ACV BMV Handleiding


Lees hieronder de 📖 handleiding in het Nederlandse voor ACV BMV (48 pagina's) in de categorie Diversen klimaatbeheersing. Deze handleiding was nuttig voor 28 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/48
BMV3 / BMV4 / BMV5 : 662Y1000 • A
en
1
EN
FR
NL
ES
IT
DE
PL
RU
BMV3 / BMV4 / BMV5
BMV
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
en
2
EN
FR
NL
ES
IT
DE
PL
RU
BMV3 / BMV4 / BMV5 : 662Y1000 • A
Dear customer,
We are pleased that you have decided to purchase an ACV
burner.
The BMV burner model is a modern generation ame burner.
The advantage of this burner construction is the extensive
energy saving operation with very low emissions (Sampling
test according to EN 267:1999-11 Class 3, German environ-
mental label “Blue Angel” according to RAL-UZ 9, Sampling
test according to the Swiss Emissions Regulation LRV).
Every burner is checked in the scope of a thorough nal in-
spection. In addition to the hydraulic and electrical parame-
ters, the appearance of the ame is also inspected.
The warranty period as of the date of purchase (receipt date)
is 2 years.
Please note that the installation, start up and inspection tasks
must be accomplished by a trained technician. The installa-
tion and operating instructions that are provided contain im-
portant information to this purpose.
We recommend a yearly inspection of the burner by a trained
technician to guarantee continuous energy saving and low
emission operation.
Table of contents
1. Technical data 3
1.1 Burner performance 3
1.2 Certification 3
1.3 Operating range 3
1.4 Fuel 3
1.5 Electrical data 3
1.6 Burner dimensions 3
1.7 Acoustic emissions 3
1.8 Burner components 3
2. Assembly 4
2.1 Assembly dimensions 4
2.2 Installing the burner 4
2.3 Service position 4
2.4 Change of nozzle 4
2.5 Nozzle table 4
2.6 Combustion chamber - minimum dimensions 4
2.7 Oil supply 5
2.8 Oil pipes dimensions 5
2.9 Flexible oil line connection of the burner 6
2.10 Electrical connection 6
2.11 General inspections 6
3. Initial operating and maintenance 6
3.1 Adjusting burner 7
3.2 Chimney draft 7
3.3 Combustion air 7
3.4 Flame monitoring 7
3.5 Oil pressure 8
3.6 Final and safety tests 8
3.7 Chimney 8
4. Basic adjustment table 9
5. Electric wiring diagram : LOA24 10
6. Burner quick service 11
7. Troubleshooting 12
Figure 3 — BMV3 / BMV4
Figure 2 — BMV3 / BMV4 / BMV5
Figure 1
en
3
EN
FR
NL
ES
IT
DE
PL
RU
BMV3 / BMV4 / BMV5 : 662Y1000 • A
Figure 6
Figure 5
Figure 4
1. TECHNICAL DATA
1.1. Burner performance
Type Oil throughput (kg/h) Burner output (kW)
BMV3 1.4 - 4.1 16 - 48
BMV4 1.4 - 4.1 16 - 48
BMV 5 3.2 - 4.7 38 - 56
* Specications for units with a low pressure furnace and an exhaust
gas loss of approx. 8%.
1.2. Certification
DIN EN 267:1999-11: register number: 5G966/11
Class 3 emission limits (only HL60 E/FLV.2-S)
German ecolabel “Blue Angel according to RAL-ZU 9: Con-
tract no. 14415 (only HL60 E/FLV.2-S)
1.3. Operating range
In the chart, you nd allowed combustion chamber pressure
as function of the oil ow (see g. 4).
The operating ranges have been determined on a test-
ing unit and refer to an altitude of approx. 100 m above
sea-level and a room temperature of approx. 20°C. The
oil ow that can be achieved in practice depends on the
starting resistance of the heater.
The starting resistance is inuenced by the combustion
chamber, the ue gas line and the starting load. Exact values
can therefore only be determined on each respective system.
1.4. Fuel
Fuel oil EL according to DIN 51603-1
Heating oil EL, low sulphur, according to DIN 51603-1
Fuel oil EL A Bio 10 (bio fuel oil according to DIN SPEC
51603-6, fuel oil EL, low sulphur, with up to 10% of FAME
according to the quality requirements of DIN 14214)
1.5. Electrical data
Nominal voltage ...................................................................230 V ~ 50 Hz
Starting power ................................................................................ca. 435 W
Operating power ..............................................................ca. 135 - 235 W
Contact rating of the thermostats and switches, ......min. 6A~
1.6. Burner dimensions
Specications of dimensions in mm (see g. 5 + 6)
Packing .............................................................l 370 / w 350 / h 485 mm
Transport weight ................................................................................14.5 kg
1.7. Acoustic emissions
The sound pressure level at maximum burner performance
is 57 dB(A).
The measurements were carried out with an accuracy class
2 measuring device according to IEC 60651 at a (horizontal)
distance of 2m.
1.8. Burner components
Item Make Ref
Motor Hanning O1A095-030
Oil pump Danfoss BFP 21 L3
Oil pre-heater Danfoss FPHE 5
Ignition unit Co TRK2-40SHK
Photocell Danfoss LDS 057H7097
Automatic oil ring unit Siemens LOA 24.171B27
Pression foyer en mbar
1,00
0
0,1
0,2
0,3
0,4
0,5
0,6
2,0
BMV3 / BMV4
BMV5
3,0 4,0 5,0 6,0 7,0
Débit de oul en kg/h
Oil mass flow in kg/h
Combustion chamber pressure in mbar


Product specificaties

Merk: ACV
Categorie: Diversen klimaatbeheersing
Model: BMV

Heb je hulp nodig?

Als je hulp nodig hebt met ACV BMV stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Diversen klimaatbeheersing ACV

ACV

ACV BMR 31 Handleiding

21 Augustus 2022
ACV

ACV BMV Handleiding

21 Augustus 2022

Handleiding Diversen klimaatbeheersing

Nieuwste handleidingen voor Diversen klimaatbeheersing