ABB System Pro M DT2 Handleiding

ABB Niet gecategoriseerd System Pro M DT2

Lees hieronder de 📖 handleiding in het Nederlandse voor ABB System Pro M DT2 (64 pagina's) in de categorie Niet gecategoriseerd. Deze handleiding was nuttig voor 71 personen en werd door 2 gebruikers gemiddeld met 4.5 sterren beoordeeld

Pagina 1/64
DT1
2CSM204255R0611
DT1-K
2CSM204265R0611
DT2
2CSM204305R0611
DT2-K
2CSM204315R0611
WEEKLY DIGITAL TIME SWITCH
+ PROGRAMMING KEY
INTERRUTTORE ORARIO DIGITALE SETTIMANALE
+ CHIAVE DI PROGRAMMAZIONE
INTERRUPTEUR HORAIRE ÉLECTRONIQUE
+ CLÉ DE PROGRAMMATION
ELEKTRONISCHE WOCHENSCHALTUHR
+ PROGRAMMIERSCHLÜSSEL
INTERRUPTOR HORARIO ELECTRÓNICO
+ LLAVE DE PROGRAMACIÓN
INTERRUPTOR HORÁRIO ELECTRÓNICO
+ CHAVE DE PROGRAMAÇÃO
Электронный таймер недельный
+ ключ программирования
RU
P
E
D
F
GB
I
2CSM441016D5601
System pro M
1
Technical specifications
Product delivered with current time and date set.
Automatic change of winter/summer time .
Programming key (Ref. DT1-K and DT2-K)
- for permanent waivers,
- or program copy or save.
Programming for day or group of days.
56 program steps On/Off.
Permanent overrides On or Off ( permanent light on).
Temporary overrides On or Off ( flashing).
Display bar graph of daily profile.
Keyboard locking possible .
Programmable with power off.
Electrical characteristics
Supply voltage: 230 V AC ± 15%
Frequency: 50/60 Hz
Power consumption: max. 6 VA to 50 Hz
Output DT1, DT1-K: 1 changeover volt free contact.
Output DT2, DT2-K: 2 changeover volt free contacts.
Maximum load: AC1 µ16A 250 V~
DC1 (DT1, DT1-K) µ4A 12 V
Cos φ= 0,6 µ10A 250 V~
Minimum current: AC1 100 mA 250 V~
DC1 (DT1, DT1-K) 100 mA 12 V
Galvanic insulation between power supply and output: < 4 kV
Functional characteristics
Programming capacity: 56 steps
Minimum time between 2 steps: 1 minute
Running accuracy: ± 1,5 Sec / 24 h
Operating reserve: lithium battery provides 5 years of backup.
The product is set in standby mode (display is off) if power goes off.
It is set back in auto mode when power is back on. With power off, the screen
display is turned on when striking any key. After one minute, it is turned off.
Protection degree: IP 20
Operating temperature: -5 °C to +55 °C
Storage temperature: -20 °C to +70 °C
GB


Product specificaties

Merk: ABB
Categorie: Niet gecategoriseerd
Model: System Pro M DT2

Heb je hulp nodig?

Als je hulp nodig hebt met ABB System Pro M DT2 stel dan hieronder een vraag en andere gebruikers zullen je antwoorden




Handleiding Niet gecategoriseerd ABB

Handleiding Niet gecategoriseerd

Nieuwste handleidingen voor Niet gecategoriseerd