the power source. Connect the ground wire from the house to the green
wire from the fan housing. Connect the Black wire of the fan to the Black wire (Hot) from
the power source. The fan will operate on low speed continuously and boost to high speed
when motion is detected. Using a properly grounded standard duplex toggle switch (such
as Leviton 5224-2W, not included) connect the black wire from the supply to one side of
the top and bottom switch. Connect the red wire (light) from the fan housing to the other
side of the top switch. A manual override switch (not included) can be used to provide a
manual fan Off function (Figure 11).
Figure 9 Supply from house
Black
Neutral (White)
Ground (Green or Bare)
Wire Compartment
Black
Neutral (White)
Green
Switch
(by others)
Black
Red
Neutral (White)
By others
Figure 10 Supply from house
Black
Yellow
Neutral (White)
Ground (Green or Bare)
Wire Compartment
Black
Neutral (White)
Green
Yellow
Switch
(by others)
Black
Red
Neutral (White)
By others
Switch
(by others)
Figure 5
Screw
Wire
Compartment
Cover
Screw
Wire Compartment
Cover
Figure 7 NOTE: Wire compartment configuration
will be dependent on model.
Plug
Tabs
Screws
Figure 6
Figure 8 Supply from house
Black
Yellow
Neutral (White)
Ground (Green or Bare)
Wire Compartment
Black
Neutral (White)
Green
Yellow
Switch
(by others)
Black
Red
Neutral (White)
By others
Switch
(by others)


Product specificaties

Merk: Air King
Categorie: Niet gecategoriseerd
Model: EVLD

Heb je hulp nodig?

Als je hulp nodig hebt met Air King EVLD stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd Air King

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd